Payne PA3P042 Installation Instructions Manual Download Page 1

1

Installation Instructions

PA3P

SINGLE--PACKAGED AIR CONDITIONER SYSTEM

WITH R--22 REFRIGERANT

2 TO 5 NOMINAL TONS (SIZES 024--060) 1 & 3 PHASE

NOTE

: Read the entire instruction manual before starting the

installation.

NOTE

: Installer: Make sure the Owner’s Manual and Service

Instructions are left with the unit after installation.

TABLE OF CONTENTS

Page

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RECEIVING AND INSTALLATION

2--9

. . . . . . . . . . . . . . . . .

Check Equipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Identify Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspect Shipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Unit Support

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Roof Curb

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Slab Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Ground Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Clearances

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Field Fabricate Ductwork

2

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Rig and Place Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspection

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Use of Rigging Bracket

6

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Connect Condensate Drain

7

. . . . . . . . . . . . . . . . . . . . . . . . . .

Install Duct Connections

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Configuring Units for Downflow (Vertical) Discharge

7

. . . . .

Install Electrical Connections

8

. . . . . . . . . . . . . . . . . . . . . . . .

High--Voltage Connections

9

. . . . . . . . . . . . . . . . . . . . . . . .

Special Procedures for 208v Operation

9

. . . . . . . . . . . . . . .

Control Voltage Connections

9

. . . . . . . . . . . . . . . . . . . . . . .

Standard Connection

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Transformer Protection

9

. . . . . . . . . . . . . . . . . . . . . . . . . . .

PRE--START--UP

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP

11--16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check for Refrigerant Leaks

11

. . . . . . . . . . . . . . . . . . . . . . . .

Start--Up Adjustments

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checking Cooling Control Operation

11

. . . . . . . . . . . . . . .

Checking and Adjusting Refrigerant Charge

11

. . . . . . . . . .

Indoor Airflow and Airflow Adjustments

11

. . . . . . . . . . . .

Cooling Sequence of Operation

16

. . . . . . . . . . . . . . . . . . . .

MAINTENANCE

16--18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Filter

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Blower and Motor

17

. . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

17

. . . .

Outdoor Fan

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Controls and Wiring

18

. . . . . . . . . . . . . . . . . . . . . .

Refrigerant Circuit

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Airflow

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Metering Devices–AccuRater

®

Piston

18

. . . . . . . . . . . . . . . .

TROUBLESHOOTING

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP CHECKLIST

18

. . . . . . . . . . . . . . . . . . . . . . . . . . .

A05120

Fig. 1 -- Unit PA3P

SAFETY CONSIDERATIONS

Installation and servicing of this equipment can be hazardous due to

mechanical and electrical components. Only trained and qualified

personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such

as cleaning and replacing air filters. All other operations must be
performed by trained service personnel. When working on this

equipment, observe precautions in the literature, on tags, and on

labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. Installation must be in compliance with
local and national building codes. Wear safety glasses, protective

clothing, and work gloves. Have fire extinguisher available. Read
these instructions thoroughly and follow all warnings or cautions

included in literature and attached to the unit.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or manuals,

be alert to the potential for personal injury. Understand these signal

words: DANGER, WARNING, and CAUTION. These words are
used with the safety--alert symbol. DANGER identifies the most se-

rious hazards which

will

result in severe personal injury or death.

WARNING signifies hazards which

could

result in personal injury

or death. CAUTION is used to identify unsafe practices which

may

result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which

will

result in en-

hanced installation, reliability, or operation.

Summary of Contents for PA3P042

Page 1: ...ter Piston 18 TROUBLESHOOTING 18 START UP CHECKLIST 18 A05120 Fig 1 Unit PA3P SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical compo...

Page 2: ...that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a nor...

Page 3: ...UIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTR...

Page 4: ...S INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 10...

Page 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM PA3P024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 6: ...l UNIT FALLING HAZARD Failure to follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is e...

Page 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Page 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Page 9: ...the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor contactor 6 Connect...

Page 10: ...al box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component...

Page 11: ...gerant charge is not required unless the unit is suspected of not having the proper R 22 charge A superheat charging chart is attached to the outside of the service access panel The chart includes the...

Page 12: ...511 496 478 460 439 CFM 1526 1482 1437 1398 1344 1281 1205 1125 1029 High Watts 765 746 730 709 690 664 642 624 600 CFM 1860 1805 1751 1685 1620 1541 1468 1370 1265 50SD048 Low Watts 627 617 607 584 5...

Page 13: ...13 A07034 Fig 13 Wiring Diagram 208 230 1 60 PA3P...

Page 14: ...14 A07035 Fig 14 Wiring Diagram 208 230 3 60 PA3P...

Page 15: ...15 A07037 Fig 15 Wiring Diagram 460 3 60 PA3P...

Page 16: ...onnect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and com...

Page 17: ...onomy andcontinuing efficiency clean accumulated dirt and grease from the blower wheel and motor annually ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or deat...

Page 18: ...ssemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper...

Page 19: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Page 20: ...ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERAT...

Reviews: