background image

 

10 /  14

 

-

 

‘FUNCTIONING MOTOR’ indicator light LED; 

-

 

‘PROTECTED MOTOR’ indicator light LED; 

-

 

Buttons for motor ‘automatic –  off  – manual’ operation; 

-

 

Motor protection fuses (13); 

-

 

Auxiliary circuit protection fuse (14); 

-

 

Alarm output with N/O – C – N/C exchange contacts. Delivery 16A – 250V  

-

 

 

 

5.2 Operation of the panel with active SELF-RETENTION function 

The pumps are activated by the closing of contacts G1 and G2 and they continue to work also when G1 
and G2 are opened. The pumps only switch off when the GMIN contact is opened. 
Closing the G1 contact activates alternately pumps P1 and P2, while closing the G2 contact activates 
the second  pump (P2 if  P1 is  already working  or vice  versa). 
 
Disengaging selector (6) it is possible to exclude the LED switch on and the contact exchange on 
terminal box (8) when the GMIN contact is opened. The exclusion is useful when, with selector (1) 
engaged, the self-retention function is triggered and the activation of the GMIN opening alarm is 
unwanted. 
 
 

5.3 Operation of the panel  with excluded SELF-RETENTION function 

The G.MIN contact acquires a function of protection against dry operation and the pumps are activated 
and deactivated through the G1 and G2 controls only if the G.MIN contact is closed. 
Closing the G1 contact activates alternately pumps P1 and P2, while closing the G2 contact activates 
the second  pump (P2 if  P1 is  already working  or vice  versa). 
 
If the pumps have the 2 cables for the thermal protection of the coil, the former must be connected to 
the terminal box (2); opening of the contact blocks the motor operation and switches on the related LED 
on the panel board. If there is no integrated protection in the motor inputs T1 and T2 must be closed 
with a bond. 
 

 

6 – INSTALLATION AND ACTIVATION OF THE CONTROL PANEL FOR TWO SINGLE-STAGE PUMPS 

 
5.

 

Fix the panel to a wall by means of appropriate screws and dowels, using the ports on the box; 
the  panel must be installed in a closed, ventilated environment, in which there are no dust, 
acids, corrosive and/or inflammable  gases. The room temperature must be  b4°C and 
+40°C. 

6.

 

Set up the electrical connections as shown in the attached diagram, making sure that the power 
supply voltage is appropriate for the panel and the motor-driven pump (230V±10% 50/60Hz). 

7.

 

Remove any plastic or metal impurity (e.g. copper fragments from the cables, plastic slivers, dust, 
etc.) inside the box and power the panel. On the front board the green ‘LIVE’ LED switches on 

8.

 

Calibrate the overload protection pursuant to the paragraph below. 

 

 
7 – CALIBRATION OF THE OVERLOAD PROTECTION TRIGGERING CURRENT 

 

The control panel is equipped with an adjustable electronic protection which allows, when the current value is 
adequately set, to obtain in all cases the ideal protection for the motor-driven pump. 
 
In order to calibrate the protection follow the procedure below: 

-

 

Check that selectors (8) and (9) are activated, so that the delay of amperometric protection operation 
is zeroed. 

-

 

Move the potentiometers (5) clockwise and set the maximum value; 

-

 

Start up with the manual control pump P1 and move the related potentiometer counterclockwise until 
the red ‘PROTECTED MOTOR’ LED on the front panel board switches on and the motor turns off. 

-

 

Increase the current value so obtained by 10÷20%. 

-

 

Start up with the manual control pump P2 and move the related potentiometer counterclockwise until 
the red ’PROTECTED MOTOR’ LED on the front panel board switches on and the motor turns off. 

-

 

Increase the current value so obtained by 10÷20%. 

-

 

Deactivate selectors (8) and (9) if you want to set a delay time equal to around 5 seconds in the 
amperometric protection operation. 

Summary of Contents for SAR100

Page 1: ...STAZIONI AUTOMATICHE PER L ACCUMULO ED IL SOLLEVAMENTO DI ACQUE REFLUE AUTOMATIC STATIONS FOR WASTE WATER COLLECTING AND LIFTING MANUALE DI INSTALLAZIONE E D USO INSTALLATION AND USE MANUAL Ed 01 Rev...

Page 2: ...2 14 INDEX ITALIANO pag 3 ENGLISH page 8 LEGENDA KEY page 13...

Page 3: ...per la discesa delle pompe solo per VX I prolunga da 300 mm per l apertura del serbatoio opzionale quadro di comando quadro autoalimentato con sirena e lampeggiante e galleggiante di allarme opzionale...

Page 4: ...camente un ispezione ed eventualmente la pulizia della valvola di non ritorno e dell aspirazione della pompa asportando ogni corpo estraneo o residuo che possa impedire il corretto funzionamento dell...

Page 5: ...INSTALLAZIONE E MESSA IN FUNZIONE DEL QUADRO DI COMANDO PER 2 POMPE MONOFASE 1 Fissare il quadro ad una parete tramite viti e tasselli adeguati ed utilizzando i fori predisposti sulla scatola il quad...

Page 6: ...90dB Lampada lampeggiante rossa 12Vcc 3W Batteria tampone interna 12Vcc 1 2Ah Uscita con contatti puliti in Scambio N A C N C 250V 10 A 9 INSTALLAZIONE E MESSA IN FUNZIONE DEL QUADRO DI ALLARME 1 Fiss...

Page 7: ...e spegne l allarme dopo il tempo impostato con il trimmer 8 Il led rosso sul pannello frontale del quadro rimane comunque acceso a segnalare che l anomalia non stata risolta E consigliabile verificare...

Page 8: ...pipes for pump lowering only for VX I 300 metre extension for reservoir opening optional control panel self powered panel with horn flashing light and alarm float optional 1 WARNINGS AND SAFETY 8 Rea...

Page 9: ...clean the non return valve and the pump induction valve removing any foreign body or residue that may prevent the correct operation of the system Also check that the floats may move freely It is sugg...

Page 10: ...STALLATION AND ACTIVATION OF THE CONTROL PANEL FOR TWO SINGLE STAGE PUMPS 5 Fix the panel to a wall by means of appropriate screws and dowels using the ports on the box the panel must be installed in...

Page 11: ...the panel must be installed in a closed ventilated environment in which there are no dust acids corrosive and or inflammable gases The room temperature must be between 4 C and 40 C 7 Set up the elect...

Page 12: ...ation of the panel by pushing the TEST button 10 DECLARATION OF COMPLIANCE PEDROLLO S p A declares under its own liability that the Q2EPT TA series panels are compliant with the following European reg...

Page 13: ...13 14...

Page 14: ...14 14...

Reviews: