Panduit VeriSafe VS2- AVT-3IF Instruction Manual Download Page 12

VeriSafe 2.0 AVT  

12 

June 2022

Installation Instructions

Special 

Conditions 

of Use

Hazardous Locations

 

„

The equipment shall be installed in an enclosure that provides a degree of protection not less than IP 54 in accor-

dance with IEC 60079-0 .

 

„

The enclosure must only be accessible with use of a tool .

WARNING:

 

„

The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indi-

cation of absence of voltage . Sensor leads must not be mechanically connected with each other for the device to 

verify connection to the circuit . Correct function of the device must be verified after installation, see Commissioning 

Checklist section, p . 14 .

 

„

Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND) . Each 

conductor should have at least one sensor lead set, as shown on the schematic diagrams .

 

„

Excess length from Sensor Leads should be trimmed; lead wires should not be extended with a splice .  When using 

terminal or power distribution blocks, the total length of the sensor leads from the isolation module to the source 

conductors shall not exceed 10 feet (3 .0m) .

 

„

Always comply with local installation codes and standards .

 

„

Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment .

NOTE:

 Before installation, verify that after power is removed from the circuit to be monitored . The potential measured 

between each line and ground should be less than 2 .7V, including voltages on the line from auxiliary systems

 .

 

ISOLATION MODULE

NETWORK MODULE

DIN-RAIL MOUNTING 

Snap the Isolation Module 

onto the DIN rail .

   OR   SURFACE  MOUNTING

Mount the isolation module  

to any surface using four  

#6 [M3 .5] pan head  

screws or another  

compatible fastener .  

Surface mounting with  

screws is recommended  

for high vibration  

environments

 ATTACHING NETWORK MODULE TO ISOLATION 

MODULE (OPTIONAL)

If mounting 

to isolation 

module,  

use screws 

provided 

with 

network 

module .

SENSOR LEAD TERMINATION

1. 

Route the sensor and ground leads .

 

„

The sensor leads should not be any longer than necessary and should be routed to avoid sharp edges, pinch points or mechan-

ical damage .

 

„

There is no maximum distance limitation between the two leads on each phase, however there should not be any circuit ele-

ments installed between them .

 

„

Sensor leads should not be extended with a splice .  When using terminal or power distribution blocks, the total length of the 

sensor leads from the isolation module to the source conductors shall not exceed 10 feet (3 .0m) .

2. 

Terminate the sensor and ground leads .

 

„

Use of ferrules or terminals is recommended .

 

„

Sensor leads for each phase and ground must not be mechanically terminated at the same point for the AVT to function proper-

ly .

 

„

Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND) . Each conductor 

should have at least one sensor lead set, as shown on the schematic diagrams .

 

„

Secure the sensor leads to the conductors and insulate the connections .

AUXILIARY DC POWER (OPTIONAL)

If using DC power, connect the 12 or 24 VDC power source, see DC Power Input (page 4) .

  

The DC Power Input is marked for polarity; 

connect the positive output of the supply to the terminal marked (+) and the negative output of the supply to the terminal marked (-) .

Summary of Contents for VeriSafe VS2- AVT-3IF

Page 1: ...upport Safety Information 2 Informations relatives à la sécurité 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of Voltage Outputs 5 Technical Specifications 6 7 Environmental Ratings Applications 6 Hazardous Locations AVT Power Requirements 6 AVT Quiescent Current Voltage Illumination Level 7 Functional Safety ...

Page 2: ... standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expose contents to water The AVT will not work with a standard alkaline 1 5 V AA battery Use only Panduit approved battery Use only 2 0 AVT system components system cable isolation module indicator module...

Page 3: ...nt une pile au lithium qui présente un risque d incendie d explosion et de brûlures graves Ne pas écraser recharger démonter incinérer ou chauffer la pile à plus de 85 C 185 F ni exposer son contenu à l eau Le VAT ne fonctionne pas avec une pile alcaline AA standard de 1 5 V Utiliser uniquement des piles approuvées par Panduit Utiliser uniquement les composants du système VAT 2 0 câble système mod...

Page 4: ...th or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an optional DC Power Input Recommended Wiring DC Input and Connector Specifications This connection features a pluggable screw terminal connector and is used for DC power input or connection to the network...

Page 5: ...indicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs for optional use with control systems These outputs are located on the isolation module These outputs are normally inactive and are only active when the green absence of voltage indicator is illumina...

Page 6: ...ld 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA and CSA 1 12 13 4 4X IP66 IP67 or IP69 enclosure Verify that the seal o rings and gaskets are clean to ensure proper sealing Isolation Module Open Type IP20 Hazardous Locations Special Conditions of ...

Page 7: ...rtifications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safety requirements for electrical equipment for measurement control and laboratory use UL 508 CSA C22 2 No 14 Industrial control equipment IEC 61508 1 2 and 3 SIL 3 Rating Functional safety of electric...

Page 8: ...cation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absence of Voltage Tester CAT IV 1000V CAT IV 600V _________ Follow safety procedures use required PPE 2 65 67 3 3 20 81 3 ISOLATION MODULE The Indicator Module is designed for use with a standard 30 mm kn...

Page 9: ...HIGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 L3 THREE PHASE WYE THREE PHASE WYE 3 WIRE PE NO NEUTRAL L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 THREE PHASE W...

Page 10: ... L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 DC SYSTEM ISOLATED GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 No Ground Bond ...

Page 11: ...de via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO NOT pierce or otherwise compromise the integrity of the conductor Connectors that require conductors to be cut or spliced can be used but may limit the SCCR USE OF OVERCURRENT PROTECTION Installation ...

Page 12: ...N MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatible fastener Surface mounting with screws is recommended for high vibration environments ATTACHING NETWORK MODULE TO ISOLATION MODULE OPTIONAL If mounting to isolation module use screws provided with ...

Page 13: ...osure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit as the electrical power conductors Battery Powered Battery Free BATTERY POWERED INDICATOR MODULE 1 Tighten the panel nut until both it and the gasket make full contact with the enclosure surface The...

Page 14: ... mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the test button to initiate the test The yellow caution indicator should flash rapidly to indicate the test is in progress followed by the absence of voltage...

Page 15: ...te the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators illuminate when the presence of hazardous voltage is detected Lack of red voltage pres ence indicators alone does not verify the absence of voltage VOLTAGE PRESENCE INDICATORS A When voltage is detect...

Page 16: ...as a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range 4 Proper installation of the sensor leads could not be verified WARNING The enclosure may be energized Follow safety procedures and use the appropriate PPE when verifying the enclosure is de energiz...

Page 17: ...r module to ensure the retention nut is tight and cap is firmly in place CLEANING INSTRUCTIONS The indicator module can be cleaned with a damp cloth or isopropyl alcohol based cleaner Do not use abrasives or high alka line cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures Before a wash down operation e...

Page 18: ...ICATOR MODULE For the battery free indicator module order Panduit SKU VS2 AVT GASKET for gasket replacement kit 1 Unplug the system cable and remove the panel nut 2 Squeeze the top and bottom of the housing and pull back to release the latches from the faceplate 3 Separate housing from faceplate and replace gasket Indicator Module Faceplate Instruction Label Indicator Module Housing Panel Nut Gask...

Page 19: ...er 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any third party software or firmware which may be incorporated into a Panduit product and or resold or sublicensed by Panduit To the extent any warranties extended to Panduit by the third party manufacturer ...

Reviews: