![Parker 598P Applications Manual Download Page 17](http://html.mh-extra.com/html/parker/598p/598p_applications-manual_755627017.webp)
11 of 20
598P/599P Application Manual
Technical Specification
ENVIRONMENTAL DATA
Operating Temperature
0 to +45°C
Storage Temperature
-25 to +55°C
Shipping Temperature
-25 to +70°C
Enclosure Rating
IP20
Altitude Rating
Maximum Altitude 500 metres.
De-rate the Output at 1% per 200 metres.
Humidity
Maximum 85% relative Humidity at 45°C non-condensing.
Atmosphere
Non flammable, non-corrosive and dust free.
Climatic
Class 3k3 as defined by EN60721-3-3 (1995).
Safety
Designed to : -
Europe
EN50178 when enclosure mounted.
Overvoltage Category III
Pollution Degree 2
ELECTRICAL RATINGS
Coding Supply Voltage
110 – 240 Vac ±10% 3ph – Low Voltage Build
220 – 500 Vac ±10% 3ph – Medium Voltage Build
380 – 690 Vac ±10% 3ph – High Voltage Build
Field Supply Voltage
110 – 240 Vac ±10% 1ph – Low Voltage Build
*220 – 500 Vac ±10% 1ph – Medium Voltage Build
*380 – 690 Vac ±10% 1ph – High Voltage Build
*
The field supply of the 220-500V and 380-690Vac rated products must
be derived from line-to-line of a 3 phase supply, NOT from line-to-neutral.
Supply Frequency
50/60 Hz ±10%
Armature Thyristor
Firing Isolation
Suitable for external stack supply system rated:
Overvoltage Category III
Max. 500Vac rms for Medium Voltage Build
Max. 690Vac rms for High Voltage Build
Output Current
60 Amps dc naturally cooled - 120 amps dc Force Cooled.
De-rate linearly at 1% per °C above rated temperature.
Supply Current
Field Coding
(1 times Field Current dc value) Amps 1ph ac.
Nominal 3ph ac.
Field Output Voltage
(0.9 times 1ph Supply Voltage) V dc
Total Losses
(3 times Idc out) Watts.
Auxiliary Supply
110 – 240 Vac ±10% 1ph – Naturally Cooled.
110 – 120 Vac ±10% 1ph – Force Cooled 115 Vac Fan configuration.
220 – 240 Vac ±10% 1ph – Force Cooled 230 Vac Fan configuration.
Auxiliary Supply Current SMPS Quiescent Current – 500mA 115 Vac or 250mA 230 Vac i.e. 50 VA.
Fan Current - 270mA @ 115 Vac or 135mA @ 230 Vac.
Auxiliary Supply Fuse
3 Amps.
FIELD FUSING
DC Output
Supply Voltage
Semiconductor I
2
t
Fuse Rating
Fuse I
2
t
Parker SSD Part
No.
60 Amps
500 Vac
19100 A
2
s
80 amps
2550 A
2
s
CH570084
120 Amps
500 Vac
19100 A
2
s
125 amps
8500 A
2
s
CH571253
60 Amps
690 Vac
8830 A
2
s
80 amps
2550 A
2
s
CH570084
120 Amps
690 Vac
8830 A
2
s
125 amps
8500 A
2
s
CH571253
This manual was downloaded on www.sdsdrives.com