  Gemini™ Twin-Fuel Gas-Fired Boiler 

 

service power
shutoff switch

 

 

Figure 4-4  Service Power Shutoff Switch 

(located inside the auxiliary panel at the back of the boiler) 

 

General Warning

 

Warning!  After checking controls by manual readjust-
ment, make sure they are always returned to their 
proper settings. 

NEVER attempt to operate a boiler that has failed to 
pass all the safety checks outlined below.   

 

 

 

 

 

 

4.4.1  Test of Ignition Safety System 

 

 

high limit
reset

high limit/operating 
temperature
adjustments

lo-hi-lo 
controller

"on"/"off" 
switch

fuel
selector 
switch

flame control
reset switch

propane
in-use
indicator

 

 

Figure 4-5  Lo-Hi-Lo Control Panel (faceplate opened) 

 

high limit
reset

high limit temperature 
adjustment

"on"/"off" 
switch

flame control
reset switch

operating temperature
adjustment

propane in-use
indicator and 
fuel selector switch
(on side)

 

 

Figure 4-5a  On-Off Control Panel (faceplate opened) 

 

 
The boiler is provided with an ignition safety system. 

1.  Open the faceplate on the control panel.  Discon-

nect wire # 17 (Lo-Hi-Lo) or # 26 (On-Off) at the 
terminal block on the control panel.  Disconnect-
ing this wire disables the main gas valve, ensuring 
that gas cannot flow during the test. 

2.   Turn on the circulating water pump.  With the 

natural gas shutoff and secondary shutoff open 
and the pilot gas cock open, turn the operating 
temperature control until the boiler cycles “on.

 

3.  Observe the operation of the boiler.  After all the 

safety limits on gas pressure, water flow, and tem-
perature are satisfied, the blower will run and pre-
purge the boiler.  When air flow is established, the 
ignition transformer and pilot will operate.  Both 
functions will be indicated by separate green 
lights on the control panel.  If a satisfactory pilot 
is established, the green "Ignite" light will extin-
guish and the pilot will remain on, alone, for 10 
seconds.  After 10 seconds, the green "Main Gas" 
light will go on.  (The main gas valve will not 
open with the wire disconnected and gas cannot 
flow to the burner).  The "Pilot" will remain on, 
along with the "Main Gas," for another 10 seconds 
and then go out.  Since the main flame cannot be 
burning, at this point there will be no flame signal 
and the flame safeguard programmer will assume 
a "Flame Failure" and will either re-cycle through 
the complete pre-purge and ignition cycle or, if in-

 
 

- 8 - 

 

Summary of Contents for TBIG-03

Page 1: ...ER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S MANUAL INSTALLATION OWNER S...

Page 2: ...5 1 2 Starting System 13 5 2 Lighting and Shut Down Procedures 13 5 2 1 Lighting Procedures 13 5 2 2 Normal Shut Down Procedures 14 5 2 3 Emergency Shut Down 14 5 3 Switchover to Propane Operation 14...

Page 3: ...gas fired boiler allows the boiler to be fired by propane in the event that the supply of natural gas is temporarily interrupted or restricted The necessary fittings valves piping and controls for twi...

Page 4: ...r must be Installed by qualified personnel in accordance with designs prepared by qualified facility engi neers including structural mechanical electrical and other applicable disciplines Operated and...

Page 5: ...ime Con tact Patterson Kelley at 570 421 7500 for replace ment labels 3 5 SAFETY PRECAUTIONS Provide a suitable location for the boiler away from normal personnel traffic with adequate working space a...

Page 6: ...Check entire gas train for leaks after installation If there is a smell of gas shut down the boiler and obtain immediate assistance from trained service personnel and or your local fire department Ov...

Page 7: ...t valves n o vent valve I R I only Figure 4 1 Piping Schematic for the Twin Fuel Gas Train 4 0 INSTALLATION Gas Train Connection Sizes Natural Gas Propane 700 1000 1200 Series 1 1 4 1 1500 1700 2000 S...

Page 8: ...n either the natural gas or propane supply a suitable intermediate gas pressure regulator of the lock up type must be provided to reduce the pressure to less than 14 inches W C All boilers are designe...

Page 9: ...d devices as shown above 4 3 PRE START CHECK LIST Before firing the boiler make sure the following items have been completed 1 Flue gas from the boiler is properly vented 2 Gas connections have been m...

Page 10: ...block on the control panel Disconnect ing this wire disables the main gas valve ensuring that gas cannot flow during the test 2 Turn on the circulating water pump With the natural gas shutoff and sec...

Page 11: ...rating turn down the temperature setting on the high limit thermostat until the main burner shuts off The high limit switch must be reset manually after testing This check should also be made for the...

Page 12: ...be performed by qualified service per sonnel To adjust gas pressure first connect an appropriate pressure sensing device at the manifold tap then re move seal cap from regulator Turn adjusting screw c...

Page 13: ...is OK If there are bubbles replace the valve 5 Attach the hose to the upstream leak test valve 6 Open the upstream leak test valve and check for bubbles in the hose If there are no bubbles the natural...

Page 14: ...anical link to air control auxiliary panel service power shutoff switch inside auxiliary panel service power shutoff switch inside propane low pressure switch pressure tap secondary shutoff high gas p...

Page 15: ...been under water Immediately call a qualified service technician to in spect the boiler and to replace any part of the control system and any gas control which has been under wa ter 5 2 LIGHTING AND...

Page 16: ...the gas supplies remote from the boiler 5 3 SWITCHOVER TO PROPANE OPERATION Switchover from natural gas to propane is made manually as follows 1 Turn the fuel selector switch located on the main contr...

Page 17: ...y Figure 7 1 Piping Schematic for the Twin Fuel Gas Train 7 0 MAINTENANCE 7 1 GENERAL Warning High voltage Shock hazard Properly lock out tagout the electrical service and all other energy sources bef...

Page 18: ...or marked Heat 6 The programmer first energizes Terminal 4 which supplies power to the contactor for the blower mo tor and the air flow switch which initially shows low air flow with the LowAir indica...

Page 19: ...operating control switch will close again The operating sequence will re cycle to step 5 provided that the limits on water flow gas pressure and high temperature are all met 8 0 PARTS AND TECHNICAL S...

Page 20: ...Gemini Twin Fuel Gas Fired Boiler 8 1 1 Wiring Diagram Lo Hi Lo 18...

Page 21: ...Parts and Technical Support 8 1 2 Control Logic Diagram Lo Hi Lo 19...

Page 22: ...Gemini Twin Fuel Gas Fired Boiler 8 1 3 Wiring Diagram On Off 20...

Page 23: ...Parts and Technical Support 8 1 4 Control Logic Diagram On Off 21...

Page 24: ......

Reviews: