Panduit VeriSafe VS2-NET Installation Manual Download Page 3

10/16/2022 

1006772, B21148_EN_rev1

System Overview

10/100 P

0

E

1A 1B    2A 2B  3A 3B

AVT 

DC Intput

AVT Connection

Voltage Presence

Contacts

Reset Button

(not shown)

Power Status

System Status

Network

Connection

Termination Resistor Switch

POWER INPUTS

DC Input

Network Connection (PoE)

 The power supply must be surge protected, otherwise 

external surge protection is required at the input to the supply .

 

„

IEC Class I regulated power supply

Min . Output:  12 VDC @ 100mA, 24 VDC @ 50mA

 

„

Connector / Wiring Requirements

Wire Range: AWG #24 - 14 SOL / STR (1 wire only)
Wire strip length: 9 .0mm (min) / 10 .0mm (max) 

 

„

10/100 PoE

 

„

IEEE 802 .3af Type 1 Class III PoE topology .

AVT CONNECTION

Provides power and communications to the AVT isolation module .  The connection features a pluggable screw terminal connector .

 

Only install the network module in the same electrical enclosure as the VeriSafe 2 .0 AVT isolation module .

Recommended Wiring

Connector Specifications

 

„

Connector / Wiring Requirements;

Wire Range: (1 wire): AWG #24 - 12 [2 .5mm2] SOL / STR
                    (2 wire): AWG #18 [1 .0mm2] SOL

                                  AWG #18 [1 .5mm2] STR

Wire strip length: 7 .0mm (min) / 8 .0mm (max)

Screw Drive Size:  M3x0 .5

Screw Torque Required:  5 .0 in-lb [0 .57 N-m] +/- 10%

VOLTAGE PRESENCE OUTPUTS

Reflects status of Voltage presence LEDs on the AVT indicator module . These outputs are updated every 2 seconds based on the state 

reported from the AVT isolation module . These outputs are not an indication of absence of voltage .

Output Specification

3 Solid-state Relay 

Output Contacts

Normally open, relays close when red AVT indicators are 

illuminated (see AVT manual for red indicator voltage thresholds)

Wire Size

AWG #26-16 AWG (0 .13 - 1 .3mm

2

) Solid/Stranded (1 wire only)

Isolation

5000 Vrms Input/Output

Voltage Rating

30V AC/DC

Current Rating

80 mA (max)

On-resistance

30 

Ω

Output schematic

1A
1B
2A
2B
3A
3B

1

2

Network 

Module

Isolation 

Module

 

„

The termination resistor 

switch below the AVT 

connection ports on the 

network module and AVT 

isolation module shall be 

positioned to the right 

(factory default) when 

facing the port

When using the network module with the 2 .0 AVT isolation module, the 

network module “AVT Connection” supplies power from the network module 

to the isolation module .  Therefore DO NOT apply an external power source 

to the 2 .0 AVT isolation module when used with the network module .  