Connecting the Power Supply to the BAC

Power Entry Modules (PEMs) installed in the front of the BAC provide –48 VDC 
power distribution, a 35-amp circuit breaker, power line filtering and input power 
monitoring. They are designated PEM A (on the left) and PEM B (on the right). All 
input power is distributed to the system via the PEMs, so that if one PEM or one 
power source fails, power will be supplied through the other PEM automatically 
without service interruption. Power inputs may be connected to the PEMs at the 
front of the BAC using the PEM’s terminal blocks, or at the terminal block on the 
back of the BAC. This document shows the recommended technique, with 
connections at the rear of the BAC. See the 

8820 Broadband Access Concentrator 

Installation Guide

 for more information.

Review the following procedures and determine which is appropriate for your 
configuration. The recommended configuration is two power modules connected 
to one BAC (providing a redundant power source). For all configurations: 

„

Make sure that the AC power cords are not connected to the power supply 
until other wiring is completed.

„

Use 8 AWG solid or stranded wire.

„

Attach ring tongue terminals to the ends of the wires to be connected to the 
BAC power terminal block. See the 

8820 Broadband Access Concentrator 

Installation Guide

 

for more information.

„

Attach ring tongue terminals to the ends of the wires to be connected to the 
power supply.

„

Strip 1/2 inch of insulation from the ends of the wires to be fastened at split 
bolt connectors or the grounding lug of the BAC.

CAUTION:

The following procedures must be performed by a trained technician.

SERIAL

SMCM

CLOCK

A

ALARM

2

4

6

8

10

12

14

16

18

1

3

5

7

9

11

13

15

17

LAN/WAN  SLOT

B

CLOCK

B

A

SERIAL

MCC

AC

ALARM

48V R

T

N

48V NEG

POWER ENTRY MODULE

LEFT UNIT: LINE A

RIGHT UNIT: LINE B

WARNING! POWER MUST BE DISCONNECTED A

T THE SOURCE

BEFORE REMOVING OR INSTALLING THIS PWR ENTR

Y MODULE

48V R

T

N

48V NEG

POWER ENTRY MODULE

LEFT UNIT: LINE A

RIGHT UNIT: LINE B

WARNING! POWER MUST BE DISCONNECTED A

T THE SOURCE

BEFORE REMOVING OR INSTALLING THIS PWR ENTR

Y MODULE

00-15326a-02

PEM
Circuit
Breaker

48V R

T

N

48V NEG

POWER ENTRY MODULE

LEFT UNIT: LINE A

RIGHT UNIT: LINE B

WARNING!

 POWER MUST BE DISCONNECTED AT THE SOURCE

BEFORE REMOVING OR INSTALLING THIS PWR ENTRY MODULE

O

PEM

A

PEM

B

Summary of Contents for 8820

Page 1: ...C Power Supply can be used to supply redundant power to a single 8820 Broadband Access Concentrator BAC or non redundant power to one or two BACs The maximum DC output of each power module is 825 watt...

Page 2: ...you are installing the power supply in a 23 inch rack remove the mounting brackets from the power supply chassis turn them and reinstall them with their short sides against the body of the power suppl...

Page 3: ...s are not connected to the power supply until other wiring is completed Use 8 AWG solid or stranded wire Attach ring tongue terminals to the ends of the wires to be connected to the BAC power terminal...

Page 4: ...y to the split bolt connector The PWR B 48V terminal of the BAC to the 48VB terminal of the power supply The PWR B RTN terminal of the BAC to a split bolt connector The 0VRB terminal of the power supp...

Page 5: ...ered by Two Power Modules 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 04 16717 02 CAUTION USE NO 8 AWG ONLY 48V RTN PWR A PWR B 48V RTN A B 0VRB 48VB 48VA 0VRA Split Bolt Connectors AC to DC Power Su...

Page 6: ...minal of the power supply The PWR A RTN terminal of the BAC to the split bolt connector The 0VRA terminal of the power supply to the split bolt connector The split bolt connector to an earth ground 3...

Page 7: ...wered by One Power Module 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 04 16715 02 CAUTION USE NO 8 AWG ONLY 48V RTN PWR A PWR B 48V RTN A B 0VRB 48VB 48VA 0VRA Split Bolt Connectors AC to DC Power Su...

Page 8: ...r supply to the split bolt connector The PWR A 48V terminal of the second BAC to the 48VB terminal of the power supply The PWR A RTN terminal of the second BAC to a split bolt connector The 0VRB termi...

Page 9: ...0 9 8 7 6 5 4 3 2 1 A B 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A B 0VRB 48VB 48VA 0VRA AC to DC Power Supply 04 16716 02 CAUTION USE NO 8 AWG ONLY Split Bolt Connectors Grounding Lug to Earth Gr...

Page 10: ...arranty at www paradyne com warranty Telephone Call our automated system to receive current information by fax or to speak with a company representative Within the U S A call 1 800 870 2221 Outside th...

Reviews: