Mains connection Compax3S1xxV2 3AC
Controller type
S100V2
S150V2
Supply voltage
Three phase 3* 230VAC/240VAC
80-253VAC / 50-60Hz
Input current
10Arms
13Arms
Maximum fuse rating per device
(=short circuit rating)
16A
20A
MCB miniature circuit breaker, K characteristic
* for
UL conform operation
(see on page 22), a miniature circuit breaker, K
characteristic, Type S203 is to be used.
The 3AC V2 devices must only be operated with three phases!
Caution - Risk of Electric Shock!
Always switch devices off before wiring them!
Dangerous voltages are still present until 10 min. after switching off the power
supply.
3.3.5.2
Braking resistor / high voltage DC C3S connector X2
The energy generated during braking operation is absorbed by the Compax3
storage capacity.
If this capacity is too small, the braking energy must be drained via a braking
resistor.
Braking resistor / high voltage supply plug X2 for 1AC
230VAC/240VAC devices
PIN
Designation
1
factory use
2
- braking resistor (not short-circuit protected!)
3
PE
4
+ braking resistor (not short-circuit protected!)
5
factory use
Braking operation Compax3S0xxV2 1AC
Controller type
S025V2
S063V2
Capacitance / storable energy
560
µ
F / 15Ws
1120
µ
F / 30Ws
Minimum braking- resistance
100
Ω
56
Ω
Recommended nominal power rating
20 ... 60W
60 ... 180W
Maximum continuous current
8A
15A
The power voltage DC of two Compax3 1AC V2 devices (230VAC/240VAC
devices) must not be connected.
Caution!
Caution!