WVM_BASIS_EN_03—07/2016
27
In case of draught at the installation location as can be expected with
ventilation systems, passages or similar. This applies regardless of the room
temperature. Measure the draught flow rate in the vicinity of the dryer when
you are in doubt. Insulate the dryer if the flow rate exceeds 0.3 m/s in the
immediate vicinity of the dryer.
When a pressure dew point exceeding –40° C is to be supplied.
The dryer can first be delivered without insulation. Retrofit an insulation if the
desired pressure dew point cannot be attained due to the above criteria.
Noise emission
Heed the dryer’s noise emission when selecting the installation location (see
also page 15).
Stellfläche
The installation area must be level, solid and free from vibration. It must be
capable of bearing the dryer’s weight. You will find the dryer’s weight in the
technical data in the appendix. Please add another 10% to the dryer's weight
in your calculations. This will ensure the moisture trapped by the desiccant
later is accounted for.
Lateral clearances
The dryer should be erected with
sufficient clearance above, to the
sides and behind so that
maintenance work can be carried
out and the drying agent can be
changed without hindrance (see
illustration).
Lifting devices
You should have lifting devices with
an adequate load capacity available
for assembling and maintaining
individual parts such as the vacuum
pump.
Required clearances at the top
and the sides of the unit = minimum 1 m
If in doubt, contact a specialised technician to carry out a site inspection. If you
have any queries in relation to the location of installation, please contact our
customer service department or our sales team.