background image

MT-700 series installer guide 

 

 Page 7 

 

Configuring a Sensor 

1)  Click on the newly created sensor icon. 
2)  In the sensor configuration window, give the sensor a unique, meaningful name in the 

Identification

 field. 

3)  Select the ‘Hardware’ tab.

 

4)  Confirm the manufacturer and sensor model are correct from earlier. 

5)  In the ‘Sensor Node’ field, select the controller that this sensor is connected to.

 

6)  In the ‘Sensor Node Input’ field, select the input 

location for the sensor.  The inputs are 

numbered sequentially, starting with two inputs on the Main controller and proceeding to the 
first expansion module.  The inputs are also identified 

 in parenthesis 

 by two numbers, 

corresponding to the module number and input number. 

 

For example: Input (1-2) is Input No. 2 on the Main Controller; Input (2-6) is Input #6 on the 
second module. 

7)  Select the ‘Alarm’ tab.

 

8)  

Configure the sensor’s alarm settings, by either selecting a pr

eset or manual configuration.  To 

select a preset: click 

the ‘Pick Alarm Settings’ button, select 

a preset from the list, and clic

k ‘OK’.

  

Or to manually configure the alarm settings, fill in the following fields: 

 

Description:

  

(optional) 

 

Optimal Value:

  specify the desired sensor reading 

 displayed on trend graph for reference 

 

High/Low Limit:

  specify the upper/lower threshold, above/below which an alarm will be 

generated 

 

Set Time: 

 specify the time delay, during which the sensor must remain outside of the high/low 

limit, before an alarm is generated 

 

Recall Time:

 if an alarm is Acknowledged in Alliance but the alarm condition persists, the alarm 

signal will be re-activated after the delay specified here. This feature ensures alarms conditions 
are not dismissed or forgotten without being resolved. 

 

Priority Level: 

 specify the severity of the alarm.  Temperature alarms should be considered high 

priority. 

 

Relay:  

specify the external relay to be activated when an alarm is generated (optional) 

9)  Click ‘OK’ to close the sensor window.  If prompted, click ‘Yes’ to save changes.

 

Basic Operation 

Status 

Controller 

The U700 controller has five LED status lights.  These indicators represent the basic operational status of 
the controller. 
The Main Controller

 Status 

LED shows the current programming status of the controller.  In Normal 

mode, the light will flash twice followed by a delay.  This pattern repeats every two seconds.  In Wink 
mode, the light will flash fast for up to 60 seconds. 
The Second Module

 Status

 LED shows the communication status with the main controller.  The light 

flashes green during normal operation, and red if communication is lost. 
The 

Lon Rx/Tx

 LED shows activity on the LonWorks® network. 

The 

RS485 Rx/Tx

 and 

Ethernet Act/Lnk

 LEDs are not used on U700 Monitoring Node. 

Summary of Contents for MT-700 Series

Page 1: ...Supermarket Control Solutions Installation and Operation Manual PUID 70 MTA 1017 R4 0 11221...

Page 2: ...ther materials provided from Parker or its subsidiaries or authorized distributors To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based up...

Page 3: ...ller module For DIN rail mounting mount the DIN rail in the desired location and attach the two controller modules to the rail separately First install the MT 722A controller at the left end of the DI...

Page 4: ...Transformer 24VAC 250VA BAS Building Automated Station Data cable Passive or powered sensors Passive or powered sensors Passive or powered sensors Passive or powered sensors Passive or powered sensors...

Page 5: ...perature Sensors Connect one lead to Signal Common connect the other lead to the desired Universal Input UI Temperature sensors are not polzarized Pressure Transducers Connect the Red lead to controll...

Page 6: ...Node Next for the U700 controller to be paired with Alliance and the firmware installed on the controller 1 Click on the newly created node icon 2 In the configuration window that opens give the cont...

Page 7: ...ify the upper lower threshold above below which an alarm will be generated Set Time specify the time delay during which the sensor must remain outside of the high low limit before an alarm is generate...

Page 8: ...cumulative alarm time if applicable The graph s zoom level can be set to display between 1 Hour and 4 Days of data at a time and the statistical data displayed along the right hand side is continuousl...

Page 9: ...d feature built into Micro Thermo monitoring is Cumulative Alarming The Cumulative Alarm monitors an input over an extended period of time usually 24 or 48 hours and calculates the total time that the...

Page 10: ...different controllers At any point a sensor can be changed back to Single Usage and the Alarm Set 1 settings will be retained To configure a sensor for dual use first open the Details tab in the sens...

Page 11: ...and select the Calculation tab Local and Remote resources must be configured before the calculation blocks can be set up For Remote sources click one of the Remote Source buttons and specify the Type...

Page 12: ...1 LonWorks TP FTT 10 Network 78kbps Wire 18 AWG 7 26 stranded unshielded twisted pair Belden 8461 or equivalent Operating Temperature 13 F to 140 F 25 C to 60 C 0 90 RH non condensing Storage Temperat...

Page 13: ...MT 700 series installer guide Page 13 U700 Field Wiring 4A Fuse...

Page 14: ...ometric 15 Vdc output 100 mA max internally limited Communication LonWorks port TP FT 10 channels transceiver featuring polarity insensitive free topology star daisy chain bus loop or mixed topology w...

Page 15: ...0K of SRAM 4K on battery back up for data Real Time Clock with battery back up Flash memory 2Mbytes with file system for application or data logging file storage on SPI microcontroller external Bus EE...

Page 16: ...5V 15V outputs Inputs Universal input x16 0 10V thermistor RTD Outputs 5 0 Vdc output 200 mA max internally limited ratiometric 15 Vdc output 100 mA max internally limited Indicators Buttons Status Gr...

Page 17: ...orm C Dry contact 5A 250V Max fuse protected 2AG 5A 250V 5 0 Vdc output 100 mA max internally limited ratiometric 15 Vdc output 100 mA max internally limited Indicators Buttons Status Green LED Status...

Page 18: ...4 0 10V thermistor RTD Outputs MVC output x2 Modulating Valve Control for bipolar 4 wire stepper motor Current limited Motor coil resistance range 6 to 100 1 4 W to 6 W 5 0 Vdc output 65 mA max intern...

Page 19: ...lay output x4 1 form C Dry contact 5A 250V Max fuse protected 2AG 5A 250V 5 0 Vdc output 100 mA max internally limited ratiometric 15 Vdc output 100 mA max internally limited Indicators Buttons Status...

Page 20: ...per motor 2 banks of 4 outputs with only one output active per bank Current limited Inactive outputs are high impedance no holding current Motor coil resistance range 6 to 100 1 4 W to 6 W Indicators...

Page 21: ...utton x8 To manually activate relays RO 1 to 8 Hardware features Microcontroller ARM Cortex M0 48MHz 64Kbytes of flash memory for program 8K of SRAM for data 20 FE 2018 20 FE 2018 Relay Outputs RO Use...

Page 22: ...oftware selectable Input Precision coming Power supply outputs for sensors 5V ratiometric 15V see specific module specification for maximum load 26 MR 2014 Analog Outputs AO Used on Main controller 6U...

Reviews: