Payne PA3P042 Installation Instructions Manual Download Page 16

16

A05109v2

Fig. 16 -- Cooling Charging Chart

Airflow can be changed by changing the lead connections of the
blower motor.
All PA3P units are factory wired for low speed.
FOR 208/230v
For color coding on the 208/230v motor leads, see Table 5.

Table 5—

Color Coding for 208/230v Motor Leads

Black = High Speed

Blue = Medium Speed

Red = Low Speed

To change the speed of the indoor fan motor (IFM), remove the fan

motor speed leg lead from the time delay relay (TDR). This wire is
attached to terminal--3 of TDR for 3--phase units. To change the

speed, remove and replace with lead for desired blower motor speed.
Insulate the removed lead to avoid contact with chassis parts.
COOLING SEQUENCE OF OPERATION
With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence of

operation is as follows:
When the room temperature rises to a point that is slightly above the

cooling control setting of the thermostat, the thermostat completes
the circuit between thermostat terminal R to terminals Y and G.

These completed circuits through the thermostat connect contactor

coil (C) (through unit wire Y) and time delay relay (TDR) (through
unit wire G) across the 24--v secondary of transformer (TRAN).
The normally open contacts of energized contactor (C) close and
complete the circuit through compressor motor (COMP) to

condenser (outdoor) fan motor (OFM). Both motors start instantly.
The set of normally open contacts of energized relay TDR close and
complete the circuit through evaporator blower (indoor) fan motor

(IFM).

NOTE

: Once the compressor has started and then has stopped, it

should not be started again until 5 minutes have elapsed.
The cooling cycle remains on until the room temperature drops to

a point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat breaks the circuit between

thermostat terminal R to terminals Y and G. These open circuits
deenergize contactor coil C and relay coil TDR. The condenser and

compressor motors stop. After a 30--second delay, the blower motor

stops. The unit is in a standby condition, waiting for the next call for
cooling from the room thermostat.

MAINTENANCE

To ensure continuing high performance, and to minimize the

possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This cooling unit should be

PA

3P

Summary of Contents for PA3P042

Page 1: ...ter Piston 18 TROUBLESHOOTING 18 START UP CHECKLIST 18 A05120 Fig 1 Unit PA3P SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical compo...

Page 2: ...that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a nor...

Page 3: ...UIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTR...

Page 4: ...S INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 10...

Page 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM PA3P024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 6: ...l UNIT FALLING HAZARD Failure to follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is e...

Page 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Page 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Page 9: ...the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor contactor 6 Connect...

Page 10: ...al box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component...

Page 11: ...gerant charge is not required unless the unit is suspected of not having the proper R 22 charge A superheat charging chart is attached to the outside of the service access panel The chart includes the...

Page 12: ...511 496 478 460 439 CFM 1526 1482 1437 1398 1344 1281 1205 1125 1029 High Watts 765 746 730 709 690 664 642 624 600 CFM 1860 1805 1751 1685 1620 1541 1468 1370 1265 50SD048 Low Watts 627 617 607 584 5...

Page 13: ...13 A07034 Fig 13 Wiring Diagram 208 230 1 60 PA3P...

Page 14: ...14 A07035 Fig 14 Wiring Diagram 208 230 3 60 PA3P...

Page 15: ...15 A07037 Fig 15 Wiring Diagram 460 3 60 PA3P...

Page 16: ...onnect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and com...

Page 17: ...onomy andcontinuing efficiency clean accumulated dirt and grease from the blower wheel and motor annually ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or deat...

Page 18: ...ssemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper...

Page 19: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Page 20: ...ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERAT...

Reviews: