1006772, B21148_EN_rev1
4
10/16/2022
Technical Specifications
WARNING
:
Do
not use this product outside of the specified performance and environmental limits .
Failure to comply with
these specifications could result in product failure, personal injury, or death.
Environmental Ratings
Operating Temperature
-25°C to 60°C (-13°F to 140°F)
Storage Temperature
-45°C to 85°C (-49°F to 185°F)
Humidity
5 to 90% non-condensing; Rated 80% at 40°C (104°F), decreasing linearly to 50% at 60°C (140°F)
Pollution Degree
3
Altitude
Up to 5000 meters (16400 feet)
Degree of Protection
Open Type, IP20
Hazardous Locations
Special Conditions
of Use
The equipment shall be installed in an enclosure that provides a degree of protection not less than
IP 54 in accordance with IEC 60079-0 .
Ambient Temperature Range: -25°C
≤
Tamb
≤
60°C
The enclosure must only be accessible with use of a tool .
Network Module
(Hazardous Location Ratings)
cULus: Class I, Division 2, Groups A, B, C, D
Class I Zone 2 AEx ec IIC T5 Gc; Ex ec IIC T5 Gc
Power Requirements
DC Input
The power supply must be surge protected, otherwise external surge protection is
required at the input to the supply .
12-24 VDC (IEC Class I regulated power supply) Min . Output: 12 VDC @ 100 mA, 24 VDC @ 50 mA
Power Draw: 84 mA max @ 12 VDC; 42 mA max @ 24 VDC (Network AVT)
Power over EtherNet (PoE)
PoE (10/100), 15 mA, IEEE 802 .at (-af) Type 1 Class III PoE topology
Standards and Certifications
IEC / UL / CSA C22 .2 NO . 61010-1
IEC / UL / CSA C22 .2 NO . 61010-2-030
Safety requirements for electrical equipment for measurement, control, and laboratory use
UL 508 & CSA-C22 .2 No . 14
Industrial control equipment
FCC - CFR 47 Part 15 Subpart B
Radio frequency devices
CAN ICES-001
Industrial, scientific and medical (ISM) radio frequency generators
EN 55011, CISPR 11,
AS/NZS CISPR 11
Radio frequency disturbance characteristics
IEC 61326-1
EN 61326-1
EMC and immunity requirements
IEC / EN 61000-3-2, -3-3, -6-2
Electromagnetic compatibility (EMC)
CE
UKCA
Conformity Marking for European Economic Area
Conformity Marking for United Kingdom
RoHS
Restriction of hazardous substances
Absence of Voltage
Accessory
Ind. Cont. Eq.
E489576