69
Wire Stripping and Connecting Requirement
11.2.5.1
11.2.6 Pipe Insulation
1 Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2 If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 6 mm or above.
Wire stripping
5 mm or more
(gap between wires)
No loose strand when insert
Indoor/outdoor
connecting terminal
board
10
±
1
mm
ACCEPT
Conductor over
insert
Conductor not
fully insert
Conductor fully
insert
PROHIBITED
PROHIBITED
(For UD07*E5* and UD09*E5* only)
•
Select required direction and apply protective bushing provided in accessories to protect cables from sharp edges.
•
Once all wiring work has been completed, tie the cable and cord together with the binding strap so that they do not touch other parts such as the
compressor and bare copper pipes.
Outdoor Unit
Banding strap
3
Cord clamp
Terminal Board
Connecting cable
(refer below
diagram for its
guiding)
Selection
of direction
Protective
bushing
4
Apply cut
DETAIL OF CONNECTING CABLE GUIDING