background image

6   Complete Installation Manual   

3.2

FIRE ZONE PROGRAMMING

Section [20] option [4]

When option 

[4]

 is disabled, the control panel will recognize the zone as a 24Hr. Burglary Zone (see section 3.1.4). When option 

[4]

 is enabled,

the control panel will recognize zone 6 as a 

Fire Zone

, enabling smoke detectors connected as shown in Figure 8-2: Zone Connections on page

14. Fire zones must use a 1k

 EOL resistor. If there is a line short or if the smoke detector becomes active, whether the system is armed or

disarmed, the control panel will generate an alarm. Alarms are always audible, regardless of other settings. Fire alarms will generate an
intermittent (pulsed) bell/siren output signal as demonstrated in 

Figure 3-1: Bell Output during Fire Alarm

.

Option 

[4]

 

OFF

:

Zone 6 is a 24Hr. Burglary Zone (default)

Option 

[4]

 

ON

:

Zone 6 is a Fire Zone

Figure 3-1: Bell Output during Fire Alarm

3.3

ZONE SPEED

Section [19] option [1]

The Zone Speed defines how quickly the control panel will respond to an open zone. The control panel will not display an open zone on the
keypad or generate an alarm until the programmed Zone Speed has elapsed. All other zone definitions and options do not come into effect until
the Zone Speed has elapsed. This feature prevents any momentary glitches from causing an alarm.

Option 

[1]

 

OFF

:

Zone Speed is 600ms (slow) (default)

Option 

[1]

 

ON

:

Zone Speed is 20ms (fast)

It is recommended to avoid using option 

[1]

 ON for Keypad Zones

.

 

4: 

SYSTEM OPTIONS

4.1

EXIT DELAY TIMER

Section [10]

After entering the required arming sequence (i.e. User Access code), the Exit Delay Timer determines the amount of time a user has to leave the
protected area before the control panel arms the system. The Exit Delay applies to all zones in the system. The keypad will beep rapidly and the

READY

 LED will flash during the Exit Delay. Key in the desired two-digit value from 00 to 99 seconds into section 

[10]

 (30 seconds by default).

4.2

ENTRY DELAY TIMER

Section [11]

When the system is armed and a zone defined with the Entry Delay Option opens (see section 3.1), the control panel will generate an alarm after
the programmed Entry Delay Timer has elapsed if the system is not disarmed. This is to provide users with enough time to enter the protected
area and disarm the system. To program the Entry Delay Timer, key in the desired 2-digit delay value (00 to 99 seconds) into section 

[11]

 (45

seconds by default). Entry Delay zones are commonly used at the entry/exit points of the protected area (i.e. front/back door, garage, etc.).

4.3

BELL CUT-OFF TIMER

Section [12]

After an audible alarm, the bell/siren output will deactivate when the system is disarmed or when the Bell Cut-off Timer has elapsed, whichever
comes first. Key in the desired two-digit value from 00 to 99 minutes into section

 [12]

 (04 minutes by default).

4.4

PANIC ALARM

Section [19] option [6]

In case of emergency, the 

Spectra 1727

 system provides one panic alarm. This panic alarm, if enabled, will immediately generate an alarm after

pressing and holding the 

[1]

 and 

[3]

 keys for two seconds. In the Alarm Memory (see section 6.8) the 

[8]

 key will illuminate to indicate that

someone activated the Panic Alarm.
Option 

[6]

 

OFF

:

Panic Alarm is disabled (default)

Option 

[6]

 

ON

:

Panic Alarm is enabled

4.5

ARMING OPTIONS

4.5.1

A

UTO

 F

ORCE

 A

RMING

Section [19] option [7]

With this feature enabled, the control panel will always Force arm instead of Regular arm regardless of the User Access Code’s programming. In
installations where the user must Force arm when leaving the protected area, this feature allows users to Force arm without pressing the

[

FORCE

]

 key before entering their User Access Code. 

Option 

[7]

 

OFF

:

Auto Force Arming is disabled (default)

Option 

[7]

 

ON

:

Auto Force Arming is enabled

Summary of Contents for SPECTRA 1686H

Page 1: ...SPECTRA 1727 V1 10 1727 COMPLETE INSTALLATION MANUAL Reference Installation and Programming...

Page 2: ......

Page 3: ...elay 5 Bypass Enabled Zone 5 Stay Zone 5 24 Hour Burglary Zone 5 Instant Zone 5 Follow Zone 5 Fire Zone Programming 6 Zone Speed 6 System Options 6 Exit Delay Timer 6 Entry Delay Timer 6 Bell Cut off...

Page 4: ...which returns programming to STEP 3 1 3 2 MULTIPLE FEATURE SELECT PROGRAMMING METHOD Multiple Feature Select Programming is used in sections 14 15 16 17 18 19 and 20 For sections 14 15 16 17 and 18 e...

Page 5: ...ell output which is protected by a 3A fuse Connect the siren s positive lead to the panel s BELL terminal the negative lead to the relay output NO or NC terminals and connect a wire from the relay s C...

Page 6: ...gure 8 1 PCB Layout on page 13 and the zone s parameters are defined see section 3 2 For example a door contact located at the front door can be wired directly to the input terminal of the keypad inst...

Page 7: ...our Burglary Zone opens whether the system is armed or disarmed the control panel will immediately generate an alarm Select the zones from 1 to 5 to be 24 Hour Zones Zone 6 is already a 24 Hour Zone o...

Page 8: ...apidly and the READY LED will flash during the Exit Delay Key in the desired two digit value from 00 to 99 seconds into section 10 30 seconds by default 4 2 ENTRY DELAY TIMER Section 11 When the syste...

Page 9: ...ill toggle to its opposite state When option 3 is disabled the Bell Relay remains in its opposite state When an alarm occurs it will toggle to its normal state Option 3 OFF The Bell Relay deactivates...

Page 10: ...rt The ARM1 LED will flash when the Exit Delay ends Stay Arming can also be activated using One Touch Arming User Access Codes must have the Stay Arming Option to Stay Arm the system 6 4 FORCE ARMING...

Page 11: ...reviously bypassed zones if any will illuminate 4 Press the ENTER key to accept these entries or press the key s corresponding to the zones you want to change the press ENTER How do use Bypass Recall...

Page 12: ...beep the chime feature has been enabled for that zone If the keypad emits a rejection beep the chime feature has been disabled for the corresponding zone 6 10 KEYPAD MUTING Press and hold the CLEAR b...

Page 13: ...digit code 07 User Code 05 08 User Code 06 09 User Code 07 How Do I Program the PGMs STEP 1 Press the ENTER key STEP 2 Enter the INSTALLER CODE Default 0000 000000 STEP 3 Enter 13 STEP 4 Enter one di...

Page 14: ...17 Follow N N N N N 18 Stay Zone N N N N N Entry Delay Sections 15 16 and 17 must be off for the selected zone Example for an Entry Delay on zone 1 turn key 1 off in sections 15 to 17 Force Zone Progr...

Page 15: ...Spectra 1727 13 8 HARDWARE CONNECTIONS Figure 8 1 PCB Layout...

Page 16: ...14 Complete Installation Manual Figure 8 2 Zone Connections Figure 8 3 PGM Connections...

Page 17: ...ent cannot exceed 200mA for UL installations All outputs are Class 2 or power limited except for the battery terminal The Class 2 and power limited fire alarm circuits shall be installed using CL3 CL3...

Page 18: ...16 Complete Installation Manual Notes...

Page 19: ......

Page 20: ......

Reviews: