B. SPECIFICATIONS OF CONCRETE
Specifications of concrete must be adhere to the specifications as
following. Failure to do so may result in lift and/or vehicle falling.
1. Concrete must be thickness 100mm minimum and without reinforcing steel bars
,
and must be dried completely before lift installation.
2. Concrete must be of test strength 210kg/cm
2
minimum.
C. POWER SUPPLY
The power capacity must be more than 2.2kw, The source cable size must be
2.5mm² and in good condition of contacting with floor.
III.STEPS OF INSTALLATION
A. Check the parts before assembly to make sure all the parts are completed.
1. Packaged cargo( lift, drive-in ramp, Parts box, control cabinet). Move the parts
aside, open the outer packing and check the parts according to the shipment parts
list.
see Fig.3
Fig.3