V00028CA Rev03
www.panduit.com
Page
5
of
18
b.
26.5” will not fit unless the Top Back Plate is removed in RUs 18 - 23, and 25 of the IDF. RUs 12 – 17 are dependent
on the number of horizontal trunk cables.
C)
A switch is 20.5” deep. The main power plug is on the left side facing the front, does not have a strain relief, and there are
no stack cables. 20.5” + 3” is a maximum of 23.5” on the left side. This will fit in RUs 18 – 23, and 25 of the IDF. RUs 12 –
17 are dependent on the number of horizontal trunk cables.
RU
Useable Depth
(in)
Useable Depth
(mm)
Comments
1
13.31
338
Limited by Center Section and Wall Section flange
2
22.69
576
Handle may interfere with patch field
3
22.69
576
Handle may interfere with patch field
4
22.69
576
5
22.69
576
6
22.69
576
7
22.69
576
8
22.69
576
9
22.69
576
10
22.69
576
11
22.69
576
12
22.69
576
24.9" if there is no 3rd trunk cable.
, page 11, shows 2 trunk cables.
The 3rd trunk loop would rise above the 2 shown.
13
22.69
576
24.9" if there is no 3rd trunk cable. Handle may interfere with patch field.
14
22.69
576
24.9" if there is no 3rd trunk cable. Handle may interfere with patch field.
15
22.69
576
24.9" if there is no 3rd trunk cable.
16
22.69
576
24.9" if there is no 3rd trunk cable.
17
22.69
576
24.9" if there is no 3rd trunk cable.
18
24.9
632
19
24.9
632
20
24.9
632
21
24.9
632
22
25.5
648
23
25.5
648
24
13.31
338
25
24.9
632
Handle may interfere with patch field
26
13.31
338
Handle may interfere with patch field. Limited by Center Section and Wall
Section flange
Table 1: Useable depth of the enclosure per RU