Panduit VeriSafe VS2-NET Installation Manual Download Page 4

1006772, B21148_EN_rev1 

10/16/2022

Technical Specifications

WARNING

:

 Do

 

not use this product outside of the specified performance and environmental limits . 

Failure to comply with 

these specifications could result in product failure, personal injury, or death.

Environmental Ratings

Operating Temperature

-25°C to 60°C (-13°F to 140°F)

Storage Temperature

-45°C to 85°C (-49°F to 185°F)

Humidity

5 to 90% non-condensing; Rated 80% at 40°C (104°F), decreasing linearly to 50% at 60°C (140°F)

Pollution Degree

3

Altitude

Up to 5000 meters (16400 feet)

Degree of Protection

Open Type, IP20

Hazardous Locations

Special Conditions 

of Use

 

„

The equipment shall be installed in an enclosure that provides a degree of protection not less than 

IP 54 in accordance with IEC 60079-0 .

 

„

Ambient Temperature Range:  -25°C 

 Tamb 

 60°C

 

„

The enclosure must only be accessible with use of a tool .

Network Module 

(Hazardous Location Ratings)

cULus:   Class I, Division 2, Groups A, B, C, D 

Class I Zone 2 AEx ec IIC T5 Gc; Ex ec IIC T5 Gc

Power Requirements

DC Input

 The power supply must be surge protected, otherwise external surge protection is 

required at the input to the supply .
12-24 VDC (IEC Class I regulated power supply) Min . Output: 12 VDC @ 100 mA, 24 VDC @ 50 mA
Power Draw:  84 mA max @ 12 VDC; 42 mA max @ 24 VDC (Network AVT)

Power over EtherNet (PoE)

PoE (10/100), 15 mA, IEEE 802 .at (-af) Type 1 Class III PoE topology

Standards and Certifications

IEC / UL / CSA C22 .2 NO . 61010-1 

IEC / UL / CSA C22 .2 NO . 61010-2-030

Safety requirements for electrical equipment for measurement, control, and laboratory use

UL 508 & CSA-C22 .2 No . 14

Industrial control equipment

FCC - CFR 47 Part 15 Subpart B 

Radio frequency devices

CAN ICES-001

Industrial, scientific and medical (ISM) radio frequency generators

EN 55011, CISPR 11,
AS/NZS CISPR 11

Radio frequency disturbance characteristics

IEC 61326-1 

EN 61326-1

EMC and immunity requirements

IEC / EN 61000-3-2, -3-3, -6-2

Electromagnetic compatibility (EMC)

CE 

UKCA

Conformity Marking for European Economic Area 

Conformity Marking for United Kingdom

RoHS

Restriction of hazardous substances

Absence of Voltage 

Accessory 

Ind. Cont. Eq. 

E489576