4. Doubling method

Z3

Z1

Z2

Z4

728: [1/2] [3/4] [5/6] [7/8]

Zone 1,3,5 & 7 use 1K resistor, zone 2,4,6 & 8 use 2.2K resistor.
Keypad 1 as zone 9 and keypad 2 as zone10, need to put 1K resistor for keypad zones.

[key in 090][ON key 8][ENTER], to enable zone doubling
[key in 088], [ON key MEM][ENTER], disable EOL.
AND program zone type in Step 1.

Important note: Once the panel is in zone doubling, ALL zones are Normally Closed (NC).

Note

: For zone doubling, the zone speed setting in address [053] should be [004] and above to avoid false

alarm caused by vibration sensors.

For Fire zone connections using 4-wire smoke detector

Once zone 3 is enable as FIRE zone in this zone doubling method:

[key in 090][ON key 1][ENTER], to disable zone 4.
[key in 100][ON key 3][ENTER], to program zone 3 as fire zone.

[key in 039], press [5][0], PGM to reset smoke detector
[key in 040], press [5][0], PGM to reset smoke detector
[key in 042], press [2ND][6], PGM to reset smoke detector
[key in 056], press [0][0][4], PGM to reset smoke detector

Note: Once zone 3 is a FIRE zone, zone 4 can not be used. Now, this zone 3 is a parallel wiring..

1 K

2.2
K

1K

2.2
K

1

C

2

3

C

Summary of Contents for ESPRIT 728 ULT

Page 1: ...es that are not selected in 100 to 108 automatically become delay zone key in 096 ON key wants to be SILENT zone key in 116 ON key wants to be STAY zone key in 124 ON all zone to allow for bypass Exam...

Page 2: ...number 1 ENTER CLEAR CMS phone number 1 key in 06 enter phone number 2 ENTER CLEAR CMS phone number 2 key in 08 enter 8888 8888 ENTER CLEAR account number Note to clear phone number replace digit wit...

Page 3: ...ch Connect a 500 ohm resistor in series with AUX of keypad black wire another wire connect to GRN of keypad green wire 500 ohm resistor 3 Partitioning key in 086 ON key 8 ENTER CLEAR to enable partiti...

Page 4: ...setting in address 053 should be 004 and above to avoid false alarm caused by vibration sensors For Fire zone connections using 4 wire smoke detector Once zone 3 is enable as FIRE zone in this zone d...

Page 5: ...r 3 seconds For Fire zone connections using 2 wire smoke detector Z1 Z2 Z3 Z4 Note Maximum up to 5 pcs 2 wire smoke detector 1 K 2 2 K 1 C 2 3 C 2 wire Smoke detector NO PGM AUX AUX 1 K 2 2 K 1 K 2 2...

Page 6: ...in the programming mode ENTER key is flashing Press ENTER 2828 8 CLEAR to activate walk test mode Press ENTER 2828 8 CLEAR to de activate walk test mode To reset panel back to factory default 1 Remove...

Page 7: ...0 10 button for 3 seconds One touch STAY arming Press hold the key 11 STAY button for 3 seconds One touch INSTANT arming Press hold the key 11 STAY button for 3 seconds then again Press hold again th...

Page 8: ...me for zone Press hold any button from 1 to 6 for 3 seconds Button 1 for zone 1 button 2 for zone 2 To activate deactivate chime for keypad zone Press hold button 8 To activate deactivate Buzzer Mute...

Reviews: