6

VAC-SIF-05

Training & Maintenance Manual

CVX0260B

Parker Hannifin Corporation

Pneumatic Division

Richland, Michigan

www.parker.com/pneumatic

Blow-Off

Adjustment Screw

Blow-Off

Pilot Valve

Vacuum

Pilot Valve

Blow-off Adjustment

The volume of air during the blow-off function to release the 
workpiece can be set by turning the needle adjustment up 
or down. Access the needle adjustment through opening of 
protective cover (topside).

Units of Measure

The pressure sensor has an LED function that indicates 
the degree of pressure in the system. The units can be 
changed, but are factory set to inHg (inches of Mercury). 
The relationship of inHg with a gauge pressure scale and 
absolute pressure scare are in the following table. In general, 
the negative sign on the gauge pressure scale is assumed 
and may or may not be noted on documentation.

 

Negative Gauge 

Absolute  

 

Pressure 

Pressure 

Inches of Mercury 

 

PSIG 

PSIA 

inHg

 

14.7 

 

 Atmospheric Pressure at Sea level

 

-1.5 

13.2 

3

 

-3.0 

11.7 

6

 

-4.5 

10.2 

 

 Typical Porous Vacuum level

 

-6.0 

8.7 

12

 

-7.5 

7.2 

15

 

-9.0 

5.7 

18

 

-10.5 

4.2 

21 

 

 Typical Non-Porous Vacuum level

 

-12.0 

2.7 

24

 

-13.5 

1.2 

27

 

-14.7 

29.92 

 

 Perfect Vacuum (Zero Reference Pressure)

Basic Vacuum Pressure Measurements Units

Specifications

Specifications

CVX0260B Specifications

 

Media 

Non-lubricated Dry Air

 

Pressure Port 

3/8" G, 3/8" NPT Through Port 

 

Vacuum Ports 

2 Individual Vacuum Channels  

 

  3/8" G Ports or 3/8" NPT

 

Operating Temperature 

32° to 122°F (0° to 50°C)

 

Operating Pressure 

70 PSI

 

Vacuum Filtration 

130 µm

 

Noise level 

72dB

 

Air Consumption 

10.41 SCFM

 

Maximum Vacuum level 

-25.0 inHg

Control Valve Specifications

 

3-way 

Pilot Valves

 

Manual Operation 

Manual Overrides Available

 

Electrical Connector 

DIN type w/LED and Diode  

 

  Protection, IP65 Rating

 

Power Supply 

24VDC ± 10%

 

Power Consumption 

1.2W

 

Pressure 

70 PSI

Sensor Specifications

 

Media 

Non-lubricated Dry Air

 

Operating Temperature 

32° to 122°F (0° to 50°C)

 

Humidity 

40 to 85% R.H.

 

Electrical Connection 

4-Pin, M8 Connector

 

Power Supply 

10.8 to 30 VDC,

 

  Ripple Vp-p 10% Max. 

 

  Diode Protection

 

Display 

3-Digit, 7-Segment LED

 

Units of Measure 

inHg, mmHg, bar, kPa, 

 

  Selectable

 

Display Resolution 

0.1 kPa, 0.001 bar, 1 mmHg,

 

  0.1 inHg Selectable

 

2-Switch Outputs

  Individually Selectable N.O or  

 

  N.C., 80mA, 30V with  

 

 

  Overcurrent Protection, 

 

  LED Status

 

Operating Mode 

Hysteresis Adjustable

 

Response Time

  2ms

 

Repeatability

  ± 0.2% F.S.

 

General Protection

  CE Rated

 

Current Consumption

  <55mA

 

Emergency Stop Operating System Specifications

 

Two-way Valve 

Diaphragm Actuated,  

 

 

  Pneumatic Output

 

Media 

Non-lubricated Air, Dry Air

 

Operating Range 

-4.5 to -25 inHg Vacuum

 

Pressure Operating  Range 

70 PSI

 

Accuracy 

± 1.5 inHg

 

Port Connection 

M5 Female

 

Air Supply 

Normally Closed

 

Emergency Stop Electrical Valve Specifications

 

3-way Valve 

Direct Acting

 

Media 

Air

 

Operating Range 

70 PSI

 

Electrical Connection 

DIN Connector w/LED and  

 

  Diode Protection, IP65

 

Operating Voltage 

24VDC ± 10%

 

Power Consumption 

1.8W

 

Current 

0.075A

Summary of Contents for CVX0260B

Page 1: ...Pneumatic Division Richland Michigan 49083 Training Maintenance Manual for CVX0260B Vacuum Generators VAC SIF 05 Training Maintenance Manual CVX0260B ISSUED July 2013 Supersedes November 2012...

Page 2: ...pilot valve blow off needle control valve pressure sensor vacuum check valve vacuum filter and exhaust filter Each Vacuum Generator is mounted to a 2 Station bar manifold with an optional electrical...

Page 3: ...level within the system The vacuum operated pilot valve is turned back on at a vacuum level n_2 The hysteresis feature of the vacuum sensor can maintain the vacuum level of the system indefinitely wh...

Page 4: ...tput 1 to Activate Vacuum VAC ON Vacuum Begins Vacuum Mode Continues Part Presence Command VAC ON Sensor Output 1 N C Preset n_1 18 inHg Sensor Output 2 N O Preset P_3 10 inHg n_1 n_2 P_3 P_4 Robot Co...

Page 5: ...e IDLE state Restore Power When the output power is restored with input and output power the unit will return to the output status of the PLC PC program Factory Sensor Settings All factory settings ca...

Page 6: ...Individual Vacuum Channels 3 8 G Ports or 3 8 NPT OperatingTemperature 32 to 122 F 0 to 50 C Operating Pressure 70 PSI Vacuum Filtration 130 m Noise Level 72dB Air Consumption 10 41 SCFM Maximum Vacuu...

Page 7: ...Not Shown 14 PSCVXDNB DeviceNet PSCVXD3B M12 Discrete PSCVXN3B 18 Pin Discrete 15 MPS V23C NC NPN Sensor PSCVXDNB PSCVXD3B PSCVXN3B Contents The CVX0260B is supplied with four 4 M5 x 1 Socket Head Cap...

Page 8: ...ach CVX0260B incorporates a small filter housed on the body to protect the internal components of the generator Additional maintenance of this filter will also vary with each environment and applicati...

Page 9: ...PC Program Sensor Output 1 ou1 to N O Manually changing sensor OU1 from N C to N O LED should change state See Sensor Verify Sensor Output 1 settings Programming for changing Output status Verify tha...

Page 10: ...cuum confirmation High Signal to the PLC PC at set point P_3 prior to part on Log Part On and Part Off Vacuum Check Exhaust and Vacuum Filters for Pressure P_3 must be between Part Off obstructions to...

Page 11: ...ify H 1 is illuminated at 0 inhg ou1 N C N O no signal will be passed through the Air Economizing Setting Sensor Output 1 must be set to sensor to activate the vacuum pilot from the Normally Closed Pa...

Page 12: ...p Vacuum CVX0260BE0SDN Dimensions 2 56 65 0 3 51 89 2 4 31 109 5 1 76 44 6 2 24 57 0 1 97 50 0 Blow Off Valve Mounting Holes 4 5 5mm Blow Off Needle Adjustment Vacuum Valve Vacuum Filter Housing 67 17...

Page 13: ...try and the two sensors The auxiliary power bus pro vides power for the vacuum solenoids and blow off solenoids No external PLC programming is required for Air Economizing Functions because this funct...

Page 14: ...Bit Strobed and Polled messaging General Description The Convum Vacuum Generator operates as a Group II Only slave on the DeviceNet network The unit supports the following types of messaging Explicit...

Page 15: ...as the Poll response Sensor 1 Dip Switches VAC1 BL01 BL02 VAC1 Sensor 2 1 2 3 4 5 6 7 8 Sensor 1 VAC2 BL02 BL01 VAC1 Sensor 2 O N 1 2 3 4 5 6 7 8 O N Network Status Module Status Factory DIP Switch Se...

Page 16: ...XN3B M18 24VDC Optional Mounting Plate 13 00 330 2 3 50 101 6 12 18 309 4 2 00 50 8 50 12 7 1 00 25 4 28 7 13 Dia Thru Typ 4 Places 27 6 85 Typ 4 Places 438 11 13 Dia Typ 4 Places 2 56 65 0 3 51 89 2...

Page 17: ...put Power R Not Used S Not Used T Not Used U Not Used 24VDC J K M N B H S R D E G F L A T U P C Face View Male 18 Pin Connector Notes Pin B F are jumpered inside unit Either pin can connect power to b...

Page 18: ...red by paint etc If masking is not possible contact your local representative for replacement labels WARNING FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND OR SYSTEMS DESCRIBED HERE...

Page 19: ...tore Final Key returns sensor to current pressure reading 2 1 Troubleshooting Verify ou1 is set NC LED 1 will be ON if NC Check DIN LED for electrical connection Use Manual Overrides to confirm manual...

Page 20: ...change to store Press Up or to change to store Final Key returns sensor to current pressure reading 2 1 Troubleshooting Verify ou1 is set NC LED 1 will be ON if NC Check DIN LED for electrical connect...

Page 21: ...x 1x 1x Press button for more than 3 seconds NO Mode 2 5ms Lock Mode Measure mode Key lock mode can prevent operation mistakes Press button for less than 5 seconds Key lock unlock mode Use the or butt...

Page 22: ...and then restart If error condition remains please return to factory for inspection Er6 Internal system error Er7 Internal data error Output type Manual setting mode Auto setting mode Do not use on C...

Page 23: ...y any customer Buyer shall be governed by all of the following Terms and Conditions Buyer s order for any item described in its document when communicated to Seller verbally or in writing shall consti...