background image

Bulletin 100-50-2.1 –

 Page 1

Sporlan IB-G Interface Board 

Installation and Operation Instructions

August 2016 / Bulletin 100-50-2.1

Summary of Contents for Sporlan IB-G

Page 1: ...Bulletin 100 50 2 1 Page 1 Sporlan IB G Interface Board Installation and Operation Instructions August 2016 Bulletin 100 50 2 1 ...

Page 2: ...the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specifications provided by the user the user is responsible for determining that such data and specificatio...

Page 3: ...ve open or close feature The IB G can only control a single ESX valve Warning Do not apply power to the IB G until wiring is complete Remove power before making any wiring changes Voltage drop must be considered when locating the IB G away from the power supply and external controller 2 Digital inputs connected to terminals OPN CLS and REF can be used to drive the valve open or closed A short betw...

Page 4: ...rol signal and valve position have a linear relationship For example if the external controller provides 5VDC signal across terminals S and S and the IB G is set for 0 10V signal then the valve will be positioned at 50 open 7 5VDC signal will position the valve at 75 open etc To allow for component tolerances the IB G will shut the valve when the input signal reaches 4 05 milliamps or 0 05 volts d...

Page 5: ...n REV Direction This selection allows the valve to operate in reverse direction STD direction closes the valve based on increasing control signal To reverse the valve direction turn the DIP switch 5 to ON This selection does not affect the force close direction when the CLS and REF OPN and REF or forced close DIP switch 8 is turned on STD Response Quick This selection speeds up valve response to c...

Page 6: ... stroke is set correctly based on DIP switches 1 3 see Table 2 Check to ensure DIP switch 4 is set correctly Check valve for short or open see Test the Valve instructions in the Troubleshooting section If GREEN LED is off or blinking Check signal across terminals S and S The signal should be 10VDC or 20mA depending on jumper selection found in Table 1 If using 4 20mA control signal ensure proper s...

Page 7: ...llector Indicators Red LED Power Yellow LED Valve Closed Green LED Valve Open Analog Inputs 0 10VDC 4 20mA MECHANICAL Operating Temperature 22 F to 158 F 30 C to 70 C Storage Temperature 30 F to 170 F 34 C to 77 C Humidity 10 95 RH Non Condensing Wiring Screw Terminal Mounting SNAP Track Mounting Holes COMPLIANCE CE RoHS ITEM DESCRIPTION IB G INTERFACE BOARD POWER SUPPLY 100 240 VAC 24VDC ITEM NUM...

Page 8: ...ire Green wire Red wire Power S S OPN CLS REF B W G R 24V 24V 4 20mA or 0 10V Control Signal Digital Inputs Orange wire Grey wire M Yellow wire Black wire Red wire Power A1 B1 B2 A2 Wiring Bipolar Valve to IB G Wiring Unipolar Valve to IB G Wiring Power to IB G Bipolar valves only Wiring Power to IB G Unipolar valves only Transformer 24VAC Requires 30 VA per IB board 24 24 24 24 L N Transformer 24...