Parker PID00A-40 Series Operation Manual Download Page 31

31

Electronics for Closed Loop Control

Series PID00A-40X

Operation Manual

PID00A_10 5715-616 UK.indd CM 14.11.14

Parker Hannifin Corporation

Hydraulics Group

Repeatable position error too large because of 
valve dead band or hysteresis

Utilization of the integrated dead band compensa-
tion coefficient enables this effect to be reduced 
or eliminated. There are separate adjustable pa-
rameters P7 and P8 for both valve sides. This fea-
ture generates constant correction signals which 
will be active for the dedicated valve site if a sig-
nal occurs on the command signal input. As a re-
sult this will cause the valve to “Jump“ through the 
overlap region of the spool.

Increasing load stiffness

“Load stiffness” is the term given to the resistance 
of the servo loop to deflection of the drive by ex-
ternal forces. Adjusting P16 to the highest practi-
cal value is important. 

Disappointing control loop function

The higher the value of P-gain that can be used, 
the better is the static and dynamic performance of 
the system. You may not have any direct need for 
fast response, but may still need a high value of P 
to reduce static error, reduce following error or in-
crease actuator stiffness. High values of P cause 
faster system response, whether you need it or not. 
As the system frequency response gets too close 
to the frequency response of one of your compo-
nents, the system response becomes oscillatory.
 
• 

Valve

  The frequency response of the valve can be 

obtained from the datasheets. As a first guess, it 
needs to be at least twice the system frequency 
response.

• 

Position transducer

  Some analog output transducers will present 

problems because of filtering intended to smooth 
the output. To ensure the best system dynamic, 
sensors with integrated D/A-converter should 
operate with a high sampling rate. Magnetostric-
tive transducers with digital output often have a 
low sampling rate, because an interaction with 
the achievable resolution. Please obtain detailed 
information from the transducer supplier.

• 

Drive

 

There is a mode of mechanical vibration created 
by the mass of the load and the compressibility 
of the hydraulic fluid in the whole system. This 
frequency is often surprisingly low when using 
long stroke cylinders.

Update rate of the controller

The controller updates the electrical output to the 
valve at 1000Hz. This rate is fast enough to have 
negligible effect in almost all hydraulic applications, 
but it does set an absolute limit on the response 
of the system.

Position transducer accuracy and resolution

A control system is no better than its transducer. 
Here are points to watch for:
• 

Absolute accuracy

  The controller positions the load as closely 

as possible to the position measured by the 
feedback transducer. The absolute accuracy 
of the measured position is determined by the 
transducer.

• 

Resolution

  The electronics cannot position the load more 

accurately than the resolution of the transducer. 
Be sure the resolution of your sensor is adequate. 
When using a true analog transducer (analog 
measurement principle and analog output), the 
resolution is limited by the utilized A/D-converter, 
which is 12 bit (1/4096 = 0.025 %).

• 

Installation

 

The installation of the position transducer plays 
a most important rule for the proper functionality 
of the closed loop control. By all means it has 
to be secured, that the mounting of transducer 
and actuating device provides absolute freedom 
from vibration and clearance effects. This is 
most important even for the commonly expected 
velocities and accelerations. Also, the transducer 
has to be laid out for the dynamic requirements.

Summary of Contents for PID00A-40 Series

Page 1: ...40X Design 10 Electronics for Closed Loop Control Parker Hannifin Manufacturing Germany GmbH Co KG Hydraulic Controls Division Europe Gutenbergstr 38 41564 Kaarst Germany Tel 49 181 99 44 43 0 E mail...

Page 2: ...at all performance endurance maintenance safety and warn ing requirements of the application are met The user must analyze all aspects of the application follow applicable industry standards and follo...

Page 3: ...usage 8 3 2 Common instructions 8 3 3 Liability 8 3 4 Storage 8 4 Mounting Installation 9 4 1 Scope of supply 9 4 2 Mounting 9 4 3 Operational limits 9 4 4 Electrical connection 9 4 5 Electrical inte...

Page 4: ...rker Hannifin Corporation Hydraulics Group 1 Introduction 1 1 Front view dimensions 1 2 Ordering code 1 3 Name plate Universal Code Function 0 Standard 1 Linearization Electronic module closed loop co...

Page 5: ...described electronic unit combines all neces sary functions for the optimal operation of closed loop controls The most important features are 1 5 Characteristics Extended PID controls Velocity control...

Page 6: ...solenoid output on acc NAMUR NE43 Input signal resolution 0 025 Differential input voltage max V 30 for terminals 5 und 6 against PE terminal 8 Status signal V 0 0 5 Off Us On rated max 15 mA Enable...

Page 7: ...7 Electronics for Closed Loop Control Series PID00A 40X Operation Manual PID00A_10 5715 616 UK indd CM 14 11 14 Parker Hannifin Corporation Hydraulics Group 1 7 Signal flow diagram...

Page 8: ...contamination atmospheric exposure and mechanical damages 2 Safety instructions Please read the operation manual before installa tion startup service repair or stocking Paying no attention may result...

Page 9: ...s at once as shock hazard protection and marking strip Dimensions assembly rail 4 Mounting Installation 4 1 Scope of supply Please check immediately after receiving the elec tronics if the content is...

Page 10: ...ent limit circuit may respond prematurely and create problems during energizing of the supply voltage The screw terminals are designed to allow ter mination of all kinds of copper wires without the ne...

Page 11: ...overallsafetysystems strategy Wiring diagram of enable input Enable input A signal voltage applied to the terminals 3 and 13 enables the solenoid output of the electronics Con tinuous operation of the...

Page 12: ...is case the solenoid output will be switched off The output will switched on when the input signal reaches a value of 3 8mA it switches Wiring diagram of voltage command input 10 0 10V off when the co...

Page 13: ...lfunction Wiring diagram of monitor output Wiring diagram of status output Monitor output optional comparator output A reference voltage representing the feedback sig nal is available from terminals 7...

Page 14: ...e down streamed electronic parameter E20 Signal output The terminals 7 and 9 provides the output signal set value which may be used to control exter nal amplifier modules integrated valve amplifiers a...

Page 15: ...40X Operation Manual PID00A_10 5715 616 UK indd CM 14 11 14 Parker Hannifin Corporation Hydraulics Group Wiring diagram of sensor input 0 10V Wiring diagram of sensor input 0 20mA 4 12 20mA 3 wire Wi...

Page 16: ...ydraulics Group Wiring Examples Partially the wiring requires a shielded per forance for the sake of clarify the appropriate illustration is ommitted Example 1 Closed loop position control of a hydrau...

Page 17: ...00A_10 5715 616 UK indd CM 14 11 14 Parker Hannifin Corporation Hydraulics Group Example 2 Closed loop position control of a hydraulic cylin der performed via proportional directional control valve wi...

Page 18: ...10 5715 616 UK indd CM 14 11 14 Parker Hannifin Corporation Hydraulics Group Example 3 Closed loop pressure control within a hydraulic cylinder performed utilizing a proportional pres sure con trol va...

Page 19: ...A_10 5715 616 UK indd CM 14 11 14 Parker Hannifin Corporation Hydraulics Group Example 4 Closed loop position control of a hydraulic cylin der utilizing a proportional directional control valve D FB w...

Page 20: ...structions The electronics module performs the task of com paring the command input signal value with the feedback signal value eg cylinder position The difference is then feed to a closed loop contro...

Page 21: ...setup exe Follow the instructions on the screen Answer the question if an older version should be overwritten with ok During the installation you may change destination drive resp installation path i...

Page 22: ...malfunction In case of parameter changes shut the drive down Brief instruction for first startup Connect the module electronics to the sup ply voltage Connect the module to a PC via null modem cable...

Page 23: ...Dprogramhasalsooffline i e without connection to the electronics functionality a manual pre selection of the parameters is possible After selection of the electronics type via the menu Options the par...

Page 24: ...0 1 0 P12 polarity feedback 0 1 0 P20 feedback scale 0 200 0 100 0 P29 polarity set value 0 1 0 E2 closed loop control 0 inactive open loop 0 inactive 2 active closed loop E11 sensor type feedback 1...

Page 25: ...of negative polarity signal step To compensate for the overlap of the valve spool P11 command signal polarity Adjustment of the command signal polarity To match the command signal polarity to the cont...

Page 26: ...P21 comparator function window 0 200 0 0 P23 comparator rise delay time ms 0 10000 0 P24 comparator turn off delay time ms 0 10000 0 P26 window I portion 0 20 20 P27 reduct window I portion 0 100 0 10...

Page 27: ...e I portion active range in terms of the control difference To limit the I portion on a certain range P27 I gain window reduction Adjustment of the I portion outside the window in terms of the control...

Page 28: ...onal P integral I and de rivative D each with a user adjustable coefficient The user software provides therefore the parame ters P16 P P17 I and P18 D P P16 This term provides an immediate output sign...

Page 29: ...continue with tuning of the loop Tuning of the closed loop control 1 Create a suitable tuning test profile otherwise it may be difficult for you to tell how good the system response is the test profil...

Page 30: ...26 0 Repeatable position error by using a valve with overlap hysteresis Use dead band compensation feature P7 MIN channel A resp P8 MIN channel B Position error too large when following constant veloc...

Page 31: ...th the output To ensure the best system dynamic sensors with integrated D A converter should operatewithahighsamplingrate Magnetostric tive transducers with digital output often have a low sampling ra...

Page 32: ...sure this functionality the polarities of command and feed back signal must be equal 5 5 2 Application Closed loop systems for pressure via pressure control valves Introduction The electronics uses a...

Page 33: ...the test profile may also be generated by an up stream electronic module PZD00A 400 The test profile should start caus ing the system from the circulation pressure with the desired maximum accelerati...

Page 34: ...mbarked if typical problems with pres sure control loops appear Increasing load stiffness Load stiffness is the term for the resistance of the servo loop characteristics to deflection by ex ternal for...

Page 35: ...troller updates the electrical output to the valve at 1000Hz This rate is fast enough to have negligible effect in almost all hydraulic applications but it does set an absolute limit on the response o...

Page 36: ...be poor I P17 This term causes the output to change at a rate proportional to the error in measured pressure in a direction to drive the steady state error to zero P17 is active when a window will be...

Page 37: ...as desired you can contin ue with tuning of the loop Tuning of the closed loop control 1 Create a suitable tuning test profile this will enable you to evaluate your system response A test profile may...

Page 38: ...0 Repeatable deviation by using a valve with overlap hysteresis Use dead band compensation feature P7 MIN channel A resp P8 MIN channel B Following error too large during velocity profile execution U...

Page 39: ...tiation of the posi tion transducer output signal The disadvantage of such a circuit is the creation of noise in the feed back signal Thus different filter algorithms are im plemented To match the fun...

Page 40: ...ement principle and analog output the resolutionislimitedbytheutilizedA D converter which is 12 bit 1 4096 0 025 Installation The installation of the position transducer plays a most important rule fo...

Page 41: ...Check if the Com port is set for 9600 8 1 none none via the menu Options Port Wrong password Retype the password notice the exact spelling case sensitivity Wrong input An invalid character or a value...

Page 42: ...ical experiences with similar failures Have system adjustments been changed Ineithercasetheavailablediagnosticoptions should be used The electronics permits a diagnosticofthevalvefunctionviathemonitor...

Page 43: ...ervice general support for starting up Parker hydrau lic controls maintenance of Parker controls repair of all Parker related hydraulic and elec trical devices assistanceinthesupplyofsparepartsworldwi...

Page 44: ......

Reviews: