![Panduit SynapSense 1167 Installation & Use Manual Download Page 31](http://html1.mh-extra.com/html/panduit/synapsense-1167/synapsense-1167_installation-and-use-manual_3462034031.webp)
31
Depending on the node type, values 1-7 correspond to the information shown in the table
below.
Logix
5000
Data
Sensor type:
EZ Node
(0x82)
EZH Node
(0x94)
EZH Door
Contact
(0x96)
Industrial
Node
(0x94)
Pressure
(0x13)
ThermaNode
(0x11)
Value
1
Temperature Temperature
Door
Status
Temperature
Differential
Pressure
Temp
Thermistor 1
Value
2
N/A
Humidity
N/A
Humidity
N/A
Temp
Thermistor 2
Value
3
N/A
N/A
N/A
N/A
N/A
Temp
Thermistor 3
Value
4
N/A
N/A
N/A
N/A
N/A
Temp
Thermistor 4
Value
5
N/A
N/A
N/A
N/A
N/A
Temp
Thermistor 5
Value
6
N/A
N/A
N/A
N/A
N/A
Temp
Thermistor 6
Value
7
N/A
N/A
N/A
N/A
N/A
Temp
Thermistor 7
Other Control Systems
The Industrial Gateway can also be integrated into a different control system by using an
Electronic Data Sheet (EDS). The EDS file is used by the network configuration tools to
help identify and commission a product on a network. The EDS file can be exported out
of the SynapSoft™ application.
For more information on how to install an EDS file and integrate a new device, see the
corresponding documentation of your control system vendor.
Specifications
This section describes the various technical specifications of the Industrial Gateway.
Operating temperature
(Non-Operating)
temperature
-20°C to 70°C
-45°C to 85°C
Thermal Shock
(Operating)
-20°C to 70°C, 3°C/ Min.
Dust, Water Ingress
IP67
Operating humidity
Storage humidity
5% to 85% non-condensing
5% to 95% non-condensing
Operating altitude
0 - 6,562 ft. (0 - 2000m)
Vibration
2g @ 57 to 500Hz, Tested at 12milpp Displacement
Operating shock
(Non-operating) Shock
30g
50g
Summary of Contents for SynapSense 1167
Page 1: ...SynapSense 2 4GHz Industrial Gateway Model 1167 Installation Use Manual ...
Page 2: ...SynapSense 2 4GHz Industrial Gateway Hardware Installation Manual 2 Release 0v6 Issue 1 ...
Page 6: ...SynapSense 2 4GHz Industrial Gateway Hardware Installation Manual 6 ...
Page 18: ...SynapSense 2 4GHz Industrial Gateway Hardware Installation Manual 18 ...
Page 29: ...29 Once the nodes are running data can be viewed in the Device Map tab ...
Page 36: ...36 ...