MAIN OVEN
Natural Gas
L P. Gas
Heat Input
2.4kW (8189 Btu/h)
2.4kW (172.4g/h)
Injector Marking
108
78
Flame Supervision Device
Diamond 'H' GSD 100/28
Diamond 'H' GSD 100-30
Thermostat
Diamond 'H' 1100-150/B2
Diamond 'H' 1100-152/B2
Thermostat By-pass Marking
69
78
TOP OVEN
Natural Gas
L.P.Gas
Heat Input
1.8kW (6142 Btu/h)
2.4kW (172.4 g/h)
Injector Marking
095
78
Flame Supervision Device
Diamond 'H' GSD 100/44
Diamond 'H' GSD 100/46
Thermostat
Diamond 'H' GSD 1100-112/B2
Diamond 'H' GSD 1100-99/B2
Thermostat By-Pass
73
79
GENERAL
Ignition
H.T. Spark
H.T. Spark
Spark Gap
3-4mm
3-4mm
IMPORTANT - SAFETY REQUIREMENTS
This appliance must be installed in accordance with the Gas Safety (Installation and Use) Regulations
Current Editions. Detailed recommendations are contained in the following British Standard Codes of Practice
- BS.6172, BS.5440: Part 2 and BS.6891. All British Standards must be 'Current Editions'.
PROVISION FOR VENTILATION
This appliance is not connected to a combustion products evacuation device. It shall be installed and
connected in accordance with the current installation regulations. Particular attention shall be given to the
relevant requirements regarding ventilation.
The room containing the appliance should have an air supply in accordance with BS. 5440: Part 2 Current
Edition. All rooms require an openable window or equivalent and some rooms will require a permanent vent
as well. For room volumes up to 5m³ an air vent of 100cm² is required: for room volumes between 5m³ and
10m³ an air vent of 50cm² is required. If the room has a door that opens directly to the outside, no air vent is
required. For room volumes that exceed 11m³ no air vent is required. If there are other fuel burning
appliances in the same room, BS.5440: Part 2 Current Edition should be consulted to determine the requisite
air vent requirements.
Prolonged intensive use of the appliance may call for additional ventilation, for example opening a window, or
more effective ventilation, for example increasing the level of mechanical ventilation where present.
37
R E N O W N 5 5 G X