192-120103 N13 C3I20T11 / C3I32T11 December 2010
35
3.3.5.
Compax3Sxxx V2
In this chapter you can read about:
Main voltage supply C3S connector X1 ........................................................................... 35
Braking resistor / high voltage DC C3S connector X2 ..................................................... 36
3.3.5.1
Main voltage supply C3S connector X1
By cyclically switching on and off the power voltage, the input current
limitation can be overloaded, which will cause a device error.
Therefore please wait at least 2 minutes after switching off before you switch
the device on again!
Power supply plug X1 for 1 AC 230VAC/240VAC devices
PIN
Designation
1
L
2
N
3
PE
Mains connection Compax3S0xxV2 1AC
Controller type
S025V2
S063V2
Supply voltage
Single phase 230VAC/240VAC
80-253VAC / 50-60Hz
Input current
6Arms
13Arms
Maximum fuse rating per device
(=short circuit rating)
10 A (MCB miniature
circuit breaker, K
characteristic)
16A (automatic circuit
breaker K)
* for
UL conform operation
(see on page 22), a miniature circuit breaker, K
characteristic, Type S203 is to be used.
Caution - Risk of Electric Shock!
Always switch devices off before wiring them!
Dangerous voltages are still present until 10 min. after switching off the power
supply.
Power supply plug X1 for 3AC 230VAC/240VAC devices
PIN
Designation
1
L1
2
L2
3
L3
4
PE
Device protection