12
PROGRAMMING GUIDE
Programmable Outputs
Please note that options
[1]
through
[5]
in section
[502]
represent PGMs 1 to 5 respectively. The control panel
deactivates
an activated PGM one of two ways:
Option OFF = Follow Activation Event:
If the first digit of the PGM Activation Event is set at 1, 2, 3, 4, or 7, the PGM will remain activated until the PGM Activation
Event has ended. It will ignore the PGM Deactivation Event. If the first digit of the PGM Activation Event is set at 8, 9, A, B, C,
D, E, or F, the PGM will remain activated until the PGM Deactivation Event occurs.
Option ON = Follow PGM Delay Timer:
After activating the PGM, the control panel will start the PGM delay timer and the PGM will deactivate only when the PGM
delay timer has elapsed regardless of the PGM Deactivation Event.
NOTE1*:
0 = Occurs in all partitions enabled in the sytstem (see section [500]).
1 = Partition 1 3 = Partition 3
2 = Partition 2 4 = Partition 4
8 = Occurs in at least one partition enabled in the system.
Section
PGM
Event Group
(First Digit)
Event Group
(Second Digit)
Event Selection
(on/off)
[400]
PGM1 Activation Event
___
___
1 2 3 4 5 6 7 8
[401]
PGM1 Deactivation Event
___
___
1 2 3 4 5 6 7 8
[402]
PGM2 Activation Event
___
___
1 2 3 4 5 6 7 8
[403]
PGM2 Deactivation Event
___
___
1 2 3 4 5 6 7 8
[404]
PGM3 Activation Event
___
___
1 2 3 4 5 6 7 8
[405]
PGM3 Deactivation Event
___
___
1 2 3 4 5 6 7 8
[406]
PGM4 Activation Event
___
___
1 2 3 4 5 6 7 8
[407]
PGM4 Deactivation Event
___
___
1 2 3 4 5 6 7 8
[408]
PGM5 Activation Event
___
___
1 2 3 4 5 6 7 8
[409]
PGM5 Deactivation Event
___
___
1 2 3 4 5 6 7 8
Feature Select Programming
First
Digit
Event
Second
Digit
1
2
3
4
5
6
7
8
0
PGM Disabled
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1
Status 1
Note1*
Regular
Armed
Force
Armed
Stay
Armed
Instant
Armed
Strobe
(until alarm
cancelled)
Silent
Alarm
(until cancel
alarm/bell cut-off)
Audible
Alarm
(until cancel
alarm/bell cut-off)
Fire Alarm
(until alarm
cancelled or
bell cut-off)
2
Status 2
Note1*
Ready
Status
Exit Delay
Entry Delay
Trouble
Alarm
Memory
Zones
Bypassed
(armed/not)
User or
Installer
Programming
Keypad
Lockout
3
Status 3
Note1*
Intellizone
Delay
Fire Delay
Auto Arm
Access
Tamper
Zone Low
Battery
Fire Loop
Zone
Supervision
Summary of Contents for Digiplex V2.14
Page 1: ...Digiplex System V2 14 V2 2ACC Control Panel Programming Guide...
Page 2: ......
Page 42: ...40 PROGRAMMING GUIDE Hardware Connections SINGLE ZONE INPUTS ATZ DOUBLE ZONE INPUTS...
Page 43: ...DIGIPLEX SERIES 41 CONNECTING A ZX4 EXPANDER MODULE FIRE ZONE KEYSWITCH AND PGM CONNECTIONS...
Page 44: ...42 PROGRAMMING GUIDE DIGIPLEX PCB LAYOUT...
Page 47: ......
Page 48: ......