WaveStar Color Monitor_____________________________________________________________
Ctrl Nr: PM375103 Revision: 003
48
Appendix: Color Monitor Backpanel
The Color Monitor backpanel has these connections:
•
Power connections: 120V AC, 230V AC, and 24VDC (230V is optional and requires a
different transformer.)
•
Modbus connections:
o
Downstream (to Monitor device chain) is always 4-wire Modbus
o
Upstream is 4-wire or 2-wire, jumper selected
•
Summary Alarm: Dry contact (NO) signals when the Monitor has an alarm condition. Dry
contact specification: 0.5A at 120VAC or 30VDC.
The backpanel also has a RESET button: If the Monitor hangs, you can reset it by pressing this
button.
Replaceable parts:
•
Fuse: 200 mA, 250V; replace fuse with a UL recognized, IEC compliant fuse of the same
type.
•
Battery: Lithium ion, Panasonic-BSG (CR2477), 3V, 1 AH (PDI Part Number 15174)
Caution:
The battery used in this device may present a risk of fire or chemical burn hazard if
mistreated. Do not recharge, disassemble, heat above 100°C (212°F) or incinerate. Replace
Summary alarm dry contact (NO)
RESET button
Modbus
Upstream
Connectors
Modbus
Down-
stream
Connectors
J6:
24VDC
Input
J5: AC
120V/
230V*
Input
Fuse
Transformer (*Note: AC 230V is optional and requires a
different transformer.)
Battery
J11 Ethernet port
Figure 38 Color Monitor Backpanel