2 Introduction

Th

  is manual refers to refrigeration dryers designed to guarantee high 

quality in the treatment of compressed air.

2.1 Transport

Th

  e packed unit must:

• remain upright;
• be protected against atmospheric agents;
• be protected against impacts.

2.2 Handling

Use a fork-lift  truck suitable for the weight to be lift ed, avoiding any type 
of impact. 

2.3 Inspection

a)  All the units are assembled, wired, charged with refrigerant and oil 
and tested under standard operating conditions in the factory;
b)  on receiving the machine check its condition: immediately notify the 
transport company in case of any damage;
c)  unpack the unit as close as possible to the place of installation. 

2.4 Storage

If several units have to stacked, follow the notes given on the packing. 
Keep the unit packed in a clean place protected from damp and bad 
weather.

3 Installation

3.1 Procedures

Install the dryer inside, in a clean area protected from direct atmospher-
ic agents (including sunlight).

Y

 Comply with the instructions given in par. 8.2 and 8.3.

 All dryers must be fi tted with adequate pre-fi ltration near the dryer air 
inlet. Seller is excluded any obligation of compensation or refund for any 
direct or indirect damage caused by its absence

Y

 Pre-fi lter element (for 3 micron fi ltration or better) must be replaced 

at least once a year, or sooner as per manufacturer recommendations.

Y

 Do not invert the compressed air inlet and outlet connections and 

observe the maximum tightening torque (N x m) as specifi ed in par. 8.3.

3.2 Operating space

Y

 

Leave a space of 1.5 m around the unit. 

3.3 Tips

To prevent damage to the internal parts of the dryer and air compres-
sor, avoid installations where the surrounding air contains solid and/or 
gaseous pollutants (e.g. sulphur, ammonia, chlorine and installations in 
marine environments).

Th

  e ducting of extracted air is not recommended for versions with axial 

fans.

3.4 Electrical connection

Use approved cable in conformity with the local laws and regulations 
(for minimum cable section, see par. 8.3).
Install a diff erential thermal magnetic circuit breaker with contact open-
ing distance  3 mm ahead of the system (RCCB - IDn = 0.3A) (see the 
relevant current local regulations).
Th

  e nominal current In of the magnetic circuit breaker must be equal to 

the FLA with an intervention curve type D.

3.5  Condensate drain connection

 Th

  e dryer is supplied either with a fl oat drain, a timed drain or an elec-

tronic level sensing drain.
If a timed or electronic unloader is installed, use terminals CN (R1-S1)” 
(see par. 8.8).
For timed and electronic drains: refer to separate manual supplied with 
the dryer for specifi c details concerning the condensate drain.

Y

 

Make the connection to the draining system, avoiding connection 

in a closed circuit shared by other pressurized discharge lines. Check the 
correct fl ow of condensate discharges. Dispose of all the condensate in 
conformity with current local environmental regulations.

4 Commissioning

4.1 Preliminary checks

Before commissioning the dryer, make sure: 

• installation was carried out according that given in the section 3;
• the air inlet valves are closed and that there is no air fl ow through the 

dryer;

• the power supply is correct.

4.2 Starting

a)  Start the dryer before the air compressor by means of the main power 
switch “

14

”; the power lamp will illuminate (green);

b) aft er at least 5 minutes slowly open the air inlet valve and subse-
quently open the air outlet valve: the dryer is now performing its air 
drying function.

4.3 Operation

a)  Leave the dryer on during the entire period the air compressor is 
working;
b)  the dryer operates in automatic mode, therefore fi eld settings are not 
required;
c)  in the event of unforeseen excess air fl ows, by-pass to avoid overload-
ing the dryer. 

4.4 Stop

a)  Stop the dryer 2 minutes aft er the air compressor stops or in any case 

aft er interruption of the air fl ow;
b)  do not allow compressed air to fl ow through the dryer when the lat-
ter is not running;
c) switch off  at the main power switch 

«14»

. Th

  e power light goes out 

and the compressor stops.

5 Control

11: 

Dew point indicator

14: 

Main Power Switch

Th

  e dew point indicator can show one of three conditions:

blue: 

dew point too low

green: 

dew point ideal

red: 

dew point too high

5.1  Option Free contact

An adjustable thermostat (with free  contacts) to signal high dew point 
is optionally available.   A timer allows the delay to the start of the dryer 
of the  alarm signal (10 minutes).

Summary of Contents for SPL004

Page 1: ...Starlette Plus Date 03 01 2017 Rev 23 CODE 398H272864 SPL004 SPL006 SPL009 SPL012 SPL018 SPL024 SPL030 User manual Manuel d utilisation Manual de uso 60Hz Refrigeration Dryer...

Page 2: ......

Page 3: ...e for the correct or foreseeable use of the machine itself or its components IMPORTANT The manufacturer reserves the right to modify this manual at any time The most comprehensive and updated informat...

Page 4: ...ng distance 3 mm ahead of the system RCCB IDn 0 3A see the relevant current local regulations The nominal current In of the magnetic circuit breaker must be equal to the FLA with an intervention curve...

Page 5: ...ourless gas classified in SAFETY GROUP A1 EN378 group 2 fluid according to Directive PED 2014 68 EU GWP Global Warming Potential 1430 In case of refrigerant leakage ventilate the room 6 3 Preventive M...

Page 6: ...eek external as sistance Ice formation on evapo rator low evaporation pressure By pass air flow keep ing air inlet open Open condensate drain valve manually Restart appliance checking setting of expan...

Page 7: ...les dommages ou d g ts ventuels pouvant r sulter de manipulations malveillantes et ou de modifications de l emballage L utilisateur doit s assurer que les conditions fournies pour la s lection de l un...

Page 8: ...homologu aux sens des normes fran aises en mati re d lectricit et de la r glementation locale pour la section minimale du c ble voir paragraphe 8 3 Installer l interrupteur magn to thermique diff rent...

Page 9: ...ales est un gaz incolore appartenant au SAFETY GROUP A1 EN378 fluide groupe 2 selon la directive PED 2014 68 EU GWP Global Warming Potential 1430 En cas de fuite de r frig rant a rer le local 6 3 Prog...

Page 10: ...re dans l vaporateur basse pres sion d vaporation by passer l air en maintenant ouverte l arriv e d air Ouvrir manuellement l vacuation des condensats Remettre en marche en v rifiant le tarage de la s...

Page 11: ...ente previsible de la misma unidad o de los componentes ATENCI N El fabricante se reserva el derecho de modificar sin previo aviso la informaci n de este manual Para que la informa ci n resulte comple...

Page 12: ...consulte las disposiciones locales al respecto La corriente nominal In de dicho magnetot rmico debe ser igual a FLA y la curva di intervenci n de tipo D 3 5 Conexi n del drenaje de condensados El seca...

Page 13: ...N378 fluido del grupo 2 seg n la directiva PED 2014 68 EU GWP Global Warming Potential 1430 En caso de fuga de refrigerante airee el local 6 3 Programa de mantenimiento preventivo Per garantire nel te...

Page 14: ...icitar asistencia externa formaci n de hielo en el evaporador baja presi n de evaporaci n derivar el aire by pass dejando abierta la entrada de aire Abrir manualmente el drenaje de condensados Reactiv...

Page 15: ...1 SPL004 030 Appendice Ap ndice Appendix...

Page 16: ...de condensation Salida aire de condensaci n Condensation air outlet Entr e air de condensation Entrada aire de condensaci n Condensation air inlet 1 MC Compresseur Compresor Compressor 2 Condenseur r...

Page 17: ...eeding dryer design pressure Tuyaux flexibles pour raccordements de l air si le r seau est soumis des vibrations Tubos flexibles para las conexiones de aire si la red est expuesta a vibraciones Hoses...

Page 18: ...30V 10 1ph 60Hz NPT N x m dB A 41 8 19 5 99 0 17 0 24 32 122 F 0 50 C 41 122 F 5 50 C 149 F 65 C 3 74 3G16AWG NPT compatible 1 2 50 50 SPL004 SPL006 SPL009 51 8 23 5 9 52 0 27 0 39 4 78 55 SPL012 SPL0...

Page 19: ...quest On request On request 398H785241 On request Spare parts Refrigerant condenser 2 398H114800 398H114801 398H114802 398H114803 398H114804 Evaporator Separator Air air heat exchanger 4 398H472157 39...

Page 20: ...8 5 Exploded drawing 6 SPL004 030 2 3 8 13 1 7 4 11 14 6 15 12 KA1 KT T01...

Page 21: ...8 6 Dimensional SPL004 006 7 SPL004 030 inches mm...

Page 22: ...8 6 Dimensional SPL009 012 8 SPL004 030 inches mm...

Page 23: ...8 6 Dimensional SPL018 030 9 SPL004 030 inches mm...

Page 24: ...8 7 Refrigerant circuit SPL004 030 10 SPL004 030...

Page 25: ...8 8 Wiring diagram SPL004 006 11 SPL004 030...

Page 26: ...Wiring diagram SPL009 030 12 SPL004 030...

Page 27: ...Wiring diagram optional free contact SPL030 13 SPL004 030...

Page 28: ...e to adhere to this procedure will result in loss of warranty c Seller reserves the right to replace a product under warranty and will accept no costs as to the removal and installation of the product...

Page 29: ...e de la garantie c La soci t fournisseur se r serve le droit de remplacer un produit sous garantie et n acceptera aucun frais de retrait et d installation des produits d La soci t fournisseur se r ser...

Page 30: ...o y posteriormente enviado al Proveedor El incumplimiento de este procedimiento causar la invalidaci n de la garant a c El Proveedor se reserva el derecho a reemplazar un producto en garant a y no asu...

Page 31: ...Information Centre Free phone 00 800 27 27 5374 from AT BE CH CZ DE DK EE ES FI FR IE IL IS IT LU MT NL NO PL PT RU SE SK UK ZA US Product Information Centre Toll free number 1 800 27 27 537 www park...

Page 32: ...co MI Italy Sede Operativa Gas Separation and Filtration Division EMEA Strada Zona Industriale 4 35020 S Angelo di Piove PD Italy tel 39 049 971 2111 fax 39 049 9701911 Web site www parker com hzd e m...

Reviews: