129
17.5.20
Outdoor Fan Motor (DC Motor) Mechanism Locked (F15)
Malfunction Decision Conditions:
The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine
abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm).
Malfunction Caused:
1 Operation stop due to short circuit inside the fan motor winding.
2 Operation stop due to breaking of wire inside the fan motor.
3 Operation stop due to breaking of fan motor lead wires.
4 Operation stop due to fan motor Hall IC malfunction.
5 Operation error due to faulty outdoor unit PCB.
Abnormality Judgment:
Continue 2 times in 30 minutes.
Summary of Contents for WH-SDC12F6E5
Page 24: ...24 4 2 Outdoor Unit Air inlet rear Air outlet Air inlet side ...
Page 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Page 63: ...63 57 C 57 C 57 C 57 C ...
Page 64: ...64 ...
Page 70: ...70 ...
Page 71: ...71 ...
Page 72: ...72 57 C 57 C 50 C 50 C ...