Installation and servicing manual

Shell & Tube Cooler

 

8

Parker Hannifin Corporation

Hydraulics Group

Catalogue HY10-6014-UM/CN

Preventive Maintenance/Procedures

4.4 Before Operation

4.4.1 PIPE INSTALLATION CHECKUP

Ensure that the pipe is installed properly prior to 

operating the equipment. Oil and cooling water 

may leak when the pipe is not installed properly.

4.4.2 COOLING WATER SUPPLY

Check that the cooling water is being supplied prior to use. 

No heat exchanger effect will take place if the cooling water 

is not supplied. See PRIOR TO INSTALLATION for cooling 

water quality.

4.4.3 DRAIN PLUG

Ensure that water and oil drain plugs at the bottom are 

closed prior to operating. 

4.5 Operation

1. 

Ensure the entire system is clean before starting 

operation to prevent clogging of tubes or shell side.

2. 

Open vent connections before starting up. A 

heat exchanger is a pressure vessel designed 

for operation at certain specific limits of pressure 

and temperature. The cooling or process system, 

which includes the heat exchanger, must be 

safeguarded with safety valves and controls so 

that these heat exchanger design conditions are 

not exceeded. All operating personnel should be 

made aware of these specific design pressures and 

temperatures.

3. 

Start Operating the system. If in doubt, contact 

Parker OLAER Suzhou office for specific instructions.

4. 

After the system is completely filled with the 

operating fluids and all air has been vented, close all 

manual vent connections.

5. 

Bolting on all gasket or packed joints should be 

retightened after the heat exchanger has reached 

operating temperatures to prevent leaks and gasket 

failures. Refer to tightening torque table in annex of 

this shell and tube cooler manual.

6. 

Do not operate the heat exchanger under pressure 

and temperature conditions in excess of those 

specified on the name plate.

7. 

Drain all fluids when shutting down to eliminate 

possible freezing and corrosion.

8. 

In all installation there should be no pulstation of 

fluids since this cause vibration and will result in 

reduced operating life.

5. Preventive Maintenance

5.1 Inspection and Cleaning

External and internal inspection and cleaning by 

disassembling the shell and tube cooler are required every 6 

months if used on application using clean fluid, as per water 

quality table in annex of the shell and tube manual, and 

equipped with filtration system.

For coolant from other origins, external and internal 

inspection and cleaning by disassembling the shell and tube 

cooler are required every 4 months.

5.2 Cleaning

During the inspection and cleaning process at the required 

time intervals, check the cooler carefully for any sign of wear 

or corrosion (internal and external) that could lead to product 

malfunctioning or leakage.

Any component presenting any sign of advanced wear should be 

analyzed carefully and replaced if necessary, to ensure product 

function and reliability.

5.3 Replacable Components 

Shell and tube cooler components subject to wear and that 

potentially need to be replaced during preventive maintenance 

process are the following : tube bundle, floating Cover and 

stationery cover, O-Ring, Gaskets.

Refer to the product exploded view in annex of this manual, 

or to the product technical specifications for components part 

number. 

5.4 Record 

Maintenance tasks performed on the shell and tube cooler shall 

be recorded and available at any time.

Product maintenance record should be provided in case of faulty 

product or warranty claim.

6. Maintenance Procedures

6.1 Remove O-Ring or Gasket

Ensure to remove all the pressure in the shell and 

tube heat exchanger before disconnecting any bolt, 

connection, plug or cover.

6.1.1 WHEN TO REMOvE

• 

O-Ring or gasket may be needed to be replaced when a 

leak occurs arround them.

• 

Replace O-Ring and gasket during periodic pipe cleaning.

6.1.2 HOW TO REMOvE

For the name of the components, please refer to “3. Product 

Parts Name”.

1. 

Unscrew the bolts, the spring washers and washers.

2. 

Remove the bolts, the spring washers and washers.

3. 

Remove the covers.

4. 

Remove the gaskets (if you only need to change the 

gaskets, change them and repeat the above steps 

reversely, 4 to 1).

5. 

Beat with a rubber hammer on the tube sheet on one 

side until the other side is out of the shell. DO NOT USE A 

HARD TOOL. This will result in tube damage and result in 

cooler leakage.

6. 

Remove the first O-Ring.

7. 

Beat on the other side (on the tube sheet) until tube 

bundle is out of the shell.

8. 

Remove the second O-Ring.

9. 

Change them and repeat the above steps reversely, 8 to 1 

steps reversely (in order of 1, 2,3 and 4) to  

complete assembling.

Summary of Contents for HY10-6014-UM/CN

Page 1: ...Shell Tube Cooler Installation and servicing manual aerospace climate control electromechanical filtration fluid gas handling hydraulics pneumatics process control sealing shielding...

Page 2: ...Installation and servicing manual Shell Tube Cooler 2 Parker Hannifin Corporation Hydraulics Group Catalogue HY10 6014 UM CN...

Page 3: ...0 6014 UM CN Contents Introduction Directions 4 1 Safety Notice 4 2 Product Overview 5 3 Product Parts Name 6 4 Installation 6 5 Preventive Maintenance 8 6 Maintenance Procedures 8 7 Emergency Measure...

Page 4: ...ope 1 2 Important Safety Notes 1 2 1 CAUTION This symbol point outs general safety notice 1 2 2 OPERATOR MANUAL Read carefully and ensure that you understand the product prior to use it Faillure to fo...

Page 5: ...iate oil viscosity index in the hydraulic systems extends the life cyle of the valves pumps and parts in the system thereby reducing maintenance costs of the system The Shell Tube Cooler will provide...

Page 6: ...4 2 Installation Directions Ensure that you check the safety instructions accompanying the product when handling moving and or installing it Cooler when installed vertically should be installed with...

Page 7: ...r located as close to the heat exchange as possible 4 Provide necessary air vent valves for the heat exchanger so that it can be purged to prevent or relieve vapor or gas binding on either the tube si...

Page 8: ...d tube cooler are required every 6 months if used on application using clean fluid as per water quality table in annex of the shell and tube manual and equipped with filtration system For coolant from...

Page 9: ...he shell and tube cooler or hydraulic system caused by wrong shell and tube cooler assembly and or shell and tube cooler not pressure tested prior commissioning to the hydraulic system Remove Gasket R...

Page 10: ...and oil may mix inside the heat exchanger which may result in damage to your system Please pay extra attention to this issue Broken copper pipe may not be repaired or replaced by the customers Ensure...

Page 11: ...Ion Sulfate mgSO42 L 200 X Calcium Hardness mgCaCO3 L 150 X Acid Consumption mgCaCO3 L 100 X Total Hardness mgCaCO3 L 200 X Ref item Fe mgFe L 1 0 X X Cu mgCu L 0 3 X Ion Sulfide mgS2 L Not detected...

Page 12: ...Installation and servicing manual Shell Tube Cooler 12 Parker Hannifin Corporation Hydraulics Group Catalogue HY10 6014 UM CN...

Page 13: ...Installation and servicing manual Shell Tube Cooler 13 Parker Hannifin Corporation Hydraulics Group Catalogue HY10 6014 UM CN 1 1 1 1 2 1 2 1 1 2 2 1 2 3 1 2 4 1 2 5 1 3 1 3 1 1 3 2 1 4 1 4 1...

Page 14: ...S6 4 400 455 400 290 55 150 75 250 75 174 5 100 170 9 13 OST S6 4 530 1 589 530 420 55 150 140 250 140 174 5 100 170 9 15 OST S6 5 680 1 1 733 680 570 55 164 162 318 200 225 5 130 180 9 27 OST S6 8 67...

Page 15: ...be Cooler 15 Parker Hannifin Corporation Hydraulics Group Catalogue HY10 6014 UM CN 3 1 1 9 1 M14x1 5 2 1 10 1 3 1 11 1 4 1 12 1 13 1 5 1 14 1 6 1 15 16 7 2 O 16 16 8 1 M14x1 5 17 16 4 4 1 1 2 3 4 5 6...

Page 16: ...n and servicing manual Shell Tube Cooler 16 Parker Hannifin Corporation Hydraulics Group Catalogue HY10 6014 UM CN 4 3 2 0 C 100 C 14 4 3 3 4 3 4 1 O 2 3 4 5 6 4 3 5 1 2 3 30 4 5 6 4 4 4 4 1 4 4 2 4 4...

Page 17: ...ervicing manual Shell Tube Cooler 17 Parker Hannifin Corporation Hydraulics Group Catalogue HY10 6014 UM CN 1 2 3 4 5 6 7 5 5 1 6 4 5 2 5 3 O 5 4 6 6 1 O 6 1 1 O O 6 1 2 1 2 3 4 4 1 5 6 O 7 8 O 9 O 8...

Page 18: ...ng manual Shell Tube Cooler 18 Parker Hannifin Corporation Hydraulics Group Catalogue HY10 6014 UM CN 6 2 6 2 1 6 2 2 O 5 1 O 1 4 6 3 6 3 1 3 6 3 2 1 6 1 2 1 8 2 3 6 3 3 7 7 1 O 7 2 7 3 1 2 3 4 7 4 1...

Page 19: ...289 0805 www parker com Ph 25 C 6 5 8 2 X X S cm 25 C 800 X X mgcL L 200 X mgSO42 L 200 X mgCaCO3 L 150 X mgCaCO3 L 100 X mgCaCO3 L 200 X Fe mgFe L 1 0 X X Cu mgCu L 0 3 X mgS2 L X mgNH4 L 1 0 X mgSiO...

Page 20: ...7 66 75 34 00 parker norway parker com PL Poland Warsaw Tel 48 0 22 573 24 00 parker poland parker com PT Portugal Leca da Palmeira Tel 351 22 999 7360 parker portugal parker com RO Romania Bucharest...

Reviews: