background image

6

www.parker.com/euro_pneumatic

Outlet silencer

Central silencer

Sound levels

Sound levels are measured at free speed with the measuring instrument 
positioned 1 m away from the air motor, see the table below

Air 

Free outlet 

With outlet 

Exhaust air removed 

motor 

 

silencer 

with pipes to  

 

 

 

another room 

 

 dB 

(A) 

 dB 

(A) 

   dB 

(A)

Please refer to the technical catalogue PDE2554TC

The noise from an air motor consists of both mechanical noise and a 
pulsating noise from the air flowing out of the  outlet. The installation of 
the motor has a considerable effect on mechanical noise. It should be 
installed so that no mechanical resonance effects occur.  The  outlet air 
creates a noise level which can amount to 108 dB(A) if the air is allowed 
to exhaust freely into the atmosphere. To reduce noise levels, various 
types of outlet silencer are used. The most common type screws 
directly into the outlet port of the motor. A wide range of silencers are 
available. Many are made of sintered brass or sintered plastic. Since the 
motor function causes the exhaust air to pulsate, it is a good idea to 
allow the air to  exhaust into some kind of chamber first, which reduces 
the pulsations before they reach the silencer. The best silencing method 
is to connect a soft hose to a central silencer allowing the speed of the 
air to reduce as much as possible.

NOTE! 

Remember that if a silencer is too small or is blocked, back 

pressure is generated on the outlet side of the motor, which in turn 
reduces the motor power.

5.9 Silencing

Test prior to use of motor in EX-area 

Checked  Reference

 

 Chapter 

Is a formal EC-Declaration of Conformity in
accordance with guideline 2014/34/EU available 

 

5.5
for all components that will be at-tached to
the air motor?

Test prior to use of motor in EX-area 

Checked  Reference

 

 Chapter 

Do the following specifications of the tag on
the air motor agree with the required
specifications of the Ex-area: 

 

4.3

• design group 

 

4.4

• design category
• Ex-area
• temperature class 
• maximum surface temperature

Has it been confirmed that during the
installation of the air motor there were no 

 

5.1

explosive atmospheres, such as oils, acid,
gas, steam or radiation?

Is the ambient temperature in accordance 

 

5.3

with requirements?

Has it been certified that the air motor is
sufficiently ventilated and that there is no 

 

5.5

additional warming source (such as a clutch)?
I

This check list shows all activities, which have to be performed during 
the use of the air motor in an Ex-area (according to the guideline  
2014/34/EU – previously ATEX 100a).

Test during use of motor in Ex-area 

Checked  Reference

 

 Chapter 

After approximately 1.5 hours of operation,
measure the surface temperature.
A temperature increase of over 40K is not 

 

6.3

allowed.

Example:

T

max

 = T

U

 + 

r

T = 20°C + 40K = 60°C

If a temperature increase >40K occurs
immediately stop the drive and contact
Parker!

6.2  Motor Operation

Make sure that all air supply parts are correctly 
connected, prior to motor operation. 

Do not step into the air stream 

Turn the air-supply to “ON”. 
If necessary, adjust the air-pressure or the flow-pressure to 
achieve the required speed or torque.

Adjust the oiler as described in chapter 5.7 – paragraph 
„Lubrication“.

Regularly check the oil-level and if necessary refill the oil 
container.

The motor needs to be cleaned on a regular basis to avoid 
a dust deposit with a more than 5-mm thickness.

6. Operation

6.1  Check List

This check list shows all activities, which have to be performed prior 
to the use of the air motor in an Ex-area (according to the guideline 
2014/34/EU – previously ATEX 100a).

6.3  Measure Surface Temperature
 

(if motor is used in an explosive area)

The details of the maximum allowable surface 
temperature as shown on the motor tag are based 
on measurements under normal environmental and 
installation conditions. Small changes to those 
conditions (such as a constructed installation area) 
will considerably effect the temperature
development!

Measure Surface Temperature 

It is very important to measure the surface temperature of 
the motor during operation. Measurement can be done 
using conventional temperature measuring instruments.
The surface temperature should be taken at the marked 
measuring point as specified on the dimensions (see 
chapter 5.6).
The maximum allowable surface temperature is reached 
after approximately 1.5 hours of operation. This maximum 
temperature must not increase more than 40K.
Ambient temperature in the Ex-area:  -20°C to +40°C

If the surface temperature exceeds the mandate, the 
motor must be stopped immediately.
Please immediately contact Parker!

Summary of Contents for P1V-S

Page 1: ...the surrounding area Important instructions relating to explosion protection Application tips and other useful information Definition Potentially explosive atmosphere hereinafter referred to as Ex are...

Page 2: ...apply Warranty and liability claims in regards to persons or equipment damage are invalid if one or several of the following causes apply Use of the equipment in a non designated application Improper...

Page 3: ...erature of 135 C Motor should be tested to ensure that the permissible temperature does not exceed 130 C there is a safety margin of 5 C This is the maximum permissible surface temperature of the moto...

Page 4: ...utch etc have to be covered by a contact guard 8 8 0 72 1 28 2 9 5 75 9 9 24 48 83 132 200 275 390 10 9 1 02 1 8 4 1 8 1 14 34 67 117 185 285 390 550 12 9 1 21 2 15 4 95 9 7 16 5 40 81 140 220 340 470...

Page 5: ...make sure that the flow pressure at the motor connection side is 6 bar 85 PSI A higher air pressure leads to increased wear and tear install a pressure regulator An air pressure below 6 bar reduces t...

Page 6: ...ure in accordance 5 3 with requirements Has it been certified that the air motor is sufficiently ventilated and that there is no 5 5 additional warming source such as a clutch I This check list shows...

Page 7: ...for the disassembly original spare parts and the trained repair specialists that can adjust the air motor to the correct gap play The gap play determines the motors power efficiency and life expectanc...

Page 8: ...t be changed Continuous lubrication free operation of motors equipped with vanes option C Duty cycle Continuous Filtering 40 m 750 hours of operation Filtering 5 m 1 000 hours of operation The specifi...

Page 9: ...operation For motors Order code P1V S002A P1V 6 446083A P1V S003A P1V 6 446083A P1V S008A P1V 6 446084A P1V S012A0 D0 to serial no 948688 9121720601 P1V S012A0 D0 from serial no 948689 9121720636 P1V...

Page 10: ...0620 P1V S120A 110 9121720620 P1V S120A 078 9121720621 P1V S120A 032 9121720621 P1V S120A 012 9121720621 Service kits for brake module for motors with brakes For motors Order code P1V S020AD and P1V S...

Page 11: ...1V S motors carry the CE mark because they are ATEX certified for use in explosive atmospheres The following are the currently applicable directives Machinery Directive essential health and safety req...

Page 12: ...and of motor bearing cover Air pressure is Increase air too low pressure No air shut off Open shut off valve is closed valve Hose diameter Use a hose with a is too small larger diameter Exhaust air i...

Page 13: ...s the ambient temperature as specified in the technical data in the catalogue at all times 3 Are you certain that the P1V S motor is adequately ventilated and that no additional heat is added for exam...

Page 14: ...eich clamping area 119 13 5 17 e8 17 11 5 3 5 6 5 4 k6 10 8 e8 1 1 measuring point for temperature measurement Motor P1V S002A0130 Motor P1V S002A0095 Motor P1V S008A0190 Motor P1V S008A0130 1 measuri...

Page 15: ...5 K 80 C Maximum permitted surface temperature on the motor in atmospheres containing potentially explosive dust X Note special conditions Test certificate number IBExU04ATEXB004 X from IBExU Institu...

Page 16: ...0 parker easteurope parker com NL The Netherlands Oldenzaal Tel 31 0 541 585 000 parker nl parker com NO Norway Asker Tel 47 66 75 34 00 parker norway parker com PL Poland Warsaw Tel 48 0 22 573 24 00...

Reviews: