Patio Heater Instructions
OZGLOW HE 40 Hi/Lo
UNIT CLEARANCE
The OZGLOW heater must have the following clearances from combustible materials:
300mm above, 600mm at the sides and 1200mm below.
This appliance shall only be used in an above ground open-air situation with natural ventilation,
without stagnant areas, where gas leakage and products of combustion are rapidly dispersed
by wind and natural convection.
Any enclosure in which the appliance is used shall comply with one of the following:
An enclosure with walls on all sides, but at least
one permanent opening at ground level and no
overhead cover.
Within a partial enclosure that includes an overhead cover and no more than two walls.
Within a partial enclosure that includes an overhead cover and more than two walls, the
following shall apply:
At least 25% of the total wall area is completely open, and
At least 30% of the remaining wall area is open and unrestricted.
In the case of balconies, at least 20% of the total wall area shall be and remain open and
unrestricted.