40
| ENGLISH
DISPLAY
PARAMETERS
DESCRIPTION
u.m. Default Min
Max
Step
HF 50
MAXIMUM
FREQUENCY
Sets the maximum operating frequency.
ATTENTION: the increase in the maximum
frequency.
compared to the nominal frequency can
cause strong overloads of the motor.
Hz
MF
MF
-10
MF
+5
1
FS 8
SWITCHING
FREQUENCY OF
MODULE
Sets the switching frequency of the power
module.
kHz
8
4
10
2
LP 0,2
LOW PRESSURE
ALARM THRESHOLD
Sets the alarm threshold for too low an
operating pressure (possibility of a broken
tube).
bar
0,2
0
10
0,1
FWS 0
FLOW SENSOR
Sets the presence/absence of the flow
sensor:
0 = sensor not present.
1 = flow sensor present.
-
0
0
1
1
2P 2.5
SECOND PRESSURE
OF SET
Sets a second value for the system pressure
(constant). To activate it configure the
parameter EI in the advanced parameters.
bar
2,5
1
9
0,1
psi
50
15
130
1,5
SET.F
RESETTING
OF FACTORY
PARAMETERS
Press the ENTER key until “OK” appears on the display, all the parameters return to
their factory settings.