This screen is used for setting the on time when the input is configured as an OVr (toggle)
override type. The on time is programmable from 0 seconds to 23 hours, 59 minutes and
59 seconds. When this on time is set to 0:00.00, the override functions as a toggle on/tog-
gle off override. When a non-zero value is programmed, the override functions as a timed
on/toggle off override.
This screen is used for assigning channels to the inputs. This applies only to the On\d,
OVr and ENb input types. This screen does not appear for a one channel control.
This screen is used for calibrating the sensors.The following calibration options
are provided:
F: -12,-11,-9,-8,-6,-5,-3,-2,0,2,3,5,6,8,9,11
C: -8,-7,-6,-5,-4,-3,-2,-1,0,1,2,3,4,5,6,7
L: -4,-3,-2,-1,0,1,2,3
U: -8,-7,-6,-5,-4,-3,-2,-1,0,1,2,3,4,5,6,7