background image

Spectra 1727   5

3: 

ZONE PROGRAMMING

3.1

ZONE OPTIONS

Sections [14], [15], [16], [17], and [18]

Each section from 

[14] 

to 

[18]

 represents a specific Zone Option. Enter the desired section and use Multiple Feature Select Programming to

select the zones from 1 to 5 that will programmed with the Zone Option. Zone 6 is programmed as a 24-Hour Burglary Zone or a Fire Zone only
(see section 3.2). To select a zone press the corresponding key. Selected zones will illuminate. For example, if you want zone 2 to be a Stay
Zone, in section 

[18]

 press the 

[2]

 key to illuminate it. To remove the option from the zone, press the key corresponding to the zone so the key

extinguishes.

3.1.1

E

NTRY

 D

ELAY

Zones that are 

not

 selected in sections 

[15]

 to 

[17]

 will be defined with the Entry Delay Option. For example, if you want Zone 1 to be

programmed with the Entry Delay Option, make sure key 

[1]

 is 

not

 illuminated in sections 

[15]

[16]

 and 

[17]

. The Entry Delay Timer

is programmed in section 

[11]

 (see section 4.2). All zones are Entry Delay by default.

3.1.2

B

YPASS

 E

NABLED

 Z

ONE

Section [14]

When using the 

Bypass Programming

 feature or 

Force Arming

 (see section 6.4), only zones with the option Bypass Enabled can be

bypassed. Select the zones from 1 to 5 to be Bypass Enabled. Zone 6 is a 24-Hour Zone or a Fire Zone (see section 3.2) and cannot
be Bypass Enabled. 

3.1.3

S

TAY

 Z

ONE

Section [18]

Zones with the Stay Zone option enabled will be bypassed when the system is 

Stay Armed

 (see section 6.3). Select the zones from 1

to 6 to be Stay Zones. 

The Zone Options 24-Hour Zone, Instant Zone and Follow Zone cannot be programmed on the same zone. Each zone can be
programmed with only one of these Zone Options:  

3.1.4

24-H

OUR

 B

URGLARY

 Z

ONE

Section [15]

Whenever a 24-Hour Burglary Zone opens, whether the system is armed or disarmed, the control panel will immediately generate an
alarm. Select the zones from 1 to 5 to be 24-Hour Zones. Zone 6 is already a 24-Hour Zone or a Fire Zone (see section 3.2). Also,
refer to 

Zone Speed

 (see section 3.3).

3.1.5

I

NSTANT

 Z

ONE

Section [16]

When an armed Instant Zone opens, the control panel immediately generates an alarm. Instant Zones are commonly used for
windows, patio doors, skylights and other perimeter type zones. Select zones from 1 to 5 to be Instant Zones. Zone 6 is a 24-Hour
Zone or a Fire Zone (see section 3.2) and cannot be programmed as an Instant Zone. Also, refer to 

Zone Speed

 (see section 3.3).

3.1.6

F

OLLOW

 Z

ONE

Section [17]

When an armed Follow Zone opens, the control panel will immediately generate an alarm, unless an Entry Delay zone opens first: 

If an armed Follow Zone opens after an Entry Delay zone opens, the control panel waits until the Entry Delay Timer has elapsed 
before generating an alarm. If the system is disarmed during the Entry Delay, the alarm is cancelled.

If an armed Follow Zone opens after more than one Entry Delay zone opens, the control panel will wait until the Entry Delay 
Timer of the zone that opened first has elapsed before generating an alarm. If the system is disarmed during the Entry Delay, the 
alarm is cancelled.

This feature is commonly used when a motion detector is protecting the area occupied by the entry point keypad. This will prevent the
motion detector from causing an alarm when a user enters through the entry point to disarm the system. Select the zones from 1 to 5
to be Follow Zones. Zone 6 is a 24-Hour Zone or a Fire Zone (see section 3.2) and cannot be programmed as a Follow Zone. Also,
refer to 

Zone Speed

 (see section 3.3).

Table 3: Zones

Control Panel Inputs

Zone Number

Key

Z1

Zone 1

[1]

Z2

Zone 2

[2]

Z3

Zone 3

[3]

Z4

Zone 4

[4]

Keypad Zone/Keypad Tamper

Zone 5

[5]

Fire

Zone 6

[6]

Summary of Contents for SPECTRA 1686H

Page 1: ...SPECTRA 1727 V1 10 1727 COMPLETE INSTALLATION MANUAL Reference Installation and Programming...

Page 2: ......

Page 3: ...elay 5 Bypass Enabled Zone 5 Stay Zone 5 24 Hour Burglary Zone 5 Instant Zone 5 Follow Zone 5 Fire Zone Programming 6 Zone Speed 6 System Options 6 Exit Delay Timer 6 Entry Delay Timer 6 Bell Cut off...

Page 4: ...which returns programming to STEP 3 1 3 2 MULTIPLE FEATURE SELECT PROGRAMMING METHOD Multiple Feature Select Programming is used in sections 14 15 16 17 18 19 and 20 For sections 14 15 16 17 and 18 e...

Page 5: ...ell output which is protected by a 3A fuse Connect the siren s positive lead to the panel s BELL terminal the negative lead to the relay output NO or NC terminals and connect a wire from the relay s C...

Page 6: ...gure 8 1 PCB Layout on page 13 and the zone s parameters are defined see section 3 2 For example a door contact located at the front door can be wired directly to the input terminal of the keypad inst...

Page 7: ...our Burglary Zone opens whether the system is armed or disarmed the control panel will immediately generate an alarm Select the zones from 1 to 5 to be 24 Hour Zones Zone 6 is already a 24 Hour Zone o...

Page 8: ...apidly and the READY LED will flash during the Exit Delay Key in the desired two digit value from 00 to 99 seconds into section 10 30 seconds by default 4 2 ENTRY DELAY TIMER Section 11 When the syste...

Page 9: ...ill toggle to its opposite state When option 3 is disabled the Bell Relay remains in its opposite state When an alarm occurs it will toggle to its normal state Option 3 OFF The Bell Relay deactivates...

Page 10: ...rt The ARM1 LED will flash when the Exit Delay ends Stay Arming can also be activated using One Touch Arming User Access Codes must have the Stay Arming Option to Stay Arm the system 6 4 FORCE ARMING...

Page 11: ...reviously bypassed zones if any will illuminate 4 Press the ENTER key to accept these entries or press the key s corresponding to the zones you want to change the press ENTER How do use Bypass Recall...

Page 12: ...beep the chime feature has been enabled for that zone If the keypad emits a rejection beep the chime feature has been disabled for the corresponding zone 6 10 KEYPAD MUTING Press and hold the CLEAR b...

Page 13: ...digit code 07 User Code 05 08 User Code 06 09 User Code 07 How Do I Program the PGMs STEP 1 Press the ENTER key STEP 2 Enter the INSTALLER CODE Default 0000 000000 STEP 3 Enter 13 STEP 4 Enter one di...

Page 14: ...17 Follow N N N N N 18 Stay Zone N N N N N Entry Delay Sections 15 16 and 17 must be off for the selected zone Example for an Entry Delay on zone 1 turn key 1 off in sections 15 to 17 Force Zone Progr...

Page 15: ...Spectra 1727 13 8 HARDWARE CONNECTIONS Figure 8 1 PCB Layout...

Page 16: ...14 Complete Installation Manual Figure 8 2 Zone Connections Figure 8 3 PGM Connections...

Page 17: ...ent cannot exceed 200mA for UL installations All outputs are Class 2 or power limited except for the battery terminal The Class 2 and power limited fire alarm circuits shall be installed using CL3 CL3...

Page 18: ...16 Complete Installation Manual Notes...

Page 19: ......

Page 20: ......

Reviews: