background image

  Gemini™ Twin-Fuel Gas-Fired Boiler 

 

4.4.5  Gas Pressure Adjustment 

 
 

Increase

Decrease

 

Figure 4-7  Regulator 

 
 

The gas pressure is set initially during a factory fire-
test.  A final adjustment must be made after the boiler 
has been installed, as follows: 

See rating plate for the minimum and maximum gas 
pressure of the boiler.   

Each boiler is furnished with three plugged taps in the 
gas train for test gauge connections.  Two taps are lo-
cated at the natural gas and propane manual shutoff 
valves and are for measuring the gas supply pressure 
(1/4" I.P.S.).  The supply pressure during main burner 
operation must be greater than the minimum indicated 
on the rating plate (6 inches W.C. for natural gas, 6 
inches W.C. for propane).  The remaining tap is lo-
cated downstream from the secondary manual shutoff 
valve at the elbow where the gas line enters the back 
of the cabinet and is for measuring the manifold gas 
pressure (1/8" I.P.S.). 

If a replacement Lo-Hi-Lo actuator is required, follow 
manufacturer's instructions and pre-set the "Lo" fire 
setting of the actuator the same as the original actua-
tor.  This must be performed by qualified service per-
sonnel. 

To adjust gas pressure, first connect an appropriate 
pressure-sensing device at the manifold tap, then re-
move seal cap from regulator.  Turn adjusting screw 
clock-wise to increase pressure, counter-clockwise to 
decrease pressure.  The manifold gas pressure on the 

"Rating Plate," affixed to the back of the cabinet, is 
provided only as a guide to the proper setting.  The 
manifold gas pressure indicated on the "Factory Fire-
test" label (affixed to the back of the cabinet) should 
be used to achieve the proper firing rate of the 
individual boiler as installed.  Replace seal cap after 
adjustment. 
 
 

 

4

 

.4.6  Leak Testing of Valves 

Annually test for by-pass leaks on all motorized gas 
valves.  If gas flows when the motorized gas valve is 
closed it is defective. 

 
 

downstream
leak test
valve

upstream
leak test
valve

motorized gas
valve (natural
gas)

motorized gas
valve (propane)

secondary
shutoff

to burner

secondary 
motorized
gas valve

 

 

 

 

 

Figure 4-8  Leak Testing of Valves 

 

Each branch of the gas train must be tested separately, 

s follows: 

a

 
1. 

Open

 the natural gas connection manual shutoff.  

Close

 the propane connection manual shutoff.  

(Refer to Figure 4-1.)  

2.  Close the secondary shutoff (downstream of all 

motorized valves). 

3.  Attach a short piece of hose to the 

downstream

 

 
 

- 10 - 

 

Summary of Contents for TBIG-03

Page 1: ...ER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S...

Page 2: ...5 1 2 Starting System 13 5 2 Lighting and Shut Down Procedures 13 5 2 1 Lighting Procedures 13 5 2 2 Normal Shut Down Procedures 14 5 2 3 Emergency Shut Down 14 5 3 Switchover to Propane Operation 14...

Page 3: ...gas fired boiler allows the boiler to be fired by propane in the event that the supply of natural gas is temporarily interrupted or restricted The necessary fittings valves piping and controls for twi...

Page 4: ...r must be Installed by qualified personnel in accordance with designs prepared by qualified facility engi neers including structural mechanical electrical and other applicable disciplines Operated and...

Page 5: ...ime Con tact Patterson Kelley at 570 421 7500 for replace ment labels 3 5 SAFETY PRECAUTIONS Provide a suitable location for the boiler away from normal personnel traffic with adequate working space a...

Page 6: ...Check entire gas train for leaks after installation If there is a smell of gas shut down the boiler and obtain immediate assistance from trained service personnel and or your local fire department Ov...

Page 7: ...t valves n o vent valve I R I only Figure 4 1 Piping Schematic for the Twin Fuel Gas Train 4 0 INSTALLATION Gas Train Connection Sizes Natural Gas Propane 700 1000 1200 Series 1 1 4 1 1500 1700 2000 S...

Page 8: ...n either the natural gas or propane supply a suitable intermediate gas pressure regulator of the lock up type must be provided to reduce the pressure to less than 14 inches W C All boilers are designe...

Page 9: ...d devices as shown above 4 3 PRE START CHECK LIST Before firing the boiler make sure the following items have been completed 1 Flue gas from the boiler is properly vented 2 Gas connections have been m...

Page 10: ...block on the control panel Disconnect ing this wire disables the main gas valve ensuring that gas cannot flow during the test 2 Turn on the circulating water pump With the natural gas shutoff and sec...

Page 11: ...rating turn down the temperature setting on the high limit thermostat until the main burner shuts off The high limit switch must be reset manually after testing This check should also be made for the...

Page 12: ...be performed by qualified service per sonnel To adjust gas pressure first connect an appropriate pressure sensing device at the manifold tap then re move seal cap from regulator Turn adjusting screw c...

Page 13: ...is OK If there are bubbles replace the valve 5 Attach the hose to the upstream leak test valve 6 Open the upstream leak test valve and check for bubbles in the hose If there are no bubbles the natural...

Page 14: ...anical link to air control auxiliary panel service power shutoff switch inside auxiliary panel service power shutoff switch inside propane low pressure switch pressure tap secondary shutoff high gas p...

Page 15: ...been under water Immediately call a qualified service technician to in spect the boiler and to replace any part of the control system and any gas control which has been under wa ter 5 2 LIGHTING AND...

Page 16: ...the gas supplies remote from the boiler 5 3 SWITCHOVER TO PROPANE OPERATION Switchover from natural gas to propane is made manually as follows 1 Turn the fuel selector switch located on the main contr...

Page 17: ...y Figure 7 1 Piping Schematic for the Twin Fuel Gas Train 7 0 MAINTENANCE 7 1 GENERAL Warning High voltage Shock hazard Properly lock out tagout the electrical service and all other energy sources bef...

Page 18: ...or marked Heat 6 The programmer first energizes Terminal 4 which supplies power to the contactor for the blower mo tor and the air flow switch which initially shows low air flow with the LowAir indica...

Page 19: ...operating control switch will close again The operating sequence will re cycle to step 5 provided that the limits on water flow gas pressure and high temperature are all met 8 0 PARTS AND TECHNICAL S...

Page 20: ...Gemini Twin Fuel Gas Fired Boiler 8 1 1 Wiring Diagram Lo Hi Lo 18...

Page 21: ...Parts and Technical Support 8 1 2 Control Logic Diagram Lo Hi Lo 19...

Page 22: ...Gemini Twin Fuel Gas Fired Boiler 8 1 3 Wiring Diagram On Off 20...

Page 23: ...Parts and Technical Support 8 1 4 Control Logic Diagram On Off 21...

Page 24: ......

Reviews: