REAR PANEL 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
1.  The R-J11/R-J45 modular connectors are used for 10/100/1000 Base-T 

Network/single line Phone/Fax/Modem protection. 

2.  The External Battery Pack detect port (EXB) is for the UPS to automatically 

detect the External Battery Pack so that the UPS can calculate the estimated 
runtime. 

3.  The RS232 Communications Port is for UPS monitoring and control. 
4.  The REPO (Remote Emergency Power Off) Port is for UPS control.  This 

connection is not for telecommunication use. 

5.  The option slot is for option cards. 
6.  The fan is for ventilation. 
7.  The External Battery Connector is for connecting an External Battery Pack. 
8.  The Battery Backup output receptacles.    The output receptacles are electrically 

wired into two segments to support the "Load Shedding Function" (Labeled Load 
1 & Load 2).    The locking and Always On receptacles (Labeled Load 3) do not 
support the "Load Shedding Function".   

NOTE:

 The locking receptacle is not on 

all models. 

9.  The input circuit breaker will trip in the event the load exceeds the UPS’s power 

rating. 

10.  The rackmount brackets are for attaching the UPS to rack. 
11. The input power cord (120V models).  The AC Power Inlet IEC320 (208V 

models). 

12.  The External Ground Stud is for connecting an external ground wire. 
13.  The USB Communications Port is for UPS monitoring and control. 

 

Model 

Input Power Plug 

(All power cords are 10ft) 

Output Power Receptacles 

EXR750RT2U 
EXR1000RT2U 
EXR1500RT2U 

NEMA 5-15P 

6-NEMA 5-15R (Controllable) 
2-NEMA 5-15R (Always On) 

EXR2000RT2U NEMA 

5-20P 

8-NEMA 5-15/20R (Controllable) 
1-NEMA L5-20R (Always On) 

EXR3000RT2U NEMA 

L5-30P 

6-NEMA 5-15/20R (Controllable) 
1-NEMA L5-30R (Always On) 

EXR1500RTHV NEMA 

6-15P 

4-NEMA 6-15R (Controllable) 
2-NEMA 6-15R (Always On) 

EXR3000RTHV NEMA 

L6-30P 

6-NEMA 6-15/20R (Controllable) 
1-NEMA L6-30R (Always On) 

11 

Chapter 3:  Installation

 

 

INSTALLATION PLACEMENT 

 
This UPS series is 

ONLY

 intended to be installed in an indoor temperature-

controlled environment that is free of conductive contaminants.  DO NOT 
operate the UPS in extremely dusty and/or unclean areas, locations near 
heating devices, water, or excessive humidity, or where the UPS is exposed 
to direct sunlight.  Select a location, which will always provide good air 
circulation for the UPS.   

 

Route power cords so they cannot be walked on 

or damaged.    This UPS series is not intended for use in a computer room 
as defined in the Standard for the Protection of Electronic Computer/Data 
Processing Equipment ANSI/NFPA 75.    Typical battery life is 3 to 5 years.   
Environmental factors do affect battery life.    High temperatures, poor utility 
power, and frequent, short duration discharges have a negative impact on 
battery life.

 

 

Operating Temperature (Maximum):    0 to 40

C (+32 to +104

F) 

Operating Elevation:    0 to 3,000m (0 to +10,000 ft) 
Operating and Storage Relative Humidity:    5 ~ 95%, non-condensing 
Storage Temperature:    -15 to +45°C (+5 to +113°F) 
Storage Elevation:    0 to 15,000m (0 to +50,000 ft) 
 

INSTALLATION 

Be sure to read the installation placement and all the cautions before 
installing the UPS.  Place the UPS in the final desired location and 
complete the rest of the installation procedure.  These UPSs are shipped 
with the internal batteries disconnected.    The batteries must be connected 
before putting these UPSs into service.    See the "Connecting the Batteries" 
procedure to connect the batteries and then the "Rackmount Configuration" 
to install the UPS into the rack.   

USE CAUTION:   

The UPS is heavy.    Use 

the appropriate number of personnel when installing the UPS.

 

 

CAUTION!  DO NOT USE THE MOUNTING BRACKETS TO LIFT THE 
UPS.

    The mounting brackets are 

ONLY

 for securing the UPS to the rack. 

 

NOTE:  If you are using an External Battery Pack with this EXR UPS 
series, the UPS must be configured so that the UPS will report the 
correct estimated runtime on the LCD screen and in the Power 
Monitoring software and/or the SNMP card.  See the UPS's, or the 
Power Monitoring software or the SNMP card’s User's Manual to 
configure the UPS. 

Summary of Contents for MinuteMan EXR Series

Page 1: ...Para Systems Inc 1455 LeMay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000537 R2 User s Manual...

Page 2: ...ls and Indicators 6 3 Installation 11 4 Operation 17 5 Configurable Parameters Settings 21 6 Obtaining Service 22 7 Troubleshooting 23 8 Replacing the Battery 24 9 Specifications 27 10 Limited product...

Page 3: ...0 C 25 C or 68 F 77 F for at least one hour to avoid moisture condensing inside the UPS 3 CAUTION This UPS series is ONLY intended to be installed in an indoor temperature controlled environment that...

Page 4: ...authority to operate the equipment NOTE These UPSs are shipped with the batteries disconnected The batteries must be connected before putting these UPSs into service Refer to Section 3 Installation f...

Page 5: ...ing in the AC normal Boost and Buck modes 6 The Multi function On Off Test button is used to turn the UPS on or off or to perform a self test 7 The Fault icon illuminates when the UPS detects an inter...

Page 6: ...ts the changes to the Configuration back to the factory default settings Must be in the Standby mode 7 Service Mode The UPS must be in the Standby mode to enter the Service mode Enter the password def...

Page 7: ...be installed in an indoor temperature controlled environment that is free of conductive contaminants DO NOT operate the UPS in extremely dusty and or unclean areas locations near heating devices water...

Page 8: ...FIG 1 FIG 2 13 RACKMOUNT CONFIGURATION This UPS series comes with mounting brackets for the standard 19 46 5cm rack pre installed on the UPS The mounting brackets to fit a 23 59 2cm rack and Rail Kit...

Page 9: ...n of the UPS has been determined place the UPS on a flat surface and remove the rackmount brackets from the UPS 15 2 The LCD panel can be rotated to read in the upright position Use a small flat blade...

Page 10: ...PTIONAL The Power Monitoring Software and interface cables can be used with the UPS Use only the interface cables that come with these UPSs Connect the interface cable Serial or USB to the appropriate...

Page 11: ...ilenced during a general fault alarm SERVICE MODE The UPS has a Service mode function activated through the LCD screen The Service mode items are Output Voltage Adjustment Load Shedding Function Passw...

Page 12: ...overloaded UPS will shutdown This alarm and error message will remain on until the excess load is removed or the UPS s self protection circuit shuts the UPS down If the UPS shuts down because of an O...

Page 13: ...6 Return the unit by insured prepaid carrier to Para Systems Inc MINUTEMAN UPS 1809 W Frankford Road Suite 150 Carrollton TX 75007 ATTN RMA _______ 23 Chapter 7 Troubleshooting Symptom Error Message C...

Page 14: ...the battery terminals 6 Determine if the battery is inadvertently grounded If the battery is remove the source of the grounding Contact with any part of a grounded battery can result in an electrical...

Page 15: ...Acceptable Input voltage 0 165VAC 0 300VAC Voltage Range 80 164VAC 150 271VAC Frequency Limits 50 or 60 Hz 6Hz autosensing Low Voltage Transfer Point 80V 150V resets to Utility Power at 85V 157V or h...

Page 16: ...overs faulty parts Para Systems products that are depot repaired or replaced pursuant to this warranty shall only be warranted for the unexpired portion of the warranty applying to the original produc...

Page 17: ...Manufacturer s Name Para Systems Inc MINUTEMAN UPS Manufacturer s Address 1455 LeMay Drive Carrollton Texas 75007 USA Type of Equipment Uninterruptible Power Supplies UPS Model No EXR750RT2U Y EXR1000...