13.1.7.2
Cooling Priority NOT SET
1. 3 ways valve control:
3 ways valve switch to room side during room cooling interval and switch to tank side during tank heat-up
interval. Both modes will switch alternately. Tank mode is the initial running mode of this cool + tank mode.
2. Heat pump operation control:-
a) During room cooling interval
Follow normal cooling operation.
Under Solar Priority Set condition:
Switch to tank heat-up interval and start tank heat-up timer when External Room Thermo OFF
AND
solar
3WV OFF
AND
Tank temperature < THERMO ON TEMP (End Room Interval Early)
OR
Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature < THERMO
ON TEMP
AND
solar 3VW OFF.
Under Solar Priority Not Set Condition:
Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo OFF
AND
Tank temperature < THERMO ON TEMP (End Room Interval Early)
OR
Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature < THERMO
ON TEMP.
* THERMO ON TEMP is defined from following tank thermo ON/OFF condition.
b) During tank heat-up interval
Tank water set temperature = tank set temperature or 55°C whichever lower.
Heat Pump Water Outlet set temperature is set to [53°C].
Initial Tank THERMO ON TEMP = heat pump tank target tempe [-2°C].
Tank Thermo ON/OFF characteristic
o
THERMO OFF TEMP:
1)
THERMO OFF TEMP = Tank water set tempe [0°].
2)
Tank temperature > THERMO OFF TEMP for continuous 10 seconds, 3 ways valve is switch to
room side. End Tank heat-up interval and start count cooling interval.
3)
Tank temperature > Tank set tempe [2°] for continuously 10 seconds, 3 ways valve is
switch to room side. End Tank heat-up interval and start count cooling interval.
o
THERMO ON TEMP:
1)
THERMO ON TEMP = Tank water set tempe [-2°C].
2)
During cooling interval or external room thermo OFF, always detect tank temperature.
Switch to next tank heat-up interval when tank temperature < THERMO ON TEMP.
Case 2:
o
Heat pump THERMO OFF TEMP:
1)
Heat pump THERMO OFF TEMP = [53°C] + [+4°C].
2)
Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump
OFF.
o
THERMO ON TEMP:
1)
THERMO ON TEMP = Water inlet when heat pump thermo OFF + [-3°C].