VeriSafe 2.0 AVT
4
June 2022
System Configuration
COMPONENTS
1
2
3
2
3
4
Isolation Module
System Cable
Indicator Module
3.6V Battery Powered option shown
Battery Free option available
Instruction Label
Place a Label for
each Indicator used
1
2
4
3
Flashing - Test in Progress
Solid - Voltage may be Present
Equipment De-Energized, < 3V
Push Button to Begin Test
Hazardous Voltage Present
Line
Load
Other
_________
Tester location:
# Flashes
Description
1
2
4
5, 6, 7 or 8
Check Battery
Voltage above Threshold
Installation Not Verified
See User Manual
3
Temperature Out of Range
See Diagnostic Code for Status:
V
ERI
S
AFE 2.0
Absence of Voltage Tester
CAT IV (1000V), CAT IV (600V)
_________
Follow safety
procedures &
use required PPE
2.65
[67.3]
3.20
[81.3]
PART NUMBER IDENTIFICATION
VS2-AVT-XYZ-##
VS2-AVT
XY
Power System
Z
Indicator
##
System Cable
VeriSafe 2 .0 AVT
3P
= Three-Phase System
1P
= Single-Phase / DC System
F
= Battery Free Indicator
B
= Battery Powered Indicator
02
= 2’ (0 .6m) System Cable
08
= 8’ (2 .4m) System Cable
16
= 16’ (4 .8m) System Cable
NOTE:
Accessories are available for the VS2-AVT, refer to www .panduit .com .
POWER FOR AVT TEST
Battery
Auxiliary DC
Power over Ethernet (PoE)*
3 .6V lithium
industrial
battery .
Replace without
opening the
enclosure .
12 - 24 VDC
Must be available when main is de-energized .
Can be used with or without the network module* .
10/100 PoE
IEEE 802 .3af Type 1 Class III PoE topology .
*
Refer to network module instruction manual, available at www .panduit .com .
DC POWER INPUT
The 2 .0 AVT includes an optional DC Power Input .
Recommended Wiring
DC Input and Connector Specifications
This connection features a pluggable screw-
terminal connector and is used for DC power
input or connection to the network module
(optional) .
Approved Power Source Type: IEC Class I regulated power supply;
12 - 24 VDC, 50 mA (minimum) output
Power Requirement: 35 mA max @ 12 VDC; 17 mA max @ 24 VDC
Connector / Wiring Requirements;
Wire Range: (1 wire): AWG #24 - 12 [2 .5mm2] SOL / STR
(2 wire): AWG #18 [1 .0mm2] SOL
AWG #18 [1 .5mm2] STR
Wire strip length: 7 .0mm (min) / 8 .0mm (max)
Screw Drive Size: M3x0 .5
Screw Torque Required: 5 .0 in-lb [0 .57 N-m] +/- 10%
Flashing - Test in Progress
Solid - Voltage may be Present
Equipment De-Energized, < 3V
Push Button to Begin Test
Hazardous Voltage Present
Line
Load
Other
_________
Tester location:
# Flashes
Description
1
2
4
5, 6, 7 or 8
Check Battery
Voltage above Threshold
Installation Not Verified
See User Manual
3
Temperature Out of Range
See Diagnostic Code for Status:
V
ERI
S
AFE 2.0
Absence of Voltage Tester
CAT IV (1000V), CAT IV (600V)
_________
Follow safety
procedures &
use required PPE
2.65
[67.3]
3.20
[81.3]
4
1
2
Network
Module*
Isolation
Module
1
2
Network
Module*
Isolation
Module
+
A1
A2 B1 B2
AV
T
AUX
INDICA
TOR
DC P
ow
er I
nput
A
bsenc
e of
Voltage O
utputs
Pr
imar
y I
ndica
tor
M
odule I
nput
Sec
ond I
ndica
tor
M
odule I
nput
(optional)