Panduit VeriSafe VS2-NET Installation Manual Download Page 5

10/16/2022 

1006772, B21148_EN_rev1

Dimensions

Dimensions

135 x 112 x 28 mm  (5 .3 x 4 .4 x 1 .1 inches), when network connetion is installed

Installation Instructions

Special Conditions 

of Use

Hazardous Locations

 

„

The equipment shall be installed in an enclosure that provides a degree of protection not less than 

IP 54 in accordance with IEC 60079-0 .

 

„

Ambient Temperature Range:  -25°C 

 Tamb 

 60°C

 

„

The enclosure must only be accessible with use of a tool .

WARNING:

   

 

„

Always de-energize power before accessing an electrical enclosure

 

„

Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment

 

„

Do not use this product outside of the specified performance and environmental limits

 

„

Always comply with local installation codes and standards

 

„

The data from the network module does not carry a functional safety rating . It should be used for monitoring only . If integrating 

with a safety-rated system, use the SIL 3 outputs on the AVT isolation module instead of the network module outputs .

STEP 1:  INSTALL NETWORK MODULE INTO ENCLOSURE

 

„

Mount network module flat in enclosure (see *NOTE in dimensional diagram above), or

 

„

Snap the network module onto the DIN rail, or

 

„

Mount the network module to the 2 .0 AVT isolation module .  See image to the right .

 STEP 2:  CONNECT POWER TO NETWORK MODULE (DC POWER SUPPY, OR POWER OVER ETHERNET)

 

„

Connect power supply to DC Input, or connect PoE network cable to PoE connection

 STEP 3:  CONNECT THE DATA/POWER OUTPUT FROM NETWORK MODULE TO 2.0 AVT ISOLATION MODULE

 

„

Connect wires into pluggable screw terminal connectors on network module and the 2 .0 AVT 

isolation module .  The connector ports are labeled “AVT” .

STEP 4:  CONNECT NETWORK CONNECTION TO RJ-45 PORT

 

„

if using the DC Input connector for power, and not using PoE, connect RJ-45 network cable,

 

„

if using PoE, connect the PoE network cable to RJ-45 port

STEP 5:  BEFORE POWER-UP, READ DOCUMENT B21110 (2.0 AVT INSTRUCTION MANUAL) AND DOCUMENT B21176 

(NETWORK MODULE USER GUIDE) FOR USER AND WEB-INTERFACE INSTRUCTIONS.  POWER UP THE SYSTEM.

 IF  DESIRED, 

ATTACH NETWORK MODULE 

TO THE 2 .0 AVT ISOLATION MODULE USING 

SCREWS PROVIDED WITH THE NETWORK 

MODULE

NOTE*:

For mounting the network module flat in an enclosure, 

use the hole pattern locations identified by “A” in the 

diagram .  Use four #6 [M3 .5] pan head screws or 

other compatible fasteners .

Reviews: