background image

14

VAC-SIF-05

Training & Maintenance Manual

CVX0260B

Parker Hannifin Corporation

Pneumatic Division

Richland, Michigan

www.parker.com/pneumatic

Poll Command and Digital Outputs 

The unit has four (4) outputs. The outputs are bitmapped to 
the  lower  nibble  of  the  byte. The  outputs  are  turned  ON  by 
sending a “1” to their respective bits, and they are turned OFF 
by sending a “0” to their respective bits. The following are the 
polled data bytes to actuate the four outputs:

  Polled Command Date 

Action

 

0x01 

Turns ON Channel 1 Vacuum

 

0x02 

Turns ON Channel 1 Blow-off

 

0x04 

Turns ON Channel 2 Vacuum

 

0x08 

Turns ON Channel 2 Blow-off

Poll Response and Digital Inputs

Inputs indicate that a part is present on either of the two (2) 
channels. The inputs are bit mapped to the lower nibble of the 
byte in the polled response. The following are the feedback 
signal meanings for the two (2) inputs:

 Polled Response Date  Interpretation

 

0x01  Channel 1, Part Present

 

0x02  Channel 2, Part Present

Explicit Messaging and Digital Outputs

The outputs are accessed through the Discrete Output Point 
Object, Class Code 0x09.

 

Output 

Instance No. 

Attribute

 

Vacuum 1 

3

 

Blow-off 1 

3

 

Vacuum 2 

3

 

Blow-off 2 

3

Explicit Messaging and Digital Inputs 

The  inputs  are  also  accessed  through  the  Discrete  Input 
Object, Class Code 0x08, with Explicit messaging. 

 

Input  Instance No.  Attribute   Explicit 

 

 

 

 

Response

 Channel 1, Part Present 

0x01

 Channel 2, Part Present 

0x01

Change of State Messaging

In this mode of messaging, date is sent to the Master when 
the Slave device inputs change. These device inputs are the 
two-part present indications. Change of State messaging can 
send acknowledged or unacknowledged date.
For  acknowledged  date,  the  Acknowledge  Timer  in  the 
Acknowledge Handler Object (Class Code 0x2B, Attribute 1) 
sets the time to wait before resending the data. The range of 
values for this attribute is 1 to 65,635ms. Zero is invalid. The 
default value is 16ms.
A  Slave  can  be  allocated  for  Cyclic  or  Change  of  State  but 
not both. Change of State can function with Bit-Strobed and 
Polled messaging.

General Description

The Convum Vacuum Generator operates as a Group II Only 
slave  on  the  DeviceNet™  network.  The  unit  supports  the 
following types of messaging: Explicit, Polled, Cyclic, Change 
of  State,  and  Bit  Strode.  It  does  not  support  the  Explicit 
Unconnected Message Manager (UCMM).
The  Cyclic,  Change  of  State,  and  Bit  Strobe  types  of 
messaging were incorporated into the product beginning with 
Firmware Revision No 4.23 or later. This can be verified by the 
label on the microcontroller on the p.c. board.
The unit has four (4) digital outputs and two (2) digital inputs. 
The digital outputs control two (2) vacuum states and two (2) 
blow-off states. The two (2) digital inputs are two-part present 
indications  (one  for  each  channel)  and  an  auxiliary  power 
voltage indicator.
The  DeviceNet™  power  bus  supplies  power  for  the 
DeviceNet™ circuitry and the two (2) Convum

 

sensors. The 

auxiliary power bus provides power for the vacuum solenoids, 
the  blow-off  solenoids,  and  the  solenoid  for  the  Emergency 
Stop circuit. The following are the power requirements for the 
DeviceNet™ circuitry.

Voltage Range .12.5 to 24VDC
Current ..........................150Ma

The following is the product information for the DeviceNet™ 
interface:

Vendor ID (VendCode) ......510
Device Type (ProdType).........7
Product Code (ProdCode) .....1

Bytes Produced (polled) ........1
Bytes Consumed (polled) ......1

The following are the power requirements for the circuitry on 
the auxiliary power bus:

Voltage Range ............. 24VDC
Current ................. 400Ma max.

MAC ID Settings

The MAC ID is set with the lowest six (6) positions on the 8-Pin 
DIP switch located on the p.c. board. The least significant digit 
of the setting is on position 1 and the most significant digit is 
on position 6. To have a switch be read as a “1”, set it to the 
“ON” position. To have the switch be read as a “0”, set it to the 
“OFF” position.

Baud Rate Settings

The  baud  rate  is  set  with  the  two  highest  positions  on  the 
8-Pin DIP switch. The lower digit is position 7 and the higher 
digit is position 8. To have a switch be read as a “1”, set it to 
the “ON” position. To have the switch be read as a “0”, set it to 
the “OFF” position. The following are the DIP switch settings 
for the baud rate:

 

Switch Settings (8 and 7)  Baud Rate

 

00 

125k

 

01 

250k

 

10 

500k

 

11 

Invalid

DeviceNet™ Information

Summary of Contents for CVX0260B

Page 1: ...Pneumatic Division Richland Michigan 49083 Training Maintenance Manual for CVX0260B Vacuum Generators VAC SIF 05 Training Maintenance Manual CVX0260B ISSUED July 2013 Supersedes November 2012...

Page 2: ...pilot valve blow off needle control valve pressure sensor vacuum check valve vacuum filter and exhaust filter Each Vacuum Generator is mounted to a 2 Station bar manifold with an optional electrical...

Page 3: ...level within the system The vacuum operated pilot valve is turned back on at a vacuum level n_2 The hysteresis feature of the vacuum sensor can maintain the vacuum level of the system indefinitely wh...

Page 4: ...tput 1 to Activate Vacuum VAC ON Vacuum Begins Vacuum Mode Continues Part Presence Command VAC ON Sensor Output 1 N C Preset n_1 18 inHg Sensor Output 2 N O Preset P_3 10 inHg n_1 n_2 P_3 P_4 Robot Co...

Page 5: ...e IDLE state Restore Power When the output power is restored with input and output power the unit will return to the output status of the PLC PC program Factory Sensor Settings All factory settings ca...

Page 6: ...Individual Vacuum Channels 3 8 G Ports or 3 8 NPT OperatingTemperature 32 to 122 F 0 to 50 C Operating Pressure 70 PSI Vacuum Filtration 130 m Noise Level 72dB Air Consumption 10 41 SCFM Maximum Vacuu...

Page 7: ...Not Shown 14 PSCVXDNB DeviceNet PSCVXD3B M12 Discrete PSCVXN3B 18 Pin Discrete 15 MPS V23C NC NPN Sensor PSCVXDNB PSCVXD3B PSCVXN3B Contents The CVX0260B is supplied with four 4 M5 x 1 Socket Head Cap...

Page 8: ...ach CVX0260B incorporates a small filter housed on the body to protect the internal components of the generator Additional maintenance of this filter will also vary with each environment and applicati...

Page 9: ...PC Program Sensor Output 1 ou1 to N O Manually changing sensor OU1 from N C to N O LED should change state See Sensor Verify Sensor Output 1 settings Programming for changing Output status Verify tha...

Page 10: ...cuum confirmation High Signal to the PLC PC at set point P_3 prior to part on Log Part On and Part Off Vacuum Check Exhaust and Vacuum Filters for Pressure P_3 must be between Part Off obstructions to...

Page 11: ...ify H 1 is illuminated at 0 inhg ou1 N C N O no signal will be passed through the Air Economizing Setting Sensor Output 1 must be set to sensor to activate the vacuum pilot from the Normally Closed Pa...

Page 12: ...p Vacuum CVX0260BE0SDN Dimensions 2 56 65 0 3 51 89 2 4 31 109 5 1 76 44 6 2 24 57 0 1 97 50 0 Blow Off Valve Mounting Holes 4 5 5mm Blow Off Needle Adjustment Vacuum Valve Vacuum Filter Housing 67 17...

Page 13: ...try and the two sensors The auxiliary power bus pro vides power for the vacuum solenoids and blow off solenoids No external PLC programming is required for Air Economizing Functions because this funct...

Page 14: ...Bit Strobed and Polled messaging General Description The Convum Vacuum Generator operates as a Group II Only slave on the DeviceNet network The unit supports the following types of messaging Explicit...

Page 15: ...as the Poll response Sensor 1 Dip Switches VAC1 BL01 BL02 VAC1 Sensor 2 1 2 3 4 5 6 7 8 Sensor 1 VAC2 BL02 BL01 VAC1 Sensor 2 O N 1 2 3 4 5 6 7 8 O N Network Status Module Status Factory DIP Switch Se...

Page 16: ...XN3B M18 24VDC Optional Mounting Plate 13 00 330 2 3 50 101 6 12 18 309 4 2 00 50 8 50 12 7 1 00 25 4 28 7 13 Dia Thru Typ 4 Places 27 6 85 Typ 4 Places 438 11 13 Dia Typ 4 Places 2 56 65 0 3 51 89 2...

Page 17: ...put Power R Not Used S Not Used T Not Used U Not Used 24VDC J K M N B H S R D E G F L A T U P C Face View Male 18 Pin Connector Notes Pin B F are jumpered inside unit Either pin can connect power to b...

Page 18: ...red by paint etc If masking is not possible contact your local representative for replacement labels WARNING FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND OR SYSTEMS DESCRIBED HERE...

Page 19: ...tore Final Key returns sensor to current pressure reading 2 1 Troubleshooting Verify ou1 is set NC LED 1 will be ON if NC Check DIN LED for electrical connection Use Manual Overrides to confirm manual...

Page 20: ...change to store Press Up or to change to store Final Key returns sensor to current pressure reading 2 1 Troubleshooting Verify ou1 is set NC LED 1 will be ON if NC Check DIN LED for electrical connect...

Page 21: ...x 1x 1x Press button for more than 3 seconds NO Mode 2 5ms Lock Mode Measure mode Key lock mode can prevent operation mistakes Press button for less than 5 seconds Key lock unlock mode Use the or butt...

Page 22: ...and then restart If error condition remains please return to factory for inspection Er6 Internal system error Er7 Internal data error Output type Manual setting mode Auto setting mode Do not use on C...

Page 23: ...y any customer Buyer shall be governed by all of the following Terms and Conditions Buyer s order for any item described in its document when communicated to Seller verbally or in writing shall consti...

Page 24: ...21 4PDN Option 2 E mail pdnapps parker com Customer Support Phone 877 321 4PDN Option 1 E mail pdncustsvc parker com Web site www parker com pneumatics Parker Hannifin Corporation Pneumatic Division 8...

Reviews: