background image

8

 June 

2004

8800-A2-GZ41-20

Providing Non-Redundant Power to Two BACs

Procedure

To connect two power modules to two BACs (see 

Figure 3

):

1. If none exist, install split bolt connectors or a grounding block near the rack 

where the power supply and BACs reside.

NOTE:

Split bolt connectors are not supplied.

2. Connect:

— The grounding lugs of the BACs to an earth ground.

— The PWR A –48V terminal of the first BAC to the –48VA terminal of the 

power supply.

— The PWR A RTN terminal of the first BAC to a split bolt connector.

— The 0VRA terminal of the power supply to the split bolt connector.

— The PWR A –48V terminal of the second BAC to the –48VB terminal of 

the power supply.

— The PWR A RTN terminal of the second BAC to a split bolt connector.

— The 0VRB terminal of the power supply to the split bolt connector.

— The split bolt connectors to an earth ground.

3. Verify that the power switches of the PEMs and the power modules are in the 

off (0) position.

4. Insert the AC power cords into the Input A and Input B sockets at the rear of 

the power supply. Plug the other ends into an AC power source.

5. Turn to the On (1) position the power switches of PEM A of each BAC and both 

power modules. Verify that the POWER LEDs at the front of the power 
modules and the POWER A LEDs at the top of the BACs are on. 

Summary of Contents for 8820

Page 1: ...C Power Supply can be used to supply redundant power to a single 8820 Broadband Access Concentrator BAC or non redundant power to one or two BACs The maximum DC output of each power module is 825 watt...

Page 2: ...you are installing the power supply in a 23 inch rack remove the mounting brackets from the power supply chassis turn them and reinstall them with their short sides against the body of the power suppl...

Page 3: ...s are not connected to the power supply until other wiring is completed Use 8 AWG solid or stranded wire Attach ring tongue terminals to the ends of the wires to be connected to the BAC power terminal...

Page 4: ...y to the split bolt connector The PWR B 48V terminal of the BAC to the 48VB terminal of the power supply The PWR B RTN terminal of the BAC to a split bolt connector The 0VRB terminal of the power supp...

Page 5: ...ered by Two Power Modules 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 04 16717 02 CAUTION USE NO 8 AWG ONLY 48V RTN PWR A PWR B 48V RTN A B 0VRB 48VB 48VA 0VRA Split Bolt Connectors AC to DC Power Su...

Page 6: ...minal of the power supply The PWR A RTN terminal of the BAC to the split bolt connector The 0VRA terminal of the power supply to the split bolt connector The split bolt connector to an earth ground 3...

Page 7: ...wered by One Power Module 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 04 16715 02 CAUTION USE NO 8 AWG ONLY 48V RTN PWR A PWR B 48V RTN A B 0VRB 48VB 48VA 0VRA Split Bolt Connectors AC to DC Power Su...

Page 8: ...r supply to the split bolt connector The PWR A 48V terminal of the second BAC to the 48VB terminal of the power supply The PWR A RTN terminal of the second BAC to a split bolt connector The 0VRB termi...

Page 9: ...0 9 8 7 6 5 4 3 2 1 A B 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A B 0VRB 48VB 48VA 0VRA AC to DC Power Supply 04 16716 02 CAUTION USE NO 8 AWG ONLY Split Bolt Connectors Grounding Lug to Earth Gr...

Page 10: ...arranty at www paradyne com warranty Telephone Call our automated system to receive current information by fax or to speak with a company representative Within the U S A call 1 800 870 2221 Outside th...

Reviews: