13.1.9 Water Temperature Thermo Shift Setting
Switchs are ignored during “PUMPDW” = ON.
Switchs are ignored during “STATUS” = ON.
“
▲
”, “
▼
”, ”SELECT” switch are ignored if “SETTING” = OFF.
“CANCEL” switch is ignored if “SETTING” = OFF & “STATUS” = OFF.
If “SET” Switch pressed for less than 5secs, immediately enter water temperature shift setting mode.
Once enter this setting mode, “SETTING” display is ON.
This setting mode is used to easily shift the target water outlet temperature.
Outdoor
Temp.
Water
Temp.
H2O HI
+ 5
± 0
Shift value
- 5
H2O LO
OUT LO
OUT HI
OUT LO
= Low outdoor ambient set temperature
OUT HI
= High outdoor ambient set temperature
H2O LO
= Water outlet set temperature at low
outdoor ambient set temperature
H2O HI
= Water outlet set temperature at high
outdoor ambient set temperature
Shift value = Setting water temperature thermo shift
13.1.10
Outdoor Fan Motor Operation
Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it
stops 30 seconds after compressor stops operation.
30 sec
Compressor:
ON
ON
Fan Speed
ON
ON
OFF
OFF
Outdoor Fan: