70
Buffer tank connection
Thermistor
Buffer tank
Pump
Floor heating
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Buffer Tank connection - Yes
T for buffer tank
Mono bloc
This is an application that connects the buffer tank to the Mono bloc.
Buffer tank’s temperature is detected by buffer tank thermistor (specified by Panasonic).
This system requires optional PCB (CZ-NS4P).
Buffer tank + Solar
Solar thermistor
Thermistor
Solar pump
Mixing valve
Floor heating
Pump
Buffer tank
Mono bloc
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Buffer Tank connection - Yes
T for buffer tank
Solar connection - Yes
Buffer tank
T turn ON
T turn OFF
Antifreeze
Hi limit
This is an application that connects the buffer tank to the Mono bloc before connecting to the solar water heater to
heat up the tank.
Buffer tank’s temperature is detected by buffer tank thermistor (specified by Panasonic).
Solar panel’s temperature is detected by solar thermistor (specified by Panasonic).
Buffer tank shall use tank with built-in solar heat exchange coil independently.
During winter season, solar pump for circuit protection will be activated continuously. If does not want to activate the
solar pump operation, please use glycol and set the anti-freezing operation start temperature to -20°C.
Heat accumulation operates automatically by comparing the temperature of tank thermistor and solar thermistor.
This system requires optional PCB (CZ-NS4P).