Parker Balston A915000JA-LI555 Installation, Operation And Maintenance Manual Download Page 10

Bulletin TI-A915000JA-L1555 

Parker Balston Model 9150 

 

Hydrogen Generator

Parker Hannifin Corporation

Industrial Gas Filtration and Generation  Division

Lancaster, NY  • 1-800-343-4048 

www.parker.com/igfg

10

 

Cartridge 

Regeneration

Deionizer Bag

Replacement

Fuse Replacement

When the desiccant becomes saturated with moisture the blue indicating color will turn beige 
or gray or the orange indicating color will turn clear.  If the expended desiccant cartridge will be 
regenerated for later use, it must be stored in a moisture-proof container.

Cold Vacuum Oven -

 For best results place the desiccant cartridge in a 

cold vacuum oven

 

and ramp the temperature at 2°C/minute to 150°C while supplying a vacuum. 

 Do not exceed 

175

°

C

.  Regeneration will be complete in 8 hours.

Conventional Oven -

 If only a 

conventional oven

 is available, place the cartridge upright inside 

the oven to allow the moisture to leave from the top of the cartridge.  Apply the following ramp 
rate and procedure:

•  2°C/min from room temperature to 90°C, hold at 90°C for two hours.

•  2°C/min from 90°C to 150°C and hold at 150°C for 24 hours.

•  Cool the cartridge in a desiccator or low moisture environment until needed in the hydrogen 

generator.

For either method, do not exceed 175

°

C

.  The temperature will not affect the desiccant per-

formance; however, once the beads turn black (for the blue indicator) or remain clear (for the 
orange indicator), they can no longer be used as a color indicator.

Apply a light coat of water to the o-rings prior to inserting the cartridge into the generator plas-
tic housing.

The water reservoirs should be rinsed and the deionizer bags replaced every six months, or 
whenever the 

Change Water

 light illuminates (see Figure 7).  No tools are necessary to change 

the deionizer bags.

1

  Turn the 

Power Switch

 to OFF and make sure the 

Shutoff Valve

 is in the OPEN position 

(see Figure 8) in order to vent the hydrogen from the generator.

2

  Lift the top cover and unscrew the water reservoir caps.  Lift the deionizer bag out of the 

reservoir along with the cap.  Disconnect the deionizer bags from the caps and discard.

3

  Inspect the new deionizer bags (P/N 7601132) for holes or tears and return to Parker for 

credit if damaged.  Insert the “T” end into the cap until it secures the bag to the cap (see 
Figures 2 and 3).  Repeat for second bag.

4

  Use the Drain Port Insert with the 1/4” tube connected to it to drain the water reservoirs.  

There is approximately 4 liters of water in the generator when full.  Connect the Insert to the 

Drain Port

 located on the front panel behind the gray door (see Figure 7) and drain the unit 

(see Figure 8).

5

  Remove the Drain Port Insert by pressing down on the metal tab and pulling the fitting 

out (see Figure 9).  Refill the reservoirs with deionized water. Repeat steps 4 and 5 several 
times.

6

 

Finally,  remove  the  Drain  Port  Insert  and  fill  the  reservoirs  completely  with  approximately             
4 liters of deionized water.

7

  Replace the caps, with the new deionizer bags attached, being careful to avoid blocking 

any of the ports in the generator.

Note

: Do not allow the deionizer bags to dry out, they must be immersed in water to perform.

8

  Start the generator in the same manner found in the 

Startup

 section.

Occasionally, the fuse in the hydrogen generator may burn out.  The fuse is located in the pow-
er receptacle on the back side of the generator. 

 Before servicing the fuse, turn the generator 

off and disconnect the power cord from both the power supply and the generator power 
receptacle

.

To access the fuse, use a small screwdriver to remove the fuse holder located in the back of the 
generator and in the power receptacle.  Replace with the appropriate fuse and re-assemble.

To maintain the safety and performance integrity of the product, use only the fuse of the size 
and type detailed in the

 Specifications, Parts, and Accessories 

sections of this bulletin.

Summary of Contents for A915000JA-LI555

Page 1: ...ITION SOURCE WITHIN 10 INCHES 25cm OF THE OXYGEN VENT The Hydrogen Generator Model A915000JA L1555 see Figure 1 is a completely engineered system designed to produce ultra pure dry hydrogen gas from d...

Page 2: ...on the back of the unit Desiccant Wipe any drops of moisture with a lint free cloth or paper towel from the desic cant cap and housing Remove the desiccant cartridge from the sealed bag Use a drop of...

Page 3: ...rator Pressure Regulator The pressure is controlled using the Pressure Adjust control knob located on the front panel exposed when opening the front gray panel door see Figure 7 The pressure can be mo...

Page 4: ...move all of the red tape that was applied to the unit for shipping purposes Do not let the deionizer bags dry out Open the gray panel door on the front of the generator to expose the generator control...

Page 5: ...t a Mass Leak is present please follow the procedure below 1 Close the Shutoff Valve see Figure 7 shown in the OPEN position 2 Turn Power switch located in the rear of the generator in the power recep...

Page 6: ...r further instructions The generator is designed to be run continuously 24 hours 7 days per week If the unit is to be idle for more than 24 hours the generator should be turned off To store the unit 1...

Page 7: ...is may be caused either from a leak in the piping to the equipment or it may indicate the volume that is being filled is too large for the generator The High Hydrogen Flow Indicator will stay illumina...

Page 8: ...corresponds to the changes in the current going through the water Low Water Indicator If the water level drops too low in the water reservoir the generator will stop producing hydrogen Blue or orange...

Page 9: ...voirs are filled to the Full level Water must have a minimum resistivity of 2 MegOhm cm If the Low Water indicator see Figure 7 illuminates the generator will stop producing hydro gen to safeguard the...

Page 10: ...is in the OPEN position see Figure 8 in order to vent the hydrogen from the generator 2 Lift the top cover and unscrew the water reservoir caps Lift the deionizer bag out of the reservoir along with...

Page 11: ...Temperature 40 100 F 4 38 C Electrical Requirements 2 100 120 200 240 VAC 47 63 Hz Power Consumption 480 Watts 110 VAC 460 Watts 220 VAC Fuse 110 VAC T 4 Amp 125 V Fuse 220 VAC T 2 Amp 250 V Product D...

Page 12: ...eck external piping for leaks Hydrogen demand exceeds generator capacity Check capacity of equipment and piping downstream and install a flow control device Check internal system for piping leaks Chec...

Page 13: ...Hydrogen Generator Symbol Description POWER INDICATOR HYDROGEN FLOW INDICATOR NO HYDROGEN FLOW INDICATOR HIGH HYDROGEN FLOW MASS LEAK or EXCESSIVE FLOW RATE INDICATOR CHANGE WATER INDICATOR LOW WATER...

Page 14: ...ns to the skin found on inside of some units Under certain conditions metal cabinet will be warm to touch 70 C 3 Explanation of Warning Symbols Parker Manufacturing UK Ltd Gas Separation Filtration Di...

Reviews: