Wall mount Signal Tower Instruction Manual

6. Mounting, Installation, Wiring, and Powering On

  6.  Mounting, Installation, Wiring, and Powering on

 

CAUTION

 Install a location with low vibration and sufficient strength.

 This product can only be mounted in upright position.

 Use this product indoors only. (Do not use outdoors.)
 If the cover cracks or the plating peels off due to a strong impact such as dropping the product, the damaged part becomes 

sharp and very dangerous. If the product becomes damaged, do not continue using it and immediately replace it.

 During installation, do not remove the waterproof sheet. Doing so will hinder waterproofing. (Protection Rating: IP23)
 When increased waterproofing is required, seal the screw or flanged nut parts, as well as over the waterproof sheet around 

the mounting hole, with a waterproof sealant.

 If increased waterproofing is required on an uneven mounting surface, in addition to the screw or flanged nut parts, seal 

the gap between the product and the mounting surface with a waterproof sealant.

Summary of Contents for WE-402UB-LAN

Page 1: ...using this product update to the latest version of the rmware By registering as a member on our home page you can download the latest version of the firmware from My Page To the Contractor Prior to in...

Page 2: ...wer and Buzzer Notification Functions 13 5 2 2 Communication Command Control Function 15 6 Mounting Installation Wiring and Powering on 16 6 1 Mounting Method 17 6 2 How to Remove the Cover After Inst...

Page 3: ...48 8 2 1 Function Code 48 8 2 2 Register Address 49 8 2 3 Example Mapping of Registers 52 8 2 4 Example Transmission 53 8 3 HTTP Commands 57 8 3 1 Controls HTTP Command 58 8 3 1 1 alert control 59 8...

Page 4: ...4 Wall mount Signal Tower Instruction Manual 9 5 How to update the Firmware 72 10 Troubleshooting 73 10 1 Troubleshooting 73 11 Replacement Parts 75 12 Specifications 76...

Page 5: ...ding instructions are ignored WARNING This symbol indicates Failure to follow the instructions may lead to death or serious injury CAUTION This symbol indicates Failure to follow the instructions may...

Page 6: ...installing this product requires construction have the work done by a professional contractor Failure to follow this instruction may result in electric shock re or falling objects To prevent injuries...

Page 7: ...n buttons and contacts are interfered with Avoid exposure to the buzzer sound from a close distance Failure to follow this instruction will result in injury hearing loss For the purpose of safety inse...

Page 8: ...nden in Europa Dieses Produkt wurde gepr ft und h lt die Grenzwerte f r ein Klasse A Ger t gem Diese Grenzwerte sind so ausgelegt einen angemessenen Schutz gegen sch dliche St rungen zu gew hrleisten...

Page 9: ...trademarks of those respective companies 1 5 Network Security The user is responsible for the network security of this product and its use Take appropriate network security measures to avoid security...

Page 10: ...Communication Method Model Number WE 4 02 U B LAN 4 Tier 4 Silver U LAN Communication LAN Buzzer B 24V DC 02 3 Contents Main Unit 1 Accessories Screw Pan head screw Plain Washer Nut with Flange Size...

Page 11: ...ions Cover Side View Front View Side View Tier 1 Tier 2 Tier 3 Tier 4 Front View Bottom View Bottom View 90 1000 100 37 5 206 Buzzer Aperture Status Lamp Switch for Initialize Main Unit Nameplate Name...

Page 12: ...d languages Japanese English Various color expression by multi color LED 9 colors 10 patterns Various Buzzer patterns 7 patterns 24 VDC Input Ethernet Communication PLC PC etc Protection Rating IP23 O...

Page 13: ...OFF 50ms Pulse bright and dark 1 5 sec cycles OFF100ms OFF100ms ON100ms OFF100ms ON100ms OFF100ms ON100ms ON100ms OFF100ms ON100ms OFF100ms ON100ms OFF 250ms OFF 350ms OFF 350ms OFF 350ms OFF 350ms O...

Page 14: ...uzzer pattern 5 Buzzer pattern 6 Buzzer pattern 7 0 sec 3600Hz 250ms 2420Hz 250ms 3600Hz 250ms 0 5 sec 1 sec 1 5 sec 2 sec 3600Hz 250ms 2420Hz 250ms 3600Hz 250ms 2420Hz 250ms 2420Hz 250ms 3600Hz 500ms...

Page 15: ...this product including color information Buzzer volume setting Set up the volume to play the buzzer Modbus TCP communication Function Name Overview Read Holding Registers Gets the current state of th...

Page 16: ...t the damaged part becomes sharp and very dangerous If the product becomes damaged do not continue using it and immediately replace it During installation do not remove the waterproof sheet Doing so w...

Page 17: ...kness should be 6 mm or less when using the screws provided Cover Press the lens parts of the main unit Unit mm Mounting hole 5 4 places Wire entry hole 26 Mounting dimensions How to remove the cover...

Page 18: ...ws Insert a flathead screwdriver into the removal groove of the buzzer aperture 1 3 2 Recess on the cover Protrusion on the main unit Removal groove Lift the cover and remove Use a athead screwdriver...

Page 19: ...Please read the following carefully when wiring LAN cables Con rm that the network is indoors and the LAN cable is not routed outdoors Failure to follow this instruction could result in equipment dama...

Page 20: ...ring and Powering On 6 4 Checking at Startup Remove the cover and check the status light on the bottom of the product Main Unit Status Lamp Cover Status Status Lamp Description Normal operation Light...

Page 21: ...ettings 7 4 Setting Up Product Network Settings page 29 Select the lighting color and buzzer volume for each tier of Signal Tower 7 5 Setting Up Main Unit page 30 When controlled with PNS Commands 7 6...

Page 22: ...n the factory default state When enabling the DHCP function on the Web Setup Screen con gure the settings to match your environment Click Network Internet to enter the View network status and tasks sc...

Page 23: ...23 Wall mount Signal Tower Instruction Manual 7 Before Use Click Properties Select Internet Protocol Version 4 TCP IPv4 and click Properties...

Page 24: ...eck box and set the items IP address 192 168 10 2 to 254 Subnet mask 255 255 255 0 Default gateway No setting is required for a direct connection When connecting to a network check with the network ad...

Page 25: ...tead of the login screen CAUTION Do not forget the password If you cannot remember password you will not be able to log in If you cannot remember password initialize the system and reset your password...

Page 26: ...lick the Comfirm button After completing the settings click To the Login screen to return to the login screen Password Enter the password Verify Password Enter the password again The password must be...

Page 27: ...plicate logins are not allowed Start a Web browser Select the language Enter the Password Click the Login button to log in In the Web browser address bar enter the IP address set for this product The...

Page 28: ...the Con rm button to apply Setup complete is displayed The settings are applied Error is displayed There are errors in the settings Set up as required again How to Read the Top Screen No Name Descrip...

Page 29: ...ory default network settings With the Automatic Settings option the product restarts with the DHCP function enabled After changing the IP address to reconnect to the product change the network setting...

Page 30: ...ys to set up this product Write setup data and Web setup No Item Description Default Value Tier 1 Select from BLACK light o 1 RED AMBER LEMON GREEN CYAN BLUE PURPLE PINK WHITE RED Tier 2 AMBER Tier 3...

Page 31: ...r the Command reception settings screen Enter the port number for receiving data Click Confirm to apply the defined settings Item Description Default Value Input Range Input Port number Enter the port...

Page 32: ...ter the port number to use From the Menu click Modbus TCP settings to enter the Modbus TCP settings screen Click Confirm to apply the defined settings Item Description Default Value Input Range Input...

Page 33: ...that has been read Note While reading the setup data and you transmit a command the associated operation will not run The setup data consists of operation settings registered in the main unit The fol...

Page 34: ...rite data to enter the Read Write data screen The unit automatically reboots after setup Note Do not register any setting data other than this product s setup data Failure to follow these instructions...

Page 35: ...Signal Tower Instruction Manual 7 Before Use 7 10 How to logout from the Web setup screen After completing the settings on the Web setup screen click the Log out button to log out Click when settings...

Page 36: ...view S 53H Signal Tower motion control Controls tier 1 to 4 of the Signal Tower by command with colors set on the Web screen Controls the buzzer with commands D 44H Detailed motion control ashing all...

Page 37: ...00H 00H 06H 00H 1 byte 1 byte 1 byte 1 byte 2 bytes 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 This product s product category is AB 2 Use S for ID 3 Data area is as follows Type Value Description Ty...

Page 38: ...nal Tower color Tier 3 Signal Tower color Tier 4 unused Signal Tower pattern Buzzer pattern 41H 42H 44H 00H 00H 07H 00H 1 byte 1 byte 1 byte 1 byte 2 bytes 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1...

Page 39: ...emon Tier 3 Green Tier 4 Blue Flashing fast Buzzer Pattern 2 Product Category AB ID D Unused Data Size Data Area 7 bytes 1 2 3 4 5 6 7 41H 42H 44H 00H 00H 07H 01H 03H 04H 06H 00H 03H 02H Point Setting...

Page 40: ...er pattern tier 2 Signal Tower pattern tier 3 Signal Tower pattern tier 4 unused 00H 00H 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 This product s product category...

Page 41: ...al Tower Tier 1 Red No ashing Tier 2 Amber ashing medium Tier 3 Blue No ashing Tier 4 White Pulse bright and dark Buzzer Pattern 7 Product Category AB ID F Unused Data Size 41H 42H 46H 00H 00H 0BH Dat...

Page 42: ...te 2 bytes 1 This product s product category is AB 2 Use C for ID Response Command Normal response Error response ACK NAK 06H 15H 1 byte 1 byte 8 1 5 Get Status Command You can get the Signal Tower pa...

Page 43: ...t on 01H Buzzer pattern 1 02H Flashing slow 02H Buzzer pattern 2 03H Flashing medium 03H Buzzer pattern 3 04H Flashing fast 04H Buzzer pattern 4 05H Single ash 05H Buzzer pattern 5 06H Double ash 06H...

Page 44: ...unused unused unused 00H 00H 00H 00H 00H 00H 00H 00H 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte Data Area 40 bytes 15 16 17 18 19 20 21 22 23 24...

Page 45: ...04H Flashing fast 00H FFH 00H Green 05H Single ash 00H BBH DDH Cyan 06H Double ash 00H 33H FFH Blue 07H Triple ash CCH 00H DDH Purple 08H Pulse bright and dark FFH 00H CCH Pink 0AH Right chase light...

Page 46: ...unused 80H 39H E5H 00H 1AH 2FH 00H 00H 00H 00H 00H 00H 00H 00H Data Area 40 bytes 15 16 17 18 19 20 21 22 23 24 25 26 27 unused unused unused unused unused Signal Tower tier 1 Signal Tower tier 2 Patt...

Page 47: ...roduct Category 1 ID 2 Unused Data Size Data Area 3 A B V Buzzer volume 41H 42H 56H 00H 00H 01H 1 byte 1 byte 1 byte 1 byte 2 bytes 1 byte 1 This product s product category is AB 2 Use V for ID 3 Data...

Page 48: ...e 1 byte n bytes Area Name Description Transaction ID 0000H to FFFFH Protocol ID 0000H Fixed Field Length Number of bytes following Unit ID Unit ID 00H to FFH Function Code Code that identi es the fun...

Page 49: ...w 3 13 0DH Detailed motion control Signal Tower Tier 2 Color High 00H Do not control 01H Control Low Detailed motion control Refer to Signal Tower Color low 3 14 0EH Detailed motion control Signal Tow...

Page 50: ...Detailed motion control Signal Tower pattern low Value Description Value Description 00H Light o 00H No ashing 01H Red 01H Flashing slow 02H Amber 02H Flashing medium 03H Lemon 03H Flashing fast 04H...

Page 51: ...ar Signal Tower motion control Detailed motion control When register address 17 11H Signal Tower pattern all tiers and register addresses 19 13H to 22 16H Signal Tower pattern 1 to 4 tiers are used re...

Page 52: ...ecute Clear 0001H 1 9 09H 40009 10 0AH 40010 11 0BH 40011 12 0CH 40012 Light on Red 0101H 257 Light on Amber 0102H 258 13 0DH 40013 Light on Lemon 0103H 259 Light on Green 0104H 260 14 0EH 40014 Light...

Page 53: ...zzer with Pattern 1 Transaction ID Protocol ID Field Length Unit ID Function Code 00H 01H 00H 00H 00H 0FH 01H 03H Data Number of bytes Register1 Register2 Register3 Register4 Register5 Register6 0CH 0...

Page 54: ...er Tier 1 Light on Tier 2 Flashing slow Tier 3 No change Tier 4 Light o Buzzer When emit buzzer with Pattern 2 Transaction ID Protocol ID Field Length Unit Identi er Function Code 00H 04H 00H 00H 00H...

Page 55: ...2 Number of bytes 3 Register12 Register13 Register14 Register15 Register16 Register17 00H 0BH 00H 0BH 16H 01H 01H 01H 01H 01H 05H 01H 07H 00H 00H 01H 01H Data Register18 Register19 Register20 Registe...

Page 56: ...tes in the register to send Response Command Transaction ID Protocol ID Field Length Unit ID Function Code Data Start Address Number of Registers 00H 00H 00H 00H 00H 06H 00H 10H 00H 0BH 00H 0BH Except...

Page 57: ...h tier Make sure to specify buzzer at the same time buzzer Specify the pattern of the buzzer and emit buzzer Make sure to specify color at the same time ash Controls the all tiers of the Signal Tower...

Page 58: ...ke sure to specify buzzer at the same time buzzer buzzer integer value 1 digit Specify a pattern and emit the buzzer Make sure to specify color at the same time ash ash integer value 1 digit Flashing...

Page 59: ...2 Flashing slow 2 Buzzer pattern 2 3 Flashing medium 3 Buzzer pattern 3 4 Flashing fast 4 Buzzer pattern 4 5 Single ash 5 Buzzer pattern 5 6 Double ash 6 Buzzer pattern 6 7 Triple ash 7 Buzzer patter...

Page 60: ...zzer pattern 3 4 Buzzer pattern 4 5 Buzzer pattern 5 6 Buzzer pattern 6 7 Buzzer pattern 7 8 Disabled 9 No change This will result in an error 8 3 1 4 ash control Parameter ash integer value 1 digit T...

Page 61: ...2 Signal Tower pattern Tier 3 Signal Tower pattern Tier 4 0 Fixed Type Value Description Signal Tower pattern 0 No ashing 1 Flashing slow 2 Flashing medium 3 Flashing fast 4 Single ash 5 Double ash 6...

Page 62: ...pi control color 46090 buzzer 7 color buzzer ash Signal Tower Tier 1 Green Flashing slow Tier 2 Blue Flashing slow Tier 3 Light o Tier 4 White Flashing slow Buzzer Pattern 1 http 192 168 10 1 api cont...

Page 63: ...t status of the Signal Tower in the speci ed format text data in text format json data in JSON format Specify the pattern in this order Tier 1 Tier 2 Tier 3 Tier 4 Buzzer Available data Item Header De...

Page 64: ...EE FF 00 Lemon 4 Flashing fast 00 FF 00 Green 5 Single ash 00 BB DD Cyan 6 Double ash 00 33 FF Blue 7 Triple ash CC 00 DD Purple 8 Pulse bright and dark FF 00 CC Pink 10 Right chase light FF FF FF Wh...

Page 65: ...0 text Transmission Command http 192 168 10 1 api status format text Obtained data Status1 1 Status2 1 Status3 1 Status4 1 Status5 0 Color1 FF0000 Color2 FFCC00 Color3 00FF00 Color4 0033FF Color5 0000...

Page 66: ...to follow this instruction could result in deformed frame and product damage Do not use sharp tipped objects with this product Operation may become impossible as scratches develop on Switch for Initia...

Page 67: ...ings revert to the default settings To use it again you need to recon gure the network Log in to the Web Setup Screen From the menu click Initialization Click the Initialize button When Rebooting unit...

Page 68: ...nitialization factory default Item Default Value Signal Tower Settings Main Unit Settings Signal Tower Tier 1 RED Tier 2 AMBER Tier 3 GREEN Tier 4 BLUE Buzzer Buzzer volume 2 Maximum Communication Set...

Page 69: ...hod Use the Web setup screen to restart this product From the menu click Restart Click the Restart button Displays Log in to the Web Setup Screen When Rebooting unit is displayed click To the Login sc...

Page 70: ...the new password in the password field From the Menu click User authentication to enter the User authentication settings screen Re enter the new password in the Verify Password field Click the Confirm...

Page 71: ...th the Get HTTP command status Check the version from the Web Setup Screen Check with the Get HTTP command status For information refer to 8 3 2 Get HTTP command status page 63 Log in to Web setup scr...

Page 72: ...t disconnect the power supply wire or LAN cable Failure to follow this instruction could result in product damage Before updating check the rmware version and compatible models Performing updates with...

Page 73: ...ory 5e or higher 6 3 Wiring Method page 19 Is the IP address for the product correct Check the IP address of the product 7 3 Displaying the Web Setup Screen page 27 7 4 Setting Up Product Network Sett...

Page 74: ...pment and of communication equipment on the transmission route to con rm communication is not blocked by a rewall ltering port blocking function and so on Di erent operation from the command sent Is t...

Page 75: ...75 Wall mount Signal Tower Instruction Manual 11 Replacement Parts 11 Replacement Parts Various parts are available to the customer for exchange or replacement Cover...

Page 76: ...ironmental Wall mount Upright Insulation Resistance More than 1M at 500 VDC between live part and non current carrying metallic part Withstand Voltage 500 VAC applied for 1min between live part and no...

Page 77: ...l in the bottom of the main unit Lever Switch for Initialize x 1 located on the bottom of the main unit can be operated when the cover is removed Accessories Screw Pan head screw M4 x 25 x 4 Plain Was...

Page 78: ...78...

Page 79: ...79...

Reviews: