![Pavone Systems DAT 100 Technical Manual Download Page 6](http://html.mh-extra.com/html/pavone-systems/dat-100/dat-100_technical-manual_763998006.webp)
Page 4
TECHNICAL FEATURES
Power supply
24 Vdc ±10% protected against reverse polarity.
Protection with resettable fuse.
Max. absorption
2W
Isolation
Class II
Operating temperature
-10°C ÷ +50°C (max. humidity 85% non-condensing)
Storage temperature
-20°C ÷ +60°C
Weight display
Numerical with 5 red led digits and 7 segments (h 7
mm)
Led
2 LEDs of 3 mm
Keyboards
3 mechanical keys (behind the red front door)
Overall dimensions
112 x 119 x 23 mm (l x h x w), including terminal
boards.
Installation
Brackets for DIN section or OMEGA bar
Material
Self-extinguishing Blend PC/ABS
Connections
Removable terminal boards with screws, pitch 5.08
mm
Input of the load cells with following features max. 4 of 350 Ω in parallel (or 8 cells of 700 Ω).
Load cell excitation
4 Vdc
Linearity
<0.01% of the full scale
Temperature drift
<0.001% of the full scale / °C
Internal resolution
24 bit
Measuring range
-3.9 ÷ +3.9 mV/V
Digital filter
To be selected from 0.2 Hz to 25 Hz
Number of decimals weight
0 ÷ 4 decimal places
Calibration of zero and full scale
From the buttons.
Check of load cell cable interruption
Always present
Logic outputs (DAT 100/A)
2 relay outputs with No contact
Relay load Max. 1A, 24 Vdc/Vca
Logic Inputs (DAT 100/A)
No. 2 opto-isolated
Serial ports
RS232 half duplex
RS485 half duplex (DAT 100/RS485)
Baud rate
2400 ÷ 115200 baud
Maximum cable length
15m (RS232) and 1000m (RS485)
Analog output (DAT 100/A)
Voltage: ± 10 V / ± 5 V (min. 10 KΩ)
Current: 0÷20 mA / 4÷20 mA (max 300 Ω)
Resolution
16 bits
Calibration
Digital from keys
Linearity
0.03% of the full scale
Temperature drift
0.002% of the full scale / °C
In compliance with the standards
EN61000-6-2, EN61000-6-3 for EMC
EN61010-1 for Electrical Safety
UL: FILE NO E474362
Summary of Contents for DAT 100
Page 2: ...Page II ...