Payne PA3P042 Installation Instructions Manual Download Page 7

7

3. Attach each of the 4 metal rigging brackets under the panel

rain lip (See Fig. 5). Use the screws removed in step 2 above

to secure the brackets to the unit.

PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in personal

injury/death or property damage.
Rigging bracket MUST be under the rain lip to provide

adequate lifting.

!

WARNING

PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in personal

injury/death or property damage.
Do not strip screws when re--securing the unit. If a screw is

stripped, replace the stripped one with a larger diameter screw

(included).

!

WARNING

Rigging/Lifting of Unit

1. Bend top of brackets down approximately 30 degrees from

the corner posts.

2. Attach straps of equal length to the rigging brackets at

opposite ends of the unit. Be sure straps are rated to hold the
weight of the unit (See Fig. 5).

3. Attach a clevis of sufficient strength in the middle of the

straps. Adjust the clevis location to ensure unit is lifted level

with the ground.

4. After unit is securely in place detach rigging straps. Remove

corner posts screws, and rigging brackets then reinstall

screws.

UNIT FALLING HAZARD

Failure to follow this warning could result in personal

injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36

inches above the unit top cover.

!

WARNING

After the unit is placed on the roof curb or mounting pad, remove

the top crating.

Step 6—Connect Condensate Drain

NOTE

: When installing condensate drain connection be sure to

comply with local codes and restrictions.

Model PA3P disposes of condensate water through a 3/4 in. NPT
fitting which exits through the base on the evaporator coil access

side. See Fig. 2 & 3 for location.
Condensate water can be drained directly onto the roof in rooftop

installations (where permitted) or onto a gravel apron in ground

level installations. Install a field--supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that

the outlet of the trap is at least 1 in. lower than the drain pan
condensate connection to prevent the pan from overflowing (See

Fig. 8). When using a gravel apron, make sure it slopes away from
the unit.
Connect a drain tube using a minimum of 3/4 --in. PVC or 3/4 --in.

copper pipe (all field--supplied) at the outlet end of the 2--in. trap. Do
not undersize the tube. Pitch the drain tube downward at a slope of

at least 1--in. for every 10 ft of horizontal run. Be sure to check the

drain tube for leaks. Prime trap at the beginning of the cooling
season start--up.

1” (25mm) MIN.

2” (50mm) MIN.

TRAP

OUTLET

C99013

Fig. 8 -- Condensate Trap

Step 7—Install Duct Connections

The design and installation of the duct system must be in accordance

with the standards of the NFPA for installation of non--residence
type air conditioning and ventilating systems, NFPA 90A or

residence type, NFPA 90B and/or local codes and ordinances.
Select and size ductwork, supply--air registers, and return air grilles

according to ASHRAE (American Society of Heating,

Refrigeration, and Air Conditioning Engineers) recommendations.
The unit has duct flanges on the supply-- and return--air openings on

the side of the unit.
When designing and installing ductwork, consider the following:

1. All units should have field--supplied filters or accessory filter

rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.

2. Avoid abrupt duct size increases and reductions. Abrupt

change in duct size adversely affects air performance.

IMPORTANT

: Use flexible connectors between ductwork and

unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather--tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24--in.
from electric heater element.

3. Size ductwork for cooling air quantity (cfm). The minimum

air quantity for proper electric heater operation is listed in
Table 2. Heater limit switches may trip at air quantities below
those recommended.

4. Seal, insulate, and weatherproof all external ductwork. Seal,

insulate and cover with a vapor barrier all ductwork passing

through conditioned spaces. Follow latest Sheet Metal and
Air Conditioning Contractors National Association

(SMACNA) and Air Conditioning Contractors Association
(ACCA) minimum installation standards for residential
heating and air conditioning systems.

5. Secure all ducts to building structure. Flash, weatherproof,

and vibration--isolate duct openings in wall or roof

according to good construction practices.

CONFIGURING UNITS FOR DOWNFLOW (VERTICAL)

DISCHARGE

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before performing service or maintenance operations on the

system, turn off main power to unit and install lockout tag.

!

WARNING

1. Open all electrical disconnects and install lockout tag before

starting any service work.

PA

3P

Summary of Contents for PA3P042

Page 1: ...ter Piston 18 TROUBLESHOOTING 18 START UP CHECKLIST 18 A05120 Fig 1 Unit PA3P SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical compo...

Page 2: ...that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a nor...

Page 3: ...UIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTR...

Page 4: ...S INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 10...

Page 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM PA3P024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 6: ...l UNIT FALLING HAZARD Failure to follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is e...

Page 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Page 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Page 9: ...the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor contactor 6 Connect...

Page 10: ...al box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component...

Page 11: ...gerant charge is not required unless the unit is suspected of not having the proper R 22 charge A superheat charging chart is attached to the outside of the service access panel The chart includes the...

Page 12: ...511 496 478 460 439 CFM 1526 1482 1437 1398 1344 1281 1205 1125 1029 High Watts 765 746 730 709 690 664 642 624 600 CFM 1860 1805 1751 1685 1620 1541 1468 1370 1265 50SD048 Low Watts 627 617 607 584 5...

Page 13: ...13 A07034 Fig 13 Wiring Diagram 208 230 1 60 PA3P...

Page 14: ...14 A07035 Fig 14 Wiring Diagram 208 230 3 60 PA3P...

Page 15: ...15 A07037 Fig 15 Wiring Diagram 460 3 60 PA3P...

Page 16: ...onnect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and com...

Page 17: ...onomy andcontinuing efficiency clean accumulated dirt and grease from the blower wheel and motor annually ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or deat...

Page 18: ...ssemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper...

Page 19: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Page 20: ...ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERAT...

Reviews: