© PCE Instruments
2
Specifications
2.1
Technical specifications
Operating conditions
0 … +50 °C, <75 % RH
Storage conditions
-
20 … +60 °C, <80 % RH
Backlight
Blue
Battery
7.4 V Polymer Li-Ion battery
Battery warning
is indicated if the battery voltage is
below operating level
External power supply / charger
9 V 0.5 A mains adaptor
Automatic shutdown
After 30 minutes of inactivity
Overload
Displayed by “OL” or “-OL”
Dimensions
206 x 95 x 45 mm
Weight
435 g
2.2
Technical specifications for pressure
Pressure connections
7/16
” UNF
Measurement range
-
14 … +500 psi
-
96 … +4000 kPa
-0.
96 … +34.47 bar
-28.
5 … +1018.0 inHg
-
72 … 2585 cmHg
Resolution
0.1 psi / inHg
1 kPa / cmHg
Accuracy at 25 °C, <75% RH
-
29 … 0 inHg: ±0.2 inHg
-
74 … 0 cmHg: ±0.4 cmHg
0 … 200 psi: ±1 psi
0 … 1378 kPa: ±7 kPa
200 … 500 psi: ±0.3 % + 1 psi
1378 … 3447 kPa: ±0.3 % + 7 kPa
Maximum overload
800 psi
Units
psi, kPa, inHg, cmHg
2.3
Temperature T1 / T2
Type of sensor
K-type thermocouple
Measurement range
-
60 … +537 °C
Resolution
0.1 °C
Accuracy
±0.5 °C at -
60 … +93 °C
±1 °C at +93 … +537 °C
2.4
Ambient temperature
Type of sensor
NTC
Measurement range
0 … +50 °C
Resolution
0.1 °C
Accuracy
±0.5 °C