Payne PA3P042 Installation Instructions Manual Download Page 12

12

Table 3—Wet Coil Air Delivery* — Horizontal Discharge

(Deduct 10% for 208--Volt Operation)

Unit

Motor

Speed

External Static Pressure (in. wc)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

50SD024

Low

1

Watts

311

309

304

301

286

290

286

280

--- --- --- --- ---

CFM

935

885

820

757

686

583

423

263

--- --- --- --- ---

Medium

Watts

411

405

398

390

379

357

357

345

327

CFM

1195

1155

1100

1028

957

868

769

647

365

High

Watts

528

518

509

492

477

467

447

435

421

CFM

1484

1421

1368

1279

1185

1088

970

853

712

50SD030

Low

Watts

311

309

304

301

286

290

286

280

--- --- --- --- ---

CFM

935

885

820

757

686

583

423

263

--- --- --- --- ---

Medium

1

Watts

411

405

398

390

379

357

357

345

327

CFM

1195

1155

1100

1028

957

868

769

647

365

High

Watts

528

518

509

492

477

467

447

435

421

CFM

1484

1421

1368

1279

1185

1088

970

853

712

50SD036

Low

Watts

439

429

415

401

395

380

356

339

329

CFM

1242

1170

1089

994

917

837

702

570

442

Medium

1

Watts

503

491

479

461

450

436

418

404

389

CFM

1320

1244

1162

1081

1005

897

767

662

541

High

Watts

641

627

623

609

601

588

571

559

548

CFM

1362

1288

1205

1119

1033

933

826

714

580

50SD042

Low

Watts

434

428

422

403

404

390

375

360

344

CFM

1282

1241

1206

1160

1109

1040

967

890

813

Medium

1

Watts

560

548

535

526

511

496

478

460

439

CFM

1526

1482

1437

1398

1344

1281

1205

1125

1029

High

Watts

765

746

730

709

690

664

642

624

600

CFM

1860

1805

1751

1685

1620

1541

1468

1370

1265

50SD048

Low

Watts

627

617

607

584

567

548

528

503

480

CFM

1550

1530

1493

1461

1414

1361

1320

1250

1177

Medium

1

Watts

771

755

734

711

690

665

639

607

572

CFM

1798

1771

1734

1687

1645

1595

1530

1449

1355

High

Watts

969

941

908

887

858

827

804

767

748

CFM

2124

2071

2000

1944

1876

1811

1735

1647

1555

50SD060

Low

1

Watts

786

769

754

736

722

705

684

658

616

CFM

2027

1960

1901

1821

1759

1693

1616

1513

1354

Medium

Watts

873

849

833

815

798

782

763

748

704

CFM

2095

2026

1962

1887

1817

1748

1679

1583

1439

High

Watts

1012

993

981

963

948

927

904

886

846

CFM

2184

2109

2036

1963

1886

1812

1729

1647

1496

*Air delivery values are without air filter and are for dry coil (see Wet Coil Pressure Drop table).

1

Factory--shipped cooling speed

“NA” = Not allowed for heating speed

Table 4—

PA3P Wet Coil Pressure Drop

UNIT SIZE

STANDARD CFM (S.C.F.M.)

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

024

0.030

0.037

0.044

0.053

0.063

--

--

--

--

--

--

--

--

--

--

030

--

0.037

0.044

0.053

0.063

0.072

0.081

0.105

--

--

--

--

--

--

--

036

--

--

--

0.05

0.061

0.072

0.08

0.09

0.11

--

--

--

--

--

--

042

--

--

--

--

0.044

0.051

0.059

0.065

0.072

0.080

0.088

0.095

0.105

--

--

048

--

--

--

--

--

--

0.044

0.050

0.053

0.059

0.066

0.072

0.077

0.086

--

060

--

--

--

--

--

--

--

--

--

0.079

0.087

0.095

0.102

0.113

0.123

PA

3P

Summary of Contents for PA3P042

Page 1: ...ter Piston 18 TROUBLESHOOTING 18 START UP CHECKLIST 18 A05120 Fig 1 Unit PA3P SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical compo...

Page 2: ...that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a nor...

Page 3: ...UIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTR...

Page 4: ...S INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 10...

Page 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM PA3P024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 6: ...l UNIT FALLING HAZARD Failure to follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is e...

Page 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Page 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Page 9: ...the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor contactor 6 Connect...

Page 10: ...al box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component...

Page 11: ...gerant charge is not required unless the unit is suspected of not having the proper R 22 charge A superheat charging chart is attached to the outside of the service access panel The chart includes the...

Page 12: ...511 496 478 460 439 CFM 1526 1482 1437 1398 1344 1281 1205 1125 1029 High Watts 765 746 730 709 690 664 642 624 600 CFM 1860 1805 1751 1685 1620 1541 1468 1370 1265 50SD048 Low Watts 627 617 607 584 5...

Page 13: ...13 A07034 Fig 13 Wiring Diagram 208 230 1 60 PA3P...

Page 14: ...14 A07035 Fig 14 Wiring Diagram 208 230 3 60 PA3P...

Page 15: ...15 A07037 Fig 15 Wiring Diagram 460 3 60 PA3P...

Page 16: ...onnect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and com...

Page 17: ...onomy andcontinuing efficiency clean accumulated dirt and grease from the blower wheel and motor annually ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or deat...

Page 18: ...ssemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper...

Page 19: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Page 20: ...ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERAT...

Reviews: