Panduit VeriSafe VS2- AVT-3IF Instruction Manual Download Page 6

VeriSafe 2.0 AVT  

June 2022

Technical Specifications

WARNING

:

 Do

 

not use this product outside of the specified performance and environmental limits . 

Failure to comply with 

these specifications could result in product failure, personal injury, or death. 

WARNING

:

 

The VeriSafe 2 .0 AVT is designed for use in 50 or 60Hz AC electrical systems and DC electrical systems . The AVT 

should not be installed on sections of a circuit where the AVT is exposed to high frequency energy such as variable frequency 

drives (VFD) or other circuit elements generating high frequency energy (waveforms exhibiting high Electro-Magnetic Inter-

ference (EMI)) . For more information on where to position the VeriSafe 2 .0 AVT in VFD applications, see the Technical Note 

available on Panduit .com .

Environmental Ratings

Operating Temperature

-25°C to 60°C (-13°F to 140°F)

Storage Temperature

-45°C to 85°C (-49°F to 185°F)

Humidity

5 to 90% non-condensing; Rated 80% at 40°C (104°F), decreasing linearly to 50% at 60°C (140°F)

Pollution Degree

3 (Ordinary Locations); 2 (see Hazardous Locations Table for special requirements)

Altitude

Up to 5000 meters (16400 feet)

 

Applications

Electrical System

For use in 3-phase AC systems, single-phase AC systems and DC systems

Voltage Detection Range

Up to 1000 VAC (50 or 60 Hz), 1000 VDC

Absence of Voltage Threshold 3 V (See the Installation Considerations section for additional information)
Overvoltage Category

III (1000 V), IV (600 V)

Degree of Protection

Indicator Module:  for flat surface mounting in a TYPE (UL, NEMA and CSA) 1, 12, 13, 4, 4X, IP66, 

IP67 or IP69 enclosure .  Verify that the seal, o-rings and gaskets are clean to ensure proper sealing .
Isolation Module:  Open Type, IP20 .

 

 

Hazardous Locations

Special Conditions 

of Use

 

„

The equipment shall be installed in an enclosure that provides a degree of protection not less than 

IP 54 in accordance with IEC 60079-0 .

 

„

The enclosure must only be accessible with use of a tool .

Certificate Numbers 

(Hazardous Locations)

ATEX:   UL 22 ATEX 2608X
IECEx:  IECEx UL22 .0094X
UKEx:   UKEX UL22UKEX2482X

Isolation Module 

(Hazardous Location Ratings)

cULus:   Class I, Division 2, Groups A, B, C, D 

Class I Zone 2 AEx ec IIC T5 Gc; Ex ec T5 Gc

ATEX:   II 3G Ex ec IIC T5 Gc

IECEx:   Ex ec IIC T5 Gc

Voltage Indicator Modules 

(Hazardous Location Ratings)

cULus:   Class I, Division 2, Groups A, B, C, D 

Class II, Division 2, Groups F and G 

Class I Zone 2 AEx ic ec IIC T6 Gc; Ex ic ec IIC T6 Gc 

Zone 22 AEx tc IIIC T68°C Dc; Ex tc IIIC T68°C Dc

ATEX: 

  

II 3G Ex ic ec IIC T6 Gc 

 

II 3D Ex tc IIIC T68°C Dc

IECEx:   Ex ic ec IIC T6 Gc 

Ex tc IIIC T68°C Dc

 

Power Requirements

Battery

Industrial 3 .6 V Lithium .  Refer to Maintenance section for list of approved batteries .

Auxiliary (DC) Power

35 mA max @ 12 VDC; 17 mA max @ 24 VDC

Power over EtherNet (PoE)

PoE (10/100), 15 mA, IEEE 802 .at (-af) Type 1 Class III PoE topology

continued on next page

Summary of Contents for VeriSafe VS2- AVT-3IF

Page 1: ...upport Safety Information 2 Informations relatives à la sécurité 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of Voltage Outputs 5 Technical Specifications 6 7 Environmental Ratings Applications 6 Hazardous Locations AVT Power Requirements 6 AVT Quiescent Current Voltage Illumination Level 7 Functional Safety ...

Page 2: ... standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expose contents to water The AVT will not work with a standard alkaline 1 5 V AA battery Use only Panduit approved battery Use only 2 0 AVT system components system cable isolation module indicator module...

Page 3: ...nt une pile au lithium qui présente un risque d incendie d explosion et de brûlures graves Ne pas écraser recharger démonter incinérer ou chauffer la pile à plus de 85 C 185 F ni exposer son contenu à l eau Le VAT ne fonctionne pas avec une pile alcaline AA standard de 1 5 V Utiliser uniquement des piles approuvées par Panduit Utiliser uniquement les composants du système VAT 2 0 câble système mod...

Page 4: ...th or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an optional DC Power Input Recommended Wiring DC Input and Connector Specifications This connection features a pluggable screw terminal connector and is used for DC power input or connection to the network...

Page 5: ...indicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs for optional use with control systems These outputs are located on the isolation module These outputs are normally inactive and are only active when the green absence of voltage indicator is illumina...

Page 6: ...ld 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA and CSA 1 12 13 4 4X IP66 IP67 or IP69 enclosure Verify that the seal o rings and gaskets are clean to ensure proper sealing Isolation Module Open Type IP20 Hazardous Locations Special Conditions of ...

Page 7: ...rtifications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safety requirements for electrical equipment for measurement control and laboratory use UL 508 CSA C22 2 No 14 Industrial control equipment IEC 61508 1 2 and 3 SIL 3 Rating Functional safety of electric...

Page 8: ...cation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absence of Voltage Tester CAT IV 1000V CAT IV 600V _________ Follow safety procedures use required PPE 2 65 67 3 3 20 81 3 ISOLATION MODULE The Indicator Module is designed for use with a standard 30 mm kn...

Page 9: ...HIGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 L3 THREE PHASE WYE THREE PHASE WYE 3 WIRE PE NO NEUTRAL L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 THREE PHASE W...

Page 10: ... L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 DC SYSTEM ISOLATED GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 No Ground Bond ...

Page 11: ...de via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO NOT pierce or otherwise compromise the integrity of the conductor Connectors that require conductors to be cut or spliced can be used but may limit the SCCR USE OF OVERCURRENT PROTECTION Installation ...

Page 12: ...N MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatible fastener Surface mounting with screws is recommended for high vibration environments ATTACHING NETWORK MODULE TO ISOLATION MODULE OPTIONAL If mounting to isolation module use screws provided with ...

Page 13: ...osure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit as the electrical power conductors Battery Powered Battery Free BATTERY POWERED INDICATOR MODULE 1 Tighten the panel nut until both it and the gasket make full contact with the enclosure surface The...

Page 14: ... mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the test button to initiate the test The yellow caution indicator should flash rapidly to indicate the test is in progress followed by the absence of voltage...

Page 15: ...te the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators illuminate when the presence of hazardous voltage is detected Lack of red voltage pres ence indicators alone does not verify the absence of voltage VOLTAGE PRESENCE INDICATORS A When voltage is detect...

Page 16: ...as a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range 4 Proper installation of the sensor leads could not be verified WARNING The enclosure may be energized Follow safety procedures and use the appropriate PPE when verifying the enclosure is de energiz...

Page 17: ...r module to ensure the retention nut is tight and cap is firmly in place CLEANING INSTRUCTIONS The indicator module can be cleaned with a damp cloth or isopropyl alcohol based cleaner Do not use abrasives or high alka line cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures Before a wash down operation e...

Page 18: ...ICATOR MODULE For the battery free indicator module order Panduit SKU VS2 AVT GASKET for gasket replacement kit 1 Unplug the system cable and remove the panel nut 2 Squeeze the top and bottom of the housing and pull back to release the latches from the faceplate 3 Separate housing from faceplate and replace gasket Indicator Module Faceplate Instruction Label Indicator Module Housing Panel Nut Gask...

Page 19: ...er 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any third party software or firmware which may be incorporated into a Panduit product and or resold or sublicensed by Panduit To the extent any warranties extended to Panduit by the third party manufacturer ...

Reviews: