WaveStar Color Monitor_____________________________________________________________
Ctrl Nr: PM375103 Revision: 003
34
Figure 29 Readings: BCMS IEC Panelboard
Touch
BCMS IEC
device name in the device name list.
Device name turns blue when selected and device name
displays in header. (Device name can be changed in
SETTINGS.
)
Touch
READINGS
to see BCMS IEC panelboard power
monitoring data in three screens.
Panelboard Individual Circuits
Instantaneous Measurements:
NO
= circuit number (scroll through 42 circuits)
AMPS
= Amperes
KW
= Kilowatts
KVA
= kilovolt-amperes
KVAR
= kilovolt-amperes reactive
PF
= power factor
KWH
= Kilowatt Hours
Panelboard Circuits, Measurements and
Alarms:
NO
= Circuit Number
AMPS
= Amperes
CB
= Circuit breaker rating (Amps)
MIN
= Lowest current read
MAX
= Highest current read
ZERO
: OK = Current has not dropped to 0
since last reset; ACTIVE = Current has read 0
after having read a minimum current
WARNING
: OK = No warning outstanding;
ACTIVE = warning outstanding
ALARM
: OK = No alarm outstanding; ACTIVE
= Alarm is outstanding
Panelboard totals, instantaneous
measurements:
Voltage AB, BC, etc., to panelboard with THD
(Total Harmonic Distortion %) by phase:
Voltage
source
Frequency
Panelboard totals instantaneous power
measurements
by phases ABC and total:
KW
KVA
KVAR
PF
Panelboard cumulative reading:
KWH
to panelboard as whole
Clear
= Reset KWH to 0.